$ 299.69
Phoenix Contact develops terminal blocks, power supplies, relays, connectors, signal conditioners, controllers & PLCs, I/O systems, Industrial Ethernet, controller system cabling, PCB terminal blocks & connectors, and surge suppression.
| Item number | 2906242 | 
| Packing unit | 1 pc | 
| Minimum order quantity | 1 pc | 
| Sales key | CK4 | 
| Product key | CMMB21 | 
| Catalog page | Page 238 (C-5-2019) | 
| GTIN | 4055626050928 | 
| Weight per piece (including packing) | 222.8 g | 
| Weight per piece (excluding packing) | 211.7 g | 
| Customs tariff number | 85437090 | 
| Country of origin | DE | 
| Product type | Voltage transducer | 
| Alignment span | ± 20 % | 
| Alignment zero | ± 20 % | 
| Maximum power dissipation for nominal condition | 1.2 W | 
| Protective circuit | Surge protection; 33 V suppressor diode | 
| Step response (10-90%) | < 16 ms | 
| Maximum temperature coefficient | < 0.015 %/K | 
| Maximum transmission error | < 1 % (of measuring range end value) | 
| Electrical isolation | |
| Pollution degree | 2 | 
| Electrical isolation Measuring circuit to supply circuit and output IEC 61010-2-030 | |
| Standards/regulations | IEC 61010-2-030 | 
| Test voltage | 5.3 kV AC (50 Hz, 60 s) | 
| Measuring category | II (1000 V) | 
| III (600 V) | |
| IV (300 V) | |
| Insulation | Reinforced insulation | 
| Electrical isolation Supply circuit to output circuit IEC 61010-1 | |
| Standards/regulations | IEC 61010-1 | 
| Test voltage | 2.2 kV AC (50 Hz, 60 s) | 
| Overvoltage category | III (300 V) | 
| IV (150 V) | |
| Insulation | Basic insulation | 
| Supply | |
| Nominal supply voltage | 24 V DC (-20 % … +25 %) | 
| Supply voltage range | 19.2 V DC … 30 V DC | 
| Max. current consumption | < 60 mA | 
| Measurement | |
| Configurable/programmable | Yes | 
| Input voltage range | -550 V DC … 550 V DC | 
| Maximum input voltage | ± 660 V DC | 
| Input resistance of voltage input | 5500 kΩ | 
| Impulse form | DC voltage | 
| Measurement | |
| Input voltage range | -370 V DC … 370 V DC | 
| Input resistance of voltage input | 3700 kΩ | 
| Measurement | |
| Input voltage range | -250 V DC … 250 V DC | 
| Input resistance of voltage input | 2500 kΩ | 
| Measurement | |
| Input voltage range | -170 V DC … 170 V DC | 
| Input resistance of voltage input | 1700 kΩ | 
| Measurement | |
| Input voltage range | -120 V DC … 120 V DC | 
| Input resistance of voltage input | 1200 kΩ | 
| Measurement | |
| Input voltage range | -80 V DC … 80 V DC | 
| Input resistance of voltage input | 800 kΩ | 
| Measurement | |
| Input voltage range | -54 V DC … 54 V DC | 
| Input resistance of voltage input | 800 kΩ | 
| Measurement | |
| Input voltage range | -36 V DC … 36 V DC | 
| Input resistance of voltage input | 800 kΩ | 
| Measurement | |
| Input voltage range | -24 V DC … 24 V DC | 
| Input resistance of voltage input | 240 kΩ | 
| Signal: Voltage | |
| Voltage output signal | -10 V … 10 V | 
| 2 V … 10 V | |
| Max. voltage output signal | ≤ 11 V | 
| Load/output load voltage output | > 10 kΩ | 
| Ripple | 50 mV | 
| Signal: Current | |
| Current output signal | -20 mA … 20 mA | 
| 4 mA … 20 mA | |
| Max. current output signal | ≤ 22 mA | 
| Load/output load current output | < 500 Ω | 
| Max. capacitive load | < 1000 pF | 
| Max. inductive load | < 1 mH | 
| Connection method | Screw connection | 
| Stripping length | 8 mm | 
| Screw thread | M3 | 
| Conductor cross section rigid | 0.2 mm² … 2.5 mm² | 
| Conductor cross section flexible | 0.2 mm² … 2.5 mm² | 
| Conductor cross section AWG | 24 … 14 | 
| Width | 22.5 mm | 
| Height | 113 mm | 
| Depth | 114 mm | 
| Color | gray (RAL 7042) | 
| Ambient conditions | |
| Degree of protection | IP20 | 
| Ambient temperature (operation) | -25 °C … 60 °C | 
| Ambient temperature (storage/transport) | -40 °C … 85 °C (non-condensing) | 
| Altitude | ≤ 2000 m | 
| Permissible humidity (operation) | 10 % … 95 % (non-condensing) | 
| CE | |
| Certificate | CE-compliant | 
| UKCA | |
| Certificate | UKCA-compliant | 
| UL, USA/Canada | |
| Identification | UL 61010 Listed | 
| Electromagnetic compatibility | Conformance with EMC directive | 
| Low Voltage Directive | Conformance with Low Voltage Directive | 
| Noise immunity | EN 61000-6-2 | 
| Note | When being exposed to interference, there may be minimal deviations. | 
| Noise emission | |
| Standards/regulations | EN 61000-6-4 | 
| Mounting type | DIN rail mounting | 
| Assembly note | can be aligned with spacing = 10 mm | 
| Mounting position | any |