$ 369.60
Inosaki – Your Trusted Phoenix Contact Distributor
Inosaki proudly stands as one of the largest distributors of Phoenix Contact products, offering a comprehensive range of terminal blocks, interface modules, power supplies, and relays.
Series Models: PT Series, ST Series, TB Series, UT Series, and UK Series, PTV Series, UKH Series, Micro Series.
Discover industry-leading Phoenix Contact power supplies, such as:
Get Your Phoenix Contact Catalog Today
Need detailed product information? Contact us at sales@inosaki.com to request your Phoenix Contact catalog.
The fourth generation of the high-performance QUINT POWER power supplies ensures superior system availability by means of new functions. Signaling thresholds and characteristic curves can be individually adjusted via the NFC interface.
The unique SFB technology and preventive function monitoring of the QUINT POWER power supply increase the availability of your application.
Article Number | 2904608 |
---|---|
Width | 50 mm |
Height | 130 mm |
Depth | 125 mm |
Width with alternative assembly | 122 mm |
Height with alternative assembly | 130 mm |
Depth with alternative assembly | 53 mm |
Installation distance right/left | 5 mm / 5 mm |
Installation distance top/bottom | 50 mm / 50 mm |
Degree of protection | IP20 |
---|---|
Inflammability class in acc. with UL 94 (housing / terminal blocks) | V0 |
Ambient temperature (operation) | -25 °C … 70 °C (> 60 °C Derating: 2,5 %/K) |
Ambient temperature (start-up type tested) | -40 °C |
Ambient temperature (storage/transport) | -40 °C … 85 °C |
Max. permissible relative humidity (operation) | ≤ 95 % (at 25 °C, non-condensing) |
Climatic class | 3K3 (in acc. with EN 60721) |
Degree of pollution | 2 |
Installation height | ≤ 5000 m (> 2000 m, observe derating) |
Nominal input voltage range | 100 V AC … 240 V AC |
---|---|
110 V DC … 250 V DC | |
Input voltage range | 100 V AC … 240 V AC -15 % … +10 % |
110 V DC … 250 V DC -18 % … +40 % | |
Dielectric strength maximum | 300 V AC 60 s |
AC frequency range | 50 Hz … 60 Hz -10 % … +10 % |
Frequency range (fN) | 50 Hz … 60 Hz -10 % … +10 % |
16.7 Hz (acc. to EN 50163) | |
Discharge current to PE | < 3.5 mA |
Current consumption | 2.4 A (100 V AC) |
1.9 A (120 V AC) | |
1.1 A (230 V AC) | |
1.1 A (240 V AC) | |
Nominal power consumption | 221 VA |
Inrush current | typ. 15 A (at 25 °C) |
Mains buffering time | typ. 55 ms (120 V AC) |
typ. 56 ms (230 V AC) | |
Input fuse | 8 A (slow-blow, internal) |
Recommended breaker for input protection | 10 A … 16 A (Characteristic B, C, D, K or comparable) |
Type of protection | Transient surge protection |
Protective circuit/component | Varistor, gas-filled surge arrester |
Nominal output voltage | 12 V DC |
---|---|
Setting range of the output voltage (USet) | 12 V DC … 15 V DC (constant capacity) |
Nominal output current (IN) | 15 A |
Static Boost (IStat.Boost) | 17.5 A |
Dynamic Boost (IDyn.Boost) | 20 A (5 s) |
Selective Fuse Breaking (ISFB) | 60 A (15 ms) |
Derating | > 60 °C … 70 °C (2.5%/K) |
Connection in parallel | yes, for redundancy and increased capacity |
Connection in series | yes |
Feedback voltage resistance | ≤ 25 V DC |
Protection against overvoltage at the output (OVP) | ≤ 18 V DC |
Control deviation | < 0.5 % (Static load change 10 % … 90 %) |
< 4 % (Dynamic load change 10 % … 90 %, (10 Hz)) | |
< 0.25 % (change in input voltage ±10 %) | |
Residual ripple | < 70 mVPP (with nominal values) |
Output power | 180 W |
Typical response time | 300 ms (from SLEEP MODE) |
Maximum power dissipation in no-load condition | < 4 W (120 V AC) |
< 4 W (230 V AC) | |
Power loss nominal load max. | < 18 W (120 V AC) |
< 16 W (230 V AC) |
Net weight | 1 kg |
---|---|
Environmental protection directive | RoHS Directive 2011/65/EU |
WEEE | |
Reach | |
