$ 118.45
Phoenix Contact develops terminal blocks, power supplies, relays, connectors, signal conditioners, controllers & PLCs, I/O systems, Industrial Ethernet, controller system cabling, PCB terminal blocks & connectors, and surge suppression.
| Item number | 2810489 |
| Packing unit | 1 pc |
| Minimum order quantity | 1 pc |
| Note | Made to order (non-returnable) |
| Sales key | ***** |
| Product key | DKA135 |
| GTIN | 4046356166706 |
| Weight per piece (including packing) | 67.9 g |
| Weight per piece (excluding packing) | 60.5 g |
| Customs tariff number | 85437090 |
| Country of origin | DE |
| Utilization restriction | |
| EMC note | EMC: class A product, see manufacturer’s declaration in the download area |
| Product type | Temperature transmitter |
| Product family | MINI Analog |
| No. of channels | 1 |
| Type | Temperature signal conditioner |
| Insulation characteristics | |
| Overvoltage category | II |
| Pollution degree | 2 |
| Step response (0–99%) | < 500 ms |
| Maximum temperature coefficient | < 0.02 %/K |
| Transmission error in the set measuring range | ((50 K / Δ Temp)+ 0.05)% |
| Transmission error in the full measuring range | ≤ 0.25 % |
| Electrical isolation Input/output/power supply | |
| Rated insulation voltage | 50 V AC/DC |
| Test voltage | 1.5 kV AC (50 Hz, 60 s) |
| Insulation | Basic insulation in accordance with IEC/EN 61010 |
| Supply | |
| Nominal supply voltage | 24 V DC ±10 % |
| Supply voltage range | 19.2 V DC … 30 V DC |
| Max. current consumption | < 25 mA |
| Power consumption | < 500 mW |
| Signal | |
| Number of inputs | 1 |
| Measurement | |
| Sensor types (RTD) that can be used | Pt 100 (IEC 60751/EN 60751) |
| Temperature measuring range | -50 °C … 200 °C |
| Temperature measuring range | min. 50 K |
| Sensor type: | -50 °C … 200 °C (configurable) |
| Sensor input current | 1 mA (constant) |
| Max. permissible overall conductor resistance | 10 Ω (Per cable) |
| Connection technology | 3-conductor |
| Signal: Current | |
| Configurable/programmable | no |
| Non-load voltage | approx. 12.5 V |
| Current output signal | 0 mA … 20 mA |
| 4 mA … 20 mA | |
| Max. current output signal | 23 mA |
| Load/output load current output | < 500 Ω (at 20 mA) |
| Ripple | < 20 mVPP (at 500 Ω) |
| Connection method | Screw connection |
| Stripping length | 12 mm |
| Screw thread | M3 |
| Conductor cross section rigid | 0.2 mm² … 2.5 mm² |
| Conductor cross section flexible | 0.2 mm² … 2.5 mm² |
| Conductor cross section AWG | 26 … 12 |
| Width | 6.2 mm |
| Height | 93.1 mm |
| Depth | 102.5 mm |
| Color | green (RAL 6021) |
| Housing material | PBT |
| Fire protection for rail vehicles (DIN EN 45545-2) R22 | HL 1 – HL 2 |
| Fire protection for rail vehicles (DIN EN 45545-2) R23 | HL 1 – HL 2 |
| Fire protection for rail vehicles (DIN EN 45545-2) R24 | HL 1 – HL 2 |
| Ambient conditions | |
| Degree of protection | IP20 |
| Ambient temperature (operation) | -10 °C … 60 °C |
| Ambient temperature (storage/transport) | -20 °C … 65 °C |
| CE | |
| Certificate | CE-compliant |
| UKCA | |
| Certificate | UKCA-compliant |
| Electromagnetic compatibility | Conformance with EMC directive |
| Noise immunity | EN 61000-6-2:2005 |
| Noise emission | |
| Standards/regulations | EN 61000-6-4 |
| Electrostatic discharge | |
| Comments | Safety measures must be taken to prevent electrostatic discharge. |
| Mounting type | DIN rail mounting |
| Mounting position | any |