PowerLogic PM5350 – Power Meter – Schneider Basic Metering

$ 482.02

SKU: METSEPM5350P

This device is a flush-mount energy meter with a 96mm by 96mm backlit LCD display. The meter provides Class 0.5S accuracy per IEC 62053-22 standard and 64 samples per cycle. The meter will measure Energy, Active and Reactive Power, Voltage, Current, Frequency, Power Factor and up to 31th Harmonic. Include a non-volatile memory for several parameters and alarms. The meter will function in a 50Hz or 60Hz network and accepts supply voltage ranging from 85 to 265 VAC and 100 to 300 VDC. Line rated current for this meter is 1A or 5A input and will support Single Phase and Neutral, Three Phase, or Three Phase and Neutral configurations. The range of measurement voltage between Phases is 20V AC to 480V AC, CAT III or 20V AC to 690V AC, CAT II at 45 Hz to 65 Hz. The range of measurement voltage between Phase and Neutral is 20V AC to 277V AC, CAT III or 20V AC to 400V AC, CAT II at 45 Hz to 65 Hz. Communication protocol is Modbus RTU and ASCII 2 wires with RS485 port support. The meter also has four digital inputs and dual relay outputs. Product dimensions are as follows: width 3.78 inches (96 millimetres), depth 2.24 inches (57 millimetres), height 3.78 inches (96 millimetres) and product weight 8.8 onces (250 g).

Specifications

Main
Part Number METSEPM5350P
Range PowerLogic
Product name PowerLogic PM5350
Device short name PM5350P
Product or component type Power meter
Complementary
power quality analysis Total demand distortion
total harmonic distortion
up to the 31st harmonic
Device application Multi-tariff
Power monitoring
type of measurement Current
Voltage
Frequency
Power factor
Energy
Phase angle
Apparent power
Active power
Reactive power
Individual harmonics up to the 31st
supply voltage 85…265 V AC 45…65 Hz
100…300 V DC
Network frequency 50 Hz
60 Hz
[In] rated current 1:00 AM
5:00 AM
type of network 3P + N
3P
1P + N
power consumption in W 4 W at 125 V DC
5 W at 300 V DC
4 W at 120 V AC
5 W at 230 V AC
power consumption in VA 7 VA at 120 V AC
9 VA at 230 V AC
11.9 VA at 265 V AC
Display type LCD screen with white backlighting
Display colour Monochrome
Display resolution 128 x 128 pixels
Sampling rate 64 samples/cycle
Measurement current 1:00 AM
5:00 AM
analogue input type Current 0.05…9 A (impedance <= 0.3 mOhm)
measurement voltage 20…700 V AC 45…70 Hz phase to phase
20…404 V AC 45…70 Hz phase to neutral
Frequency measurement range 45…70 Hz
measurement accuracy Current 0.5 %
Voltage 0.5 %
Frequency 0.05 %
Power factor 0,01
accuracy class Class 0.5S active energy conforming to IEC 62053-22
Class 0.5 active energy conforming to IEC 61557-12
Class 2 reactive energy conforming to IEC 62053-23
Class 2 reactive energy conforming to IEC 61557-12
Class 0.5 power conforming to IEC 61557-12
Class 5 harmonic distorsion (I THD & U THD) conforming to IEC 61557-12
Class 5 individual harmonics up to the 15th conforming to IEC 61557-12
number of digital inputs 4 digital
digital input voltage rating Discrete input: 18.5…36 V DC 2 Hz 110 kOhm
number of digital outputs 2 relay
1 pulse
maximum switching current Relay outputs 2 A at 250 V AC inductive load, cos phi = 0.4
multi-tariff Tariff (4)
communication port protocol JBUS
Modbus RTU and ASCII at 9.6, 19.2 and 38.4 kbauds even/odd or none – 2-wire, insulation 2500 V
communication port support Terminal block: RS485
realtime clock Built-in battery (3 years), drift: +/- 0.5 s/day
Data recording Min/max of instantaneous values
Alarms
Web services Upgrade drive firmware
Mounting mode Flush-mounted
Type of installation Indoor installation
Standards IEC 61010-1
IEC 61557-12
IEC 62052-11
IEC 62053-22
product certifications CE conforming to IEC 61010-1
CULus conforming to CSA C22.2 No 61010-1
UL conforming to UL 61010-1
Width 96 mm
depth 44 mm embedded:
13 mm outside:
57 mm total:
Height 96 mm
Product weight 0.25 kg
Environment
electromagnetic compatibility Limitation of voltage changes, voltage fluctuations and flicker in low-voltage conforming to IEC 61000-3-3
Electrostatic discharge conforming to IEC 61000-4-2
Electrical fast transient/burst immunity test conforming to IEC 61000-4-4
1.2/50 µs shock waves immunity test conforming to IEC 61000-4-5
Conducted RF disturbances conforming to IEC 61000-4-6
Immunity to magnetic fields conforming to IEC 61000-4-8
Immunity to voltage dips conforming to IEC 61000-4-11
Conducted and radiated emissions class A conforming to EN 55011
Limits for harmonic current emissions conforming to IEC 61000-3-2
Radiated radio-frequency electromagnetic field immunity test conforming to IEC 61000-4-3
Electrical insulation class Double insulation
Class II
measurement category Category III 480 V conforming to IEC 61010-1
Category III 300 V conforming to UL 61010-1
Category III 300 V conforming to CSA C22.2 No 61010-1
Category II 690 V conforming to IEC 61010-1
Overvoltage category III
IP degree of protection IP30 back: conforming to IEC 60529
IP51 front face: conforming to IEC 60529
relative humidity 5…95 % at 50 °C non-condensing
pollution degree 2
ambient air temperature for operation -25…70 °C
-20…70 °C at for display module
-25…20 °C at with derating
Ambient air temperature for storage -40…85 °C
Operating altitude 0…3000 m
Packing Units
Unit Type of Package 1 PCE
Number of Units in Package 1 1
Package 1 Height 11.077 cm
Package 1 Width 12.447 cm
Package 1 Length 12.715 cm
Package 1 Weight 410.0 g
Unit Type of Package 2 S03
Number of Units in Package 2 12
Package 2 Height 30.0 cm
Package 2 Width 30.0 cm
Package 2 Length 40.0 cm
Package 2 Weight 5.571 kg

 

 

Weight 0.25 kg
Dimensions 5.7 × 9.6 × 9.6 cm

Related products