MGate MB3170 – MOXA Modbus TCP Gateways
$ 408.71
Manufacturer Part Number: MOXA MGate MB3170
OEM Spec Ref
The MOXA MGate MB3170 is a state-of-the-art Modbus TCP Gateway engineered to facilitate smooth communication between Modbus RTU/ASCII devices and TCP/Master devices. This gateway is designed to bridge the gap between different network protocols, enhancing connectivity and data integration in industrial environments.
Key Features:
- Advanced Protocol Conversion: Enables efficient conversion between Modbus RTU/ASCII and Modbus TCP, ensuring seamless data flow and system integration.
- Robust Network Security: Equipped with built-in features like network firewalls, access control lists, and packet filtering, the MGate MB3170 safeguards against unauthorized access and cyber threats.
- Easy Configuration and Management: Offers user-friendly web-based configuration tools and MXview industrial network management software, simplifying setup and maintenance.
- High Durability and Reliability: Designed to operate reliably in harsh industrial environments, with a wide operating temperature range and a rugged metal housing.
- Versatile Mounting Options: Supports DIN-rail and wall mounting, providing flexibility in installation to meet various spatial requirements.
Benefits:
- Enhanced System Integration: By facilitating communication between diverse network protocols, it enables the integration of older and modern equipment, enhancing overall system functionality.
- Increased Data Accessibility: Improves real-time data accessibility across different network segments, optimizing operational decisions and process monitoring.
- Reduced System Downtime: Its robust design and reliable performance minimize system failures and downtime, crucial for maintaining high productivity.
- Cost-Effective Upgrade: Allows for the cost-effective integration of legacy systems with modern TCP/IP networks, eliminating the need for expensive replacements.
Applications:
- Industrial Automation: Integral in automating processes by bridging various communication protocols, enhancing efficiency and accuracy.
- Energy Management: Critical in energy management systems for consistent data communication between field devices and control systems.
- Remote Monitoring: Facilitates remote monitoring and control of industrial equipment, ensuring operational stability and quick response to system changes.
- Transportation and Infrastructure: Plays a vital role in the transportation sector by ensuring reliable data communication in traffic management and infrastructure monitoring systems.
The MOXA MGate MB3170 stands as a testament to MOXA’s commitment to enhancing connectivity and security in industrial networking solutions, offering a robust and reliable gateway for diverse industrial applications.
Specification
Ethernet Interface | 10/100BaseT(X) Ports (RJ45 connector) | 2 Auto MDI/MDI-X connection |
Magnetic Isolation Protection | 1.5 kV (built-in) | |
Optical Fiber | Refer Table 2 | |
Ethernet Software Features | Industrial Protocols | Modbus TCP Client (Master) Modbus TCP Server (Slave) |
Configuration Options | Web Console (HTTP/HTTPS) Device Search Utility (DSU) MGate Manager MCC Tool Telnet Console |
|
Management | ARP DHCP Client DNS HTTP HTTPS SMTP SNMP Trap SNMPv1/v2c/v3 TCP/IP Telnet UDP NTP Client |
|
MIB | RFC1213, RFC1317 | |
Time Management | NTP Client | |
Security Functions | Authentication | Local database |
Encryption | HTTPS AES-128 AES-256 SHA-256 |
|
Security Protocols | SNMPv3 HTTPS (TLS 1.2) |
|
Serial Interface | No. of Ports | 1 |
Connector | DB9 male for RS-232 and terminal block for RS-422/485 | |
Serial Standards | RS-232/422/485 (software selectable) | |
Baudrate | 50 bps to 921.6 kbps | |
Data Bits | 7,8 | |
Parity | None Even Odd Space Mark |
|
Stop Bits | 1,2 | |
Flow Control | DTR/DSR RTS Toggle (RS-232 only) RTS/CTS |
|
Pull High/Low Resistor for RS-485 | 1 kilo-ohm, 150 kilo-ohms | |
Terminator for RS-485 | 120 ohms | |
RS-485 Data Direction Control | ADDC (automatic data direction control) | |
Serial Signals | RS-232 | TxD, RxD, RTS, CTS, DTR, DSR, DCD, GND |
RS-422 | Tx+, Tx-, Rx+, Rx-, GND | |
RS-485-2w | Data+, Data-, GND | |
RS-485-4w | Tx+, Tx-, Rx+, Rx-, GND | |
Serial Software Features | Industrial Protocols | Modbus RTU/ASCII Master Modbus RTU/ASCII Slave |
Modbus (Transparent) | Max. No. of Client Connections | 32 |
Max. No. of Server Connections | 32 | |
Power Parameters | Input Current | 435 mA @ 12 VDC |
Input Voltage | 12 to 48 VDC | |
Power Connector | 7-pin terminal block | |
Relays | Contact Current Rating | Resistive load: 1 A @ 30 VDC |
Physical Characteristics | Housing | Plastic |
IP Rating | IP30 | |
Dimensions (with ears) | 29 x 89.2 x 124.5 mm (1.14 x 3.51 x 4.90 in) | |
Dimensions (without ears) | 29 x 89.2 x 118.5 mm (1.14 x 3.51 x 4.67 in) | |
Weight | 360 g (0.79 lb) | |
Environmental Limits | Operating Temperature | 0 to 60°C (32 to 140°F) |
Storage Temperature (package included) | -40 to 85°C (-40 to 185°F) | |
Ambient Relative Humidity | 5 to 95% (non-condensing) | |
Standards and Certifications | EMC | EN 55032/35 |
EMI | CISPR 32, FCC Part 15B Class A | |
EMS | IEC 61000-4-2 ESD: Contact: 6 kV; Air: 8 kV IEC 61000-4-3 RS: 80 MHz to 1 GHz: 10 V/m IEC 61000-4-4 EFT: Power: 4 kV; Signal: 2 kV IEC 61000-4-5 Surge: Power: 2 kV IEC 61000-4-6 CS: 10 V IEC 61000-4-8 PFMF IEC 61000-4-11 |
|
Hazardous Locations | ATEX Class I Division 2 IECEx |
|
Maritime | DNV | |
Freefall | IEC 60068-2-32 | |
Shock | IEC 60068-2-27 | |
Vibration | IEC 60068-2-6 IEC 60068-2-64 |
|
Safety | UL 60950-1 IEC 60950-1 EN 62368-1 UL 508 |
|
MTBF | Time | 1,662,526 hrs |
Standards | Telcordia SR332 | |
Warranty | Warranty Period | 5 years |
Details | See www.moxa.com/warranty |
Optical Fiber
100BaseFX | ||||
Multi-Mode | Single-Mode | |||
Fiber Cable Type | OM1 | 50/125 µm | G.652 | |
800 MHz x km | ||||
Typical Distance | 4km | 5km | 40km | |
Wavelength | Typical (nm) | 1300 | 1310 | |
TX Range (nm) | 1260 to 1360 | 1280 to 1340 | ||
RX Range (nm) | 1100 to 1600 | 1100 to 1600 | ||
Optical Power | TX Range (dBm) | -10 to -20 | 0 to -5 | |
RX Range (dBm) | -3 to -32 | -3 to -34 | ||
Link Budget (dB) | 12 | 29 | ||
Dispersion Penalty (dB) | 3 | 1 |
Note: When connecting a single-mode fiber transceiver, we recommend using an attenuator to prevent damage caused by excessive optical power.
Note: Compute the “typical distance” of a specific fiber transceiver as follows: Link budget (dB) > dispersion penalty (dB) + total link loss (dB).
Weight | 0.36 kg |
---|---|
Dimensions | 2.9 × 8.92 × 12.45 cm |