Inosaki is one of the largest Phoenix Contact Distributors to provide terminal block, interface module, power supply and relay. And our best offer for terminal block types are Feed-through, Fuse Modular, Spring Cage, Double Level, and Multi-level, hence the series model references to PT Series, ST Series, TB Series, UT Series, UK Series. In additional for power supply are QUINT Power, STEP Power, Trio Power, and UNO Power. Please email us for catalog: sales@inosaki.my
Product Description
QUINT POWER power supplies with maximum functionality
QUINT POWER circuit breakers magnetically and therefore quickly trip at six times the nominal current, for selective and therefore cost-effective system protection. The high level of system availability is additionally ensured, thanks to preventive function monitoring, as it reports critical operating states before errors occur.
Reliable starting of heavy loads takes place via the static power reserve POWER BOOST. Thanks to the adjustable voltage, all ranges between 5 V DC … 56 V DC are covered.
Dimensions
Article Number |
2320827 |
Width |
96 mm |
Height |
130 mm |
Depth |
179 mm |
Width with alternative assembly |
176 mm |
Height with alternative assembly |
130 mm |
Depth with alternative assembly |
99 mm |
Ambient conditions
Degree of protection |
IP20 |
Ambient temperature (operation) |
-25 °C … 70 °C (> 60 °C Derating: 2,5 %/K) |
Ambient temperature (start-up type tested) |
-40 °C |
Ambient temperature (storage/transport) |
-40 °C … 85 °C |
Max. permissible relative humidity (operation) |
≤ 95 % (at 25 °C, non-condensing) |
Climatic class |
3K3 (in acc. with EN 60721) |
Degree of pollution |
2 |
Installation height |
4000 m |
Input data
Nominal input voltage range |
3x 400 V AC … 500 V AC |
Input voltage range |
3x 320 V AC … 575 V AC |
|
2x 360 V AC … 575 V AC (Not approved by UL) |
|
450 V DC … 800 V DC |
AC frequency range |
45 Hz … 65 Hz |
Frequency range DC |
0 Hz |
Discharge current to PE |
< 3.5 mA |
Current consumption |
3x 2.1 A (400 V AC) |
|
3x 1.7 A (500 V AC) |
|
1.7 A (600 V DC) |
Nominal power consumption |
1386 VA |
Inrush current |
< 20 A (typical) |
Mains buffering time |
typ. 25 ms (400 V AC) |
|
typ. 35 ms (500 V AC) |
Recommended breaker for input protection |
6 A … 16 A (AC: Characteristics B, C, D, K) |
Type of protection |
Transient surge protection |
Protective circuit/component |
Varistor |
Output data
Nominal output voltage |
48 V DC ±1 % |
Setting range of the output voltage (USet) |
30 V DC … 56 V DC (> 48 V DC, constant capacity restricted) |
Nominal output current (IN) |
20 A (-25 °C … 60 °C, UOUT = 48 V DC) |
POWER BOOST (IBoost) |
22.5 A (-25 °C … 40 °C permanent, UOUT = 48 V DC ) |
Selective Fuse Breaking (ISFB) |
100 A (12 ms) |
Derating |
60 °C … 70 °C (2.5%/K) |
Connection in parallel |
yes, for redundancy and increased capacity |
Connection in series |
yes |
Feedback voltage resistance |
max. 60 V DC |
Protection against overvoltage at the output (OVP) |
< 60 V DC |
Active current limitation |
Approx. IBOOST = 22.5 A (for short-circuit) |
Control deviation |
< 1 % (change in load, static 10 % … 90 %) |
|
< 4 % (change in load, dynamic 10 % … 90 %) |
|
< 0.1 % (change in input voltage ±10 %) |
Residual ripple |
< 50 mVPP (with nominal values) |
Output power |
960 W |
Typical response time |
< 1 s |
Maximum power dissipation in no-load condition |
24 W |
Power loss nominal load max. |
70 W |
General
Net weight |
2.5 kg |
Efficiency |
> 93 % (at 400 V AC and nominal values) |
MTBF (IEC 61709, SN 29500) |
> 890000 h (25 °C) |
|
> 509000 h (40 °C) |
|
|
Insulation voltage input/output |
4 kV AC (type test) |
|
2 kV AC (routine test) |
Insulation voltage input / PE |
3.5 kV AC (type test) |
|
2 kV AC (routine test) |
Insulation voltage output / PE |
500 V DC (routine test) |
Degree of protection |
IP20 |
Protection class |
I |
Housing material |
Steel sheet, zinc-plated |
Mounting position |
horizontal DIN rail NS 35, EN 60715 |
Assembly instructions |
