Input Data
Nominal input voltage UN |
24 V DC |
Input voltage range in reference to UN |
0.8 … 1.2 |
Input voltage range |
19.2 V DC … 28.8 V DC |
Switching threshold “0” signal, voltage |
≤ 10 V |
Switching threshold “1” signal voltage |
≥ 16 V |
Typical input current at UN |
7 mA |
Typical response time |
20 µs (at UN) |
Typical turn-off time |
300 µs (at UN) |
Transmission frequency |
300 Hz |
Output Data
Contact type |
1 N/O contact |
Design of digital output |
electronic |
Output voltage range |
3 V DC … 33 V DC |
Limiting continuous current |
3 A (see derating curve) |
Maximum inrush current |
15 A (10 ms) |
Voltage drop at max. limiting continuous current |
≤ 150 mV |
Output circuit |
2-conductor, floating |
Protective circuit |
Reverse polarity protection |
Surge protection |
Dimensions
Width |
5 mm |
Height |
28 mm |
Depth |
15 mm |
Commercial Data
Item number |
2966595 |
Packing unit |
10 pc |
Minimum order quantity |
10 pc |
Sales Key |
08 |
Product Key |
CK61F2 |
Catalog Page |
Page 286 (C-5-2019) |
GTIN |
4017918130947 |
Weight per Piece (including packing) |
5.26 g |
Weight per Piece (excluding packing) |
5.2 g |
Customs tariff number |
85364190 |
Country of origin |
HU |
Ambient conditions
Degree of protection |
RT III |
Ambient temperature (operation) |
-25 °C … 60 °C |
Ambient temperature (storage/transport) |
-25 °C … 70 °C |