$ 559.02 – $ 1,295.14
Main | |||
Part Number | BMXP342000 | BMXP3420102 | BMXP342020 |
Range of product | Modicon M340 automation platform | Modicon M340 automation platform | Modicon M340 automation platform |
Product or component type | Processor module | Processor module | Processor module |
Number of racks | 1 | 4 | 4 |
Number of slots | 11 | 11 | 11 |
discrete I/O processor capacity | 1024 I/O single-rack configuration | 1024 I/O multi-rack configuration 704 I/O single-rack configuration |
1024 I/O multi-rack configuration 704 I/O single-rack configuration |
analogue I/O processor capacity | 256 I/O multi-rack configuration 66 I/O single-rack configuration |
256 I/O multi-rack configuration 66 I/O single-rack configuration |
256 I/O multi-rack configuration 66 I/O single-rack configuration |
Number of application specific channel | 36 | 36 | 36 |
monitoring | Diagnostic counters Modbus Event counters Modbus |
Diagnostic counters Modbus Event counters Modbus |
Diagnostic counters Modbus Event counters Modbus |
Complementary | |||
Control channels | Programmable loops | Programmable loops | Programmable loops |
integrated connection type | Non isolated serial link RJ45 character mode, transmission mode: asynchronous in baseband, RS232C, transmission mode: 2 twisted shielded pairs at 0.3…19.2 kbit/s full duplex Non isolated serial link RJ45 character mode, transmission mode: asynchronous in baseband, RS485, transmission mode: 1 twisted shielded pair at 0.3…19.2 kbit/s half duplex Non isolated serial link RJ45, master/slave Modbus, RTU/ASCII, transmission mode: asynchronous in baseband, RS232C, transmission mode: 1 twisted shielded pair at 0.3…19.2 kbit/s half duplex Non isolated serial link RJ45, master/slave Modbus, RTU/ASCII, transmission mode: asynchronous in baseband, RS485, transmission mode: 1 twisted shielded pair at 0.3…19.2 kbit/s half duplex USB port at 12 Mbit/s |
Non isolated serial link RJ45 character mode, transmission mode: asynchronous in baseband, RS232C, transmission mode: 2 twisted shielded pairs at 0.3…19.2 kbit/s full duplex Non isolated serial link RJ45 character mode, transmission mode: asynchronous in baseband, RS485, transmission mode: 1 twisted shielded pair at 0.3…19.2 kbit/s half duplex Non isolated serial link RJ45, master/slave Modbus, RTU/ASCII, transmission mode: asynchronous in baseband, RS232C, transmission mode: 1 twisted shielded pair at 0.3…19.2 kbit/s half duplex Non isolated serial link RJ45, master/slave Modbus, RTU/ASCII, transmission mode: asynchronous in baseband, RS485, transmission mode: 1 twisted shielded pair at 0.3…19.2 kbit/s half duplex USB port at 12 Mbit/s CANopen master bus SUB-D 9, transmission mode: 2 twisted shielded pairs at 20 kbit/s…1 Mbit/s |
Non isolated serial link RJ45 character mode, transmission mode: asynchronous in baseband, RS232C, transmission mode: 2 twisted shielded pairs at 0.3…19.2 kbit/s full duplex Non isolated serial link RJ45 character mode, transmission mode: asynchronous in baseband, RS485, transmission mode: 1 twisted shielded pair at 0.3…19.2 kbit/s half duplex Non isolated serial link RJ45, master/slave Modbus, RTU/ASCII, transmission mode: asynchronous in baseband, RS232C, transmission mode: 1 twisted shielded pair at 0.3…19.2 kbit/s half duplex Non isolated serial link RJ45, master/slave Modbus, RTU/ASCII, transmission mode: asynchronous in baseband, RS485, transmission mode: 1 twisted shielded pair at 0.3…19.2 kbit/s half duplex USB port at 12 Mbit/s Ethernet TCP/IP RJ45, transmission mode: 1 twisted pair at 10/100 Mbit/s |
communication module processor capacity | 2 Ethernet communication module 4 AS-Interface module |
2 Ethernet communication module 4 AS-Interface module |
2 Ethernet communication module 4 AS-Interface module |
number of devices per segment | 0…32 (character mode) 0…32 (Modbus) |
0…32 (character mode) 0…32 (Modbus) 0…16 for <205 m (CANopen) 0…32 for <185 m (CANopen) 0…64 for <160 m (CANopen) |
0…32 (character mode) 0…32 (Modbus) |
number of devices | 2 point-to-point character mode 2 point-to-point Modbus |
2 point-to-point character mode 2 point-to-point Modbus |