alignable: PN ≥50%, 5 mm horizontally, 15 mm next to active components, 50 mm vertically
alignable: PN <50%, 0 mm horizontally, 40 mm vertically top, 20 mm vertically bottom |
Connection data, input
Connection method |
Screw connection |
Conductor cross section solid min. |
0.2 mm² |
Conductor cross section solid max. |
6 mm² |
Conductor cross section flexible min. |
0.2 mm² |
Conductor cross section flexible max. |
4 mm² |
Conductor cross section AWG min. |
18 |
Conductor cross section AWG max. |
10 |
Stripping length |
7 mm |
Screw thread |
M3 |
Connection data, output
Connection method |
Screw connection |
Conductor cross section solid min. |
0.5 mm² |
Conductor cross section solid max. |
16 mm² |
Conductor cross section flexible min. |
0.5 mm² |
Conductor cross section flexible max. |
16 mm² |
Conductor cross section AWG min. |
8 |
Conductor cross section AWG max. |
6 |
Stripping length |
10 mm |
Screw thread |
M3 |
Connection data for signaling
Connection method |
Screw connection |
Conductor cross section solid min. |
0.2 mm² |
Conductor cross section solid max. |
6 mm² |
Conductor cross section flexible min. |
0.2 mm² |
Conductor cross section flexible max. |
4 mm² |
Conductor cross section AWG min. |
18 |
Conductor cross section AWG max. |
10 |
Screw thread |
M3 |
Standards
EMC requirements for noise immunity |
EN 61000-6-1 |
|
EN 61000-6-2 |
EMC requirements for noise emission |
EN 61000-6-3 |
|
EN 61000-6-4 |
Standard – Safety of transformers |
IEC 61558-2-17 |
Standard – Electrical safety |
IEC 61010-2-201 (SELV) |
Standard – safety for equipment for measurement, control, and laboratory use |
IEC 61010-1 |
Standard – Safety extra-low voltage |
IEC 61010-1 (SELV) |
|
IEC 61010-2-201 (PELV) |
Standard – Safe isolation |
IEC 61010-2-201 |
Standard – Protection against shock currents, basic requirements for protective separation in electrical equipment |
EN 50178 |
Standard – Limitation of mains harmonic currents |
EN 61000-3-2 |
Standard – Equipment safety |
BG (design tested) |
Standard – Approval for medical use |
IEC 60601-1, 2 x MOOP |
Rail applications |
EN 50121-4 |
|
EN 50121-3-2 |
Overvoltage category EN 62477-1 |
III |
Conformance/approvals
UL approvals |
UL Listed UL 508 |
|
UL/C-UL Recognized UL 60950-1 (3-wire + PE, star net) |
|
UL ANSI/ISA-12.12.01 Class I, Division 2, Groups A, B, C, D (Hazardous Location) |
CSA |
CAN/CSA-C22.2 No. 60950-1-07 |
|
CSA-C22.2 No. 107.1-01 |
EMC data
Electromagnetic compatibility |
Conformance with EMC Directive 2014/30/EU |
Low Voltage Directive |
Conformance with Low Voltage Directive 2014/35/EC |
Electrostatic discharge |
EN 61000-4-2 |
Contact discharge |
8 kV (Test Level 4) |
Discharge in air |
15 kV (Test Level 4) |
Electromagnetic HF field |
EN 61000-4-3 |
Frequency range |
80 MHz … 1 GHz |
Test field strength |
20 V/m (Test Level 3) |
Frequency range |
1 GHz … 2 GHz |
Test field strength |
10 V/m (Test Level 3) |
Frequency range |
2 GHz … 3 GHz |
Test field strength |
10 V/m (Test Level 3) |
Comments |
Criterion A |
Fast transients (burst) |
EN 61000-4-4 |
Input |
4 kV (Test Level 4 – asymmetrical) |
Output |
2 kV (Test Level 3 – asymmetrical) |
Signal |
2 kV (Test Level 4 – asymmetrical) |
Comments |
Criterion A |
Surge voltage load (surge) |
EN 61000-4-5 |
Input |
2 kV (Test Level 3 – symmetrical) |
|
6 kV (Test Level 4 – asymmetrical) |
Output |
1 kV (Test Level 2 – symmetrical) |
|
2 kV (Test Level 3 – asymmetrical) |
Signal |
1 kV (Test Level 2 – asymmetrical) |
Comments |
Criterion A |
Conducted interference |
EN 61000-4-6 |
I/O/S |
asymmetrical |
Frequency range |
0.15 MHz … 80 MHz |
Voltage |
10 V (Test Level 3) |
Comments |
Criterion A |
Criterion A |
Normal operating behavior within the specified limits. |
Criterion B |
Temporary impairment to operational behavior that is corrected by the device itself. |
Environmental Product Compliance
REACh SVHC |
Lead 7439-92-1 |
China RoHS |
Environmentally Friendly Use Period = 25; |
|
For details about hazardous substances go to tab “Downloads”, Category “Manufacturer’s declaration” |