Efficiency | typ. 91.2 % (120 V AC) |
typ. 92 % (230 V AC) | |
MTBF (IEC 61709, SN 29500) | > 1196000 h (25 °C) |
> 749000 h (40 °C) | |
> 355000 h (60 °C) | |
Insulation voltage input/output | 4 kV AC (type test) |
2 kV AC (routine test) | |
Insulation voltage input / PE | 3.5 kV AC (type test) |
2.4 kV AC (routine test) | |
Insulation voltage output / PE | 0.5 kV DC (type test) |
0.5 kV DC (routine test) | |
Degree of protection | IP20 |
Protection class | I |
Inflammability class in acc. with UL 94 (housing / terminal blocks) | V0 |
Mounting position | horizontal DIN rail NS 35, EN 60715 |
Assembly instructions | alignable: PN ≥50%, 5 mm horizontally, 15 mm next to active components, 50 mm vertically alignable: PN <50%, 0 mm horizontally, 40 mm vertically top, 20 mm vertically bottom |
Connection method | Screw connection |
---|---|
Conductor cross section solid min. | 0.2 mm² |
Conductor cross section solid max. | 2.5 mm² |
Conductor cross section flexible min. | 0.2 mm² |
Conductor cross section flexible max. | 2.5 mm² |
Conductor cross section AWG min. | 24 |
Conductor cross section AWG max. | 14 |
Stripping length | 6.5 mm |
Connection method | Screw connection |
---|---|
Conductor cross section solid min. | 0.2 mm² |
Conductor cross section solid max. | 2.5 mm² |
Conductor cross section flexible min. | 0.2 mm² |
Conductor cross section flexible max. | 2.5 mm² |
Conductor cross section AWG min. | 24 |
Conductor cross section AWG max. | 14 |
Stripping length | 6.5 mm |
Connection method | Push-in connection |
---|---|
Conductor cross section solid min. | 0.2 mm² |
Conductor cross section solid max. | 1 mm² |
Conductor cross section flexible min. | 0.2 mm² |
Conductor cross section flexible max. | 1.5 mm² |
Conductor cross section AWG min. | 24 |
Conductor cross section AWG max. | 16 |
Stripping length | 8 mm |
EMC requirements for noise immunity | EN 61000-6-1 |
---|---|
EN 61000-6-2 | |
EMC requirements for noise emission | EN 61000-6-3 |
EN 61000-6-4 | |
EMC requirements, power plant | IEC 61850-3 |
EN 61000-6-5 | |
HART FSK Physical Layer Test Specification Compliance | Output voltage UOut compliant |
Standard – Safety of transformers | EN 61558-2-16 |
Standard – Electrical safety | IEC 61010-2-201 (SELV) |
Standard – safety for equipment for measurement, control, and laboratory use | IEC 61010-1 |
Standard – Safety extra-low voltage | IEC 61010-1 (SELV) |
IEC 61010-2-201 (PELV) | |
Standard – Safe isolation | IEC 61558-2-16 |
Standard – Limitation of mains harmonic currents | EN 61000-3-2 |
Mains variation/undervoltage | SEMI F47-0706, EN 61000-4-11 |
Rail applications | EN 50121-3-2 |
EN 50121-4 | |
EN 50121-5 | |
IEC 62236-3-2 | |
IEC 62236-4 | |
IEC 62236-5 | |
Overvoltage category EN 61010-1 | II (≤ 5000 m) |
Overvoltage category EN 62477-1 | III (≤ 2000 m) |
UL approvals | UL Listed UL 508 |
---|---|
UL/C-UL Recognized UL 60950-1 | |
UL ANSI/ISA-12.12.01 Class I, Division 2, Groups A, B, C, D (Hazardous Location) | |
CSA | CAN/CSA-C22.2 No. 60950-1-07 |
CSA-C22.2 No. 107.1-01 |
Electromagnetic compatibility | Conformance with EMC Directive 2014/30/EU |
---|---|
Low Voltage Directive | Conformance with Low Voltage Directive 2014/35/EC |
Conducted noise emission | EN 55016 |
EN 61000-6-3 (Class B) | |
Noise emission | EN 55016 |
EN 61000-6-3 (Class B) | |
Harmonic currents | EN 61000-3-2 |
EN 61000-3-2 (Class A) | |
Flicker | EN 61000-3-3 |
EN 61000-3-3 | |
Electrostatic discharge | EN 61000-4-2 |
Contact discharge | 8 kV (Test Level 4) |
Discharge in air | 15 kV (Test Level 4) |
Electromagnetic HF field | EN 61000-4-3 |
Frequency range | 80 MHz … 1 GHz |
Test field strength | 20 V/m (Test Level 3) |
Frequency range | 1 GHz … 6 GHz |
Test field strength | 10 V/m (Test Level 3) |
Frequency range | 1 GHz … 6 GHz |