2 point-to-point character mode 2 point-to-point Modbus |
bus length | 0…10 m serial link non isolated character mode segment 0…10 m serial link non isolated Modbus segment 0…1000 m serial link isolated character mode segment 0…1000 m serial link isolated Modbus segment 0…15 m character mode point-to-point 0…15 m Modbus point-to-point |
0…10 m serial link non isolated character mode segment 0…10 m serial link non isolated Modbus segment 0…1000 m serial link isolated character mode segment 0…1000 m serial link isolated Modbus segment 0…15 m character mode point-to-point 0…15 m Modbus point-to-point |
0…10 m serial link non isolated character mode segment 0…10 m serial link non isolated Modbus segment 0…1000 m serial link isolated character mode segment 0…1000 m serial link isolated Modbus segment 0…15 m character mode point-to-point 0…15 m Modbus point-to-point |
maximum tap links length | <15 m serial link non isolated character mode segment <15 m serial link non isolated Modbus segment <40 m serial link isolated character mode segment <40 m serial link isolated Modbus segment |
<15 m serial link non isolated character mode segment <15 m serial link non isolated Modbus segment <40 m serial link isolated character mode segment <40 m serial link isolated Modbus segment |
<15 m serial link non isolated character mode segment <15 m serial link non isolated Modbus segment <40 m serial link isolated character mode segment <40 m serial link isolated Modbus segment |
number of addresses | 0…248 for character mode 0…248 for Modbus |
0…248 for character mode 0…248 for Modbus |
0…248 for character mode 0…248 for Modbus |
requests | 1 K data bytes per request character mode 252 data bytes per RTU request Modbus 504 data bytes per ASCII request Modbus |
1 K data bytes per request character mode 252 data bytes per RTU request Modbus 504 data bytes per ASCII request Modbus |
1 K data bytes per request character mode 252 data bytes per RTU request Modbus 504 data bytes per ASCII request Modbus |
control parameter | One CRC on each frame (RTU) Modbus One LRC on each frame (ASCII) character mode One LRC on each frame (ASCII) Modbus |
One CRC on each frame (RTU) Modbus One LRC on each frame (ASCII) character mode One LRC on each frame (ASCII) Modbus |
One CRC on each frame (RTU) Modbus One LRC on each frame (ASCII) character mode One LRC on each frame (ASCII) Modbus |
memory description | Internal RAM 4096 kB Internal RAM 256 kB data Internal RAM 3584 kB program constants and symbols Supplied memory card (BMXRMS008MP) backup of programs, constants, symbols and data |
Supplied memory card (BMXRMS008MP) backup of programs, constants, symbols and data Internal RAM 4096 kB Internal RAM 256 kB data Internal RAM 3584 kB program constants and symbols |
Supplied memory card (BMXRMS008MP) backup of programs, constants, symbols and data Internal RAM 4096 kB Internal RAM 256 kB data Internal RAM 3584 kB program constants and symbols Supplied memory card (BMXRMS008MP) activation of standard web server, class B10 |
maximum size of object areas | 128 kB unlocated internal data 16250 %Mi located internal bits 32464 %MWi internal words located internal data 32760 %KWi constant words located internal data |
256 kB unlocated internal data 32634 %Mi located internal bits |
256 kB unlocated internal data 32634 %Mi located internal bits |
default size of object areas | 128 %KWi constant words located internal data 256 %Mi located internal bits 512 %MWi internal words located internal data |
1024 %MWi internal words located internal data 256 %KWi constant words located internal data 512 %Mi located internal bits |
1024 %MWi internal words located internal data 256 %KWi constant words located internal data 512 %Mi located internal bits |
Application structure | 1 cyclic/periodic master task 1 periodic fast task No auxiliary task 32 event tasks |
No auxiliary task 1 cyclic/periodic master task 1 periodic fast task 64 event tasks |
1 cyclic/periodic master task 1 periodic fast task No auxiliary task 64 event tasks |
