$ 197.80
Phoenix Contact develops terminal blocks, power supplies, relays, connectors, signal conditioners, controllers & PLCs, I/O systems, Industrial Ethernet, controller system cabling, PCB terminal blocks & connectors, and surge suppression.
| Item number | 2865476 | 
| Packing unit | 1 pc | 
| Minimum order quantity | 1 pc | 
| Product key | DK1213 | 
| Catalog page | Page 156 (C-5-2019) | 
| GTIN | 4046356160490 | 
| Weight per piece (including packing) | 187.5 g | 
| Weight per piece (excluding packing) | 143.3 g | 
| Customs tariff number | 85365019 | 
| Country of origin | DE | 
| Product type | Isolating switch amplifier | 
| Product family | MACX Analog | 
| Application | Digital IN | 
| No. of channels | 2 | 
| Type | Ex i signal conditioners with SIL functional safety | 
| Configuration | DIP switches | 
| Functionality | |
| Configuration | DIP switches | 
| Electrical isolation | 3-way isolation | 
| Electrical isolation between input and output | yes | 
| Line monitoring | Line fault detection | 
| Maximum power dissipation for nominal condition | < 1 W | 
| Electrical isolation Input/output IEC/EN 60079-11 | |
| Standards/regulations | IEC/EN 60079-11 | 
| Rated insulation voltage | 375 VPP | 
| Overvoltage category | III | 
| Pollution degree | 2 | 
| Electrical isolation Input/supply, DIN rail connector IEC/EN 60079-11 | |
| Standards/regulations | IEC/EN 60079-11 | 
| Rated insulation voltage | 375 VPP | 
| Overvoltage category | II | 
| Pollution degree | 2 | 
| Electrical isolation Input/supply, DIN rail connector IEC/EN 61010-1 | |
| Standards/regulations | IEC/EN 61010-1 | 
| Rated insulation voltage | 300 Vrms | 
| Overvoltage category | II | 
| Pollution degree | 2 | 
| Insulation | Safe isolation | 
| Electrical isolation Output 1/output 2/input, power supply, DIN rail connector IEC/EN 61010-1 | |
| Standards/regulations | IEC/EN 61010-1 | 
| Rated insulation voltage | 300 Vrms | 
| Overvoltage category | III | 
| Pollution degree | 2 | 
| Insulation | Safe isolation | 
| Electrical isolation Output 1/output 2/input/power supply, DIN rail connector | |
| Test voltage | 2.5 kV AC (50 Hz, 60 s) | 
| Overvoltage category | III | 
| Pollution degree | 2 | 
| Supply | |
| Nominal supply voltage | 24 V DC -20 % … +25 % | 
| Supply voltage range | 19.2 V DC … 30 V DC | 
| Max. current consumption | 35 mA (24 V DC) | 
| Power dissipation | < 1 W | 
| Power consumption | < 1 W | 
| Signal: NAMUR | |
| Description of the input | Intrinsically safe | 
| Number of inputs | 2 | 
| Available input sources | NAMUR proximity sensors (IEC/EN 60947-5-6) | 
| Floating switch contacts | |
| Switch contacts with resistance circuit | |
| Input signal | NAMUR | 
| Switching threshold “0” signal current | < 1.2 mA (blocking) | 
| Switching threshold “1” signal, current | > 2.1 mA (conductive) | 
| Short-circuit current | 8 mA | 
| Switching hysteresis | < 0.2 mA | 
| Line fault detection | < 0.05 mA … 0.35 mA (Line break) | 
| < 100 Ω … 360 Ω (Short circuit) | |
| Activated /deactivated via DIP switch | |
| Non-load voltage | 8 V DC | 
| Switching: Relay | |