Test field strength | 10 V/m (Test Level 3) |
Comments | Criterion A |
Fast transients (burst) | EN 61000-4-4 |
Input | 4 kV (Test Level 4 – asymmetrical) |
Output | 4 kV (Test Level 4 – asymmetrical) |
Signal | 4 kV (Test Level 4 – asymmetrical) |
Comments | Criterion A |
Input | 3 kV (Test Level 4 – symmetrical) |
6 kV (Test Level 4 – asymmetrical) | |
Output | 0.5 V (Test Level 2 – symmetrical) |
2 kV (Test Level 3 – asymmetrical) | |
Signal | 4 kV (Test Level 4 – asymmetrical) |
Comments | Criterion A |
Conducted interference | EN 61000-4-6 |
I/O/S | asymmetrical |
Frequency range | 0.15 MHz … 80 MHz |
Voltage | 10 V (Test Level 3) |
Comments | Criterion A |
Power frequency magnetic field | EN 61000-4-8 |
Frequency | 16.7 Hz |
50 Hz | |
60 Hz | |
Test field strength | 100 A/m |
Additional text | 60 s |
Comments | Criterion A |
Frequency | 50 Hz |
60 Hz | |
Frequency range | 50 Hz … 60 Hz |
Test field strength | 1 kA/m |
Additional text | 3 s |
Frequency | 0 Hz |
Test field strength | 300 A/m |
Additional text | DC, 60 s |
Voltage dips | EN 61000-4-11 |
Voltage | 230 V AC |
Frequency | 50 Hz |
Voltage dip | 70 % |
Number of periods | 0.5 / 1 / 25 periods |
Additional text | Test Level 2 |
Comments | Criterion A: 0.5 / 1 / 25 periods |
Voltage dip | 40 % |
Number of periods | 5 / 10 / 50 periods |
Additional text | Test Level 2 |
Comments | Criterion A |
Voltage dip | 0 % |
Number of periods | 0,5 / 1 / 5 / 50 / 250 periods |
Additional text | Test Level 2 |
Comments | Criterion A: 0.5 / 1 period Criterion B: 5 / 50 / 250 periods |
Pulse-shape magnetic field | EN 61000-4-9 |
Test field strength | 1000 A/m |
Comments | Criterion A |
Damped oscillating magnetic field | EN 61000-4-10 |
Test field strength | 110 A/m |
Test level 1 | 100 kHz |
Test field strength | 110 A/m |
Test level 2 | 1 MHz |
Comments | Criterion A |
Attenuated sinusoidal oscillations (ring wave) | EN 61000-4-12 |
Input | 2 kV (Test Level 4 – symmetrical) |
4 kV (Test Level 4 – asymmetrical) | |
Comments | Criterion A |
Asymmetrical conducted disturbance variables | EN 61000-4-16 |
Test level 1 | 15 Hz 150 Hz (Test Level 4) |
Voltage | 30 V 3 V |
Test level 2 | 150 Hz 1.5 kHz (Test Level 4) |
Voltage | 3 V |
Test level 3 | 1.5 kHz 15 kHz (Test Level 4) |
Voltage | 3 V 30 V |
Test level 4 | 15 kHz 150 kHz (Test Level 4) |
Voltage | 30 V |
Test level 5 | 16.7 Hz 50 Hz 60 Hz (Test Level 4) |
Voltage | 30 V (Permanent) |
Test level 6 | 16.7 Hz 50 Hz 60 Hz (Test Level 4) |
Voltage | 300 V (1 s) |
Comments | Criterion A |
Attenuated oscillating wave | EN 61000-4-18 |
Input, output (test level 1) | 100 kHz 1 MHz (Test Level 3 – symmetrical) |
Voltage | 1 kV |
Input, output (test level 2) | 10 MHz |
Voltage | 1 kV |
Input, output (test level 3) | 100 kHz 1 MHz (Test Level 3 – asymmetrical) |
Voltage | 2.5 kV |
Signals (test level 1) | 100 kHz 1 MHz (Test Level 3 – symmetrical) |
Voltage | 1 kV |
Signals (test level 2) | 100 kHz 1 MHz (Test Level 3 – asymmetrical) |
Voltage | 2.5 kV |
Comments | Criterion A |
Criterion A | Normal operating behavior within the specified limits. |
Criterion B | Temporary impairment to operational behavior that is corrected by the device itself. |
Criterion C | Temporary adverse effects on the operating behavior, which the device corrects automatically or which can be restored by actuating the operating elements. |
REACh SVHC | Lead 7439-92-1 |
---|---|
China RoHS | Environmentally Friendly Use Period = 25; |
For details about hazardous substances go to tab “Downloads”, Category “Manufacturer’s declaration” |
INOSAKI Limited
RM B 5/F Gaylord Comm,
Bldg 114-118 Lockhart Rd.
Hong Kong
INOSAKI Sdn. Bhd.
2-1-9, Ground Floor, One Square, Tingkat Mahsuri 1,
11900 Bayan Lepas, Penan
INOSAKI Pte. Ltd.
101 Upper Cross Street,
No. 06-17, People’s Park Centre,
Singapore (058357)