execution time per instruction | 0.18 µs Boolean 0.26 µs double-length words 0.38 µs single-length words 1.74 µs floating points |
0.12 µs Boolean 0.17 µs double-length words 0.25 µs single-length words 1.16 µs floating points |
0.12 µs Boolean 0.17 µs double-length words 0.25 µs single-length words 1.16 µs floating points |
number of instructions per ms | 4.2 Kinst/ms 65 % Boolean + 35 % fixed arithmetic 5.4 Kinst/ms 100 % Boolean |
6.4 Kinst/ms 65 % Boolean + 35 % fixed arithmetic 8.1 Kinst/ms 100 % Boolean |
6.4 Kinst/ms 65 % Boolean + 35 % fixed arithmetic 8.1 Kinst/ms 100 % Boolean |
system overhead | 0.2 ms for fast task 1.05 ms for master task |
0.13 ms for fast task 0.7 ms for master task |
0.13 ms for fast task 0.7 ms for master task |
current consumption | 72 mA at 24 V DC | 90 mA at 24 V DC | 95 mA at 24 V DC |
Supply | Internal power supply via rack | Internal power supply via rack | Internal power supply via rack |
Marking | CE | CE | CE |
status LED | 1 LED (green) processor running (RUN) 1 LED (red) I/O module fault (I/O) 1 LED (red) memory card fault (CARD ERR) 1 LED (red) processor or system fault (ERR) 1 LED (yellow) activity on Modbus (SER COM) |
1 LED (green) integrated machine/installation bus operational (CAN RUN) 1 LED (green) processor running (RUN) 1 LED (red) I/O module fault (I/O) 1 LED (red) integrated machine/installation bus fault (CAN ERR) 1 LED (red) memory card fault (CARD ERR) 1 LED (red) processor or system fault (ERR) 1 LED (yellow) activity on Modbus (SER COM) |
1 LED (green) activity on Ethernet network (ETH ACT) 1 LED (green) processor running (RUN) 1 LED (green) status of Ethernet network (ETH STS) 1 LED (red) data rate (ETH 100) 1 LED (red) I/O module fault (I/O) 1 LED (red) memory card fault (CARD ERR) 1 LED (red) processor or system fault (ERR) 1 LED (yellow) activity on Modbus (SER COM) |
Net weight | 0.2 kg | 0.21 kg | 0.205 kg |
Environment | |||
Ambient air temperature for operation | 0…60 °C | 0…60 °C | 0…60 °C |
relative humidity | 10…95 % without condensation | 10…95 % without condensation | 10…95 % without condensation |
IP degree of protection | IP20 | IP20 | IP20 |
Protective treatment | TC | TC | TC |
Directives | 2014/35/EU – low voltage directive 2014/30/EU – electromagnetic compatibility |
2014/35/EU – low voltage directive 2014/30/EU – electromagnetic compatibility |
2014/35/EU – low voltage directive 2014/30/EU – electromagnetic compatibility |
product certifications | CE UL CSA RCM EAC Merchant Navy |
CE UL CSA RCM EAC Merchant Navy |
CE UL CSA RCM EAC Merchant Navy |
standards | EN 61131-2 EN/IEC 61010-2-201 UL 61010-2-201 CSA C22.2 No 61010-2-201 IACS E10 EN/IEC 61000-6-5, interface type 1 and type 2 EN/IEC 61850-3, location G |
EN 61131-2 EN/IEC 61010-2-201 UL 61010-2-201 CSA C22.2 No 61010-2-201 IACS E10 EN/IEC 61000-6-5, interface type 1 and type 2 EN/IEC 61850-3, location G |
EN 61131-2 EN/IEC 61010-2-201 UL 61010-2-201 CSA C22.2 No 61010-2-201 IACS E10 EN/IEC 61000-6-5, interface type 1 and type 2 EN/IEC 61850-3, location G |
environmental characteristic | Hazardous location class I division 2 | Hazardous location class I division 2 | Hazardous location class I division 2 |
Packing Units | |||
Unit Type of Package 1 | PCE | PCE | PCE |
Number of Units in Package 1 | 1 | 1 | 1 |
Package 1 Height | 5.5 cm | 5.5 cm | 5.5 cm |
Package 1 Width | 11.0 cm | 11.0 cm | 11.0 cm |
Package 1 Length | 11.5 cm | 11.6 cm | 11.5 cm |
Package 1 Weight | 240.0 g | 250.0 g | 248.0 g |
Unit Type of Package 2 | S02 | S02 | S02 |
Number of Units in Package 2 | 15 | 15 | 15 |
Package 2 Height | 15.0 cm | 15.0 cm | 15.0 cm |
Package 2 Width | 30.0 cm | 30.0 cm | 30.0 cm |
Package 2 Length | 40.0 cm | 40.0 cm | 40.0 cm |
Package 2 Weight | 3.915 kg | 4.0 kg | 3.98 kg |
Contractual warranty | |||
Warranty | 18 months | 18 months | 18 months |
Weight | N/A |
---|---|
Dimensions | N/A |
INOSAKI Limited
RM B 5/F Gaylord Comm,
Bldg 114-118 Lockhart Rd.
Hong Kong
INOSAKI Sdn. Bhd.
2-1-9, Ground Floor, One Square, Tingkat Mahsuri 1,
11900 Bayan Lepas, Penan
INOSAKI Pte. Ltd.
101 Upper Cross Street,
No. 06-17, People’s Park Centre,
Singapore (058357)