Main information
|
|
| Part Number | XCSP3902P20 |
| Product Series | Telemecanique Safety switches XCS |
| product type | Safety limit switch |
| component name | XCSP |
| design | Compact |
| Material | Plastic |
| Control head type | Direct acting head |
| protection technology | Protective plastic cover, secured with 5 leaf-shaped hexagonal security screws |
| operator type | Steel roller direct acting |
| Contact type and composition | 1 NC + 1 NC + 1 NO |
| contact action | Momentary |
| cable entry hole | 1 The cable entry with hole is suitable for M20 x 1.5 |
| Additional information | |
| Electrical connections | Terminal |
| locking force | 1 x 0.34…2 x 0.75 mm² |
| switch trigger | 30° lip |
| number of poles | 3 |
| force open | With NC contact |
| Mechanical life | 10000000 times |
| Minimum trip force | 12N |
| force open minimum force | 36 N |
| operating speed | 0.5 m/s |
| Contact wire regulation grade | B300, AC-15 (Ue = 240 V, Ie = 1.5 A) conforming to EN/IEC 60947-5-1 Annex A |
| R300, DC-13 (Ue = 250 V, Ie = 0.1 A) conforming to EN/IEC 60947-5 -1 Appendix A | |
| Conventional enclosed heating current [Ithe] | 6A |
| Rated insulation voltage [Ui] | 300 V according to UL 508 |
| 400 V (pollution degree 3) according to EN/IEC 60947-1 | |
| 300 V according to CSA C22.2 No 14 | |
| Rated impulse withstand voltage [Uimp] | 4 kV according to EN/IEC 60947-1 |
| 4 kV according to IEC 60664 | |
| Maximum resistance across terminals | 25 MΩ conforming to IEC 60255-7 Safety Class 3 |
| Short circuit protection | 6 A fuse type gG (gl) |
| Repeatability | 0.1mm above the trip point, the direct-acting operating head can perform 1 million working cycles |
| body material | Plastic |
| head material | Zamak |
| Cabinet material | Plastic |
| depth | 35 mm |
| high | 100 mm |
| width | 34mm |
| product weight | 0.255 kg |
| Environment | |
| Standards compliant | UL 508 |
| EN/IEC 60947-5-1 | |
| EN/IEC 60204-1 | |
| EN 1088/ISO 14119 | |
| CSA C22.2 No 14 | |
| certified product | UL |
| CSA | |
| Security Level | Category 4 can be achieved with appropriate monitoring system and correct wiring according to EN/ISO 13849-1 |
| PL = e can be achieved with appropriate monitoring system and correct wiring according to EN/ISO 13849-1 | |
| SIL 3 can be achieved with appropriate monitoring system and correct wiring according to IEC 61508 | |
| Safe and reliable data | B10d = 50000000 Value determined by 20 years life time, limited by mechanical or contact wear |
| Protective treatment | TC |
| operating temperature | -25…70°C |
| storage environment temperature | -40…70°C |
| Anti-vibration | 25 gn (f= 10…500 Hz) conforming to IEC 60068-2-6 |
| impact resistance | 50 gn for 11 ms conforming to IEC 60068-2-27 |
| Electric Shock Protection Level | Class II conforming to NF C 20-030 |
| Class II conforming to EN/IEC 61140 | |
| IP protection class | IP66 conforms to screwed |
| IP67 conforms to screwed | |
| IK protection class | IK04 conforms to EN 50102 |
| Packaging unit | |
| Unit Type of Package 1 | PCE |
| Number of Units in Package 1 | 1 |
| Package 1 Height | 3.5cm |
| Package 1 Width | 5cm |
| Package 1 Length | 13.2 cm |
| Package 1 Weight | 106g |
| Unit Type of Package 2 | S01 |
| Number of Units in Package 2 | Twenty one |
| Package 2 Height | 15cm |
| Package 2 Width | 15cm |
| Package 2 Length | 40cm |
| Package 2 Weight | 2.42kg |
| Contract warranty | |
| Warranty | 18 months |