| Contact switching type | 1 N/O contact per channel | 
| Contact material | AgSnO2, hard gold-plated | 
| Maximum switching voltage | 250 V AC (2 A) | 
| 120 V DC (0.2 A) | |
| 30 V DC (2 A) | |
| Maximum switching capacity | 500 VA | 
| Recommended minimum load | 5 V / 10 mA | 
| Switching frequency | ≤ 20 Hz (without load) | 
| Signal | |
| Number of outputs | 2 | 
| Connection method | Screw connection | 
| Stripping length | 7 mm | 
| Screw thread | M3 | 
| Conductor cross section rigid | 0.2 mm² … 2.5 mm² | 
| Conductor cross section flexible | 0.2 mm² … 2.5 mm² | 
| Conductor cross section AWG | 24 … 14 | 
| Tightening torque | 0.5 Nm … 0.6 Nm | 
| Test socket | |
| Max. diameter | 2 mm | 
| Ex installation (EPL) | Gc | 
| Div. 2 | |
| Ex i circuits (EPL) | Ga | 
| Da | |
| Ma | |
| Div. 1 | |
| Safety data | |
| Max. internal inductance Li | negligible | 
| Max. internal capacitance Ci | 11 nF | 
| Max. output voltage Uo | 9.6 V | 
| Max. output current Io | 10 mA | 
| Max. output power Po | 25 mW | 
| Safety-related maximum voltage Um | 253 V AC | 
| 125 V DC | |
| IIA/I (simple circuit): Max. external inductivity Lo / Max. external capacitance Co | 1000 mH / 210 µF | 
| IIB/IIIC (simple circuit): Max. external inductivity Lo / Max. external capacitance Co | 1000 mH / 26 µF | 
| IIC (simple circuit): Max. external inductivity Lo / Max. external capacitance Co | 300 mH / 3.6 µF | 
| IIC (mixed circuit): Max. external inductivity Lo / Max. external capacitance Co | 100 mH / 500 nF, 50 mH / 570 nF, 5 mH / 590 nF, 1 mH / 590 nF, 10 µH / 590 nF | 
| I/IIB/IIA/IIIC (mixed circuit): Max. external inductivity Lo / Max. external capacitance Co | 100 mH / 1 µF, 5 mH / 1 µF, 1 mH / 1 µF, 10 µH / 1 µF | 
| Data | |
| No. of channels | 0 | 
| Status display | Green LED (supply voltage) | 
| LED yellow (switching state) | |
| Red LED (line errors) | 
| Width | 12.5 mm | 
| Height | 112.5 mm | 
| Depth | 113.7 mm | 
| Depth NS 35/7,5 | 114.5 mm (Snapped onto DIN rail NS 35/7,5 in accordance with EN 60715) | 
| Color | gray (RAL 7042) | 
| Flammability rating according to UL 94 | V0 (Housing) | 
| Housing material | PA 6.6-FR | 
| Ambient conditions | |
| Degree of protection | IP20 (not assessed by UL) | 
| Ambient temperature (operation) | -40 °C … 60 °C (Any mounting position) | 
| -40 °C … 70 °C (Derating) | |
| Ambient temperature (storage/transport) | -40 °C … 80 °C | 
| Permissible humidity (operation) | 10 % … 95 % (non-condensing) | 
| Altitude range (≤ 2000 m) | |
| Altitude | ≤ 2000 m (The technical data refers to altitudes ≤2000 m above mean sea level. For altitudes >2000 m above mean sea level, refer to the data sheet.) | 
| Ambient temperature (operation) | -40 °C … 60 °C | 
| -40 °C … 70 °C (Derating) | |
| Rated insulation voltage | 253 V AC (Power supply, input / output) | 
| 125 V DC (Power supply, input / output) | |
| Altitude range (≤ 3000 m) | |
| Height range | > 2000 m … 3000 m | 
| Ambient temperature (operation) | -40 °C … 54 °C | 
| -40 °C … 63 °C (Derating) | |
| Rated insulation voltage | 190 V AC (Power supply, input / output) | 
| 110 V DC (Power supply, input / output) | |
| Altitude range (≤ 4000 m) | |
| Height range | > 3000 m … 4000 m | 
| Ambient temperature (operation) | -40 °C … 48 °C | 
| -40 °C … 56 °C (Derating) | |
| Rated insulation voltage | 60 V AC/DC (Power supply, input / output) | 
| Altitude range (≤ 5000 m) | |
| Height range | > 4000 m … 5000 m | 
| Ambient temperature (operation) | -40 °C … 42 °C | 
| -40 °C … 49 °C (Derating) | |
| Rated insulation voltage | 60 V AC/DC (Power supply, input / output) | 
| CE | |
| Certificate | CE-compliant | 
| Note | and EN 61326 | 
| ATEX | |
| Identification |  II (1) G [Ex ia Ga] IIC | 
|  II (1) D [Ex ia Da] IIIC | |
|  II 3 (1) G Ex ec [ia Ga] nC IIC T4 Gc | |
|  I (M1) [Ex ia Ma] I | |
| Certificate | IBExU 07 ATEX 1069 X | 
| IECEx | |
| Identification | [Ex ia Ga] IIC | 
| [Ex ia Da] IIIC | |
| Ex ec [ia Ga] nC IIC T4 Gc | |
| [Ex ia Ma] I | |
| Certificate | IECEx IBE 08.0001X | 
| CCC / China-Ex | |
| Identification | [Ex ia Ga] IIC | 
| [Ex ia Da] IIIC | |
| Ex ec nC [ia Ga] IIC T4 Gc | |
| Certificate | 2022122316115975 | 
| UL, USA/Canada | |
| Identification | UL 61010 Listed | 
| Class I, Div. 2, Groups A, B, C, D T4 | |
| Class I, Div. 2, Groups IIC, IIB, IIA T4 | |
| Associated apparatus for use in Class I, Division 1, Groups A,B,C,D | |
| Associated apparatus for use in Class II, Div.1 Groups E,F,G | |
| Associated apparatus for use in Class III, Division 1 | |
| Associated apparatus for use in Class I, Zone 0,1,2, Groups IIC,IIB,IIA | |
| Certificate | , C.D.-No 83104549 | 
| UL, USA/Canada | |
| Identification | Class I Div 2; IS for Class I, II, III Div 1 | 
| UL 61010 Listed | |
| Certificate | , C.D.-No 83104549 | 
| KC-s | |
| Identification | [Ex ia] IIC/IIB | 
| Certificate | 17-KA4BO-0410X | 
| Shipbuilding approval | |
| Certificate | DNV GL TAA00000AG | 
| Safety Integrity Level (SIL, IEC 61508) | |
| Identification | 2 | 
| Certificate | IN-AT-AS-MRL-24-00163 | 
| Systematic Capability | |
| Identification | 3 | 
| INMETRO | |
| Identification | [Ex ia Ga] IIC | 
| [Ex ia Da] IIIC | |
| Ex ec nC [ia Ga] IIC T4 Gc | |
| [Ex ia Ma] I | |
| Certificate | DNV 18.0114 X | 
| Shipbuilding data | |
| Temperature | B | 
| Humidity | B | 
| Vibration | A | 
| EMC | B | 
| Enclosure | Required protection according to the Rules shall be provided upon installation on board | 
| Electromagnetic compatibility | Conformance with EMC directive | 
| Noise immunity | EN 61000-6-2 | 
| EN 61326 | |
| Noise emission | |
| Standards/regulations | EN 61000-6-4 | 
| Electromagnetic HF field | |
| Designation | Electromagnetic RF field | 
| Standards/regulations | EN 61000-4-3 | 
| Evaluation criterion | A | 
| Fast transients (burst) | |
| Designation | Fast transients (burst) | 
| Standards/regulations | EN 61000-4-4 | 
| Evaluation criterion | A | 
| Conducted interference | |
| Designation | Conducted interferences | 
| Standards/regulations | EN 61000-4-6 | 
| Evaluation criterion | A | 
| Electrical isolation | 3-way isolation | 
| GB Standard | |
| Standards/regulations | GB/T 3836.1 | 
| GB/T 3836.3 | |
| GB/T 3836.4 | |
| GB/T 3836.8 | |
| Mounting type | DIN rail mounting |