			$ 112.07
| Input | |
| Article number | 6EP3333-6SB00-0AY0 | 
| type of the power supply network | 1-phase AC or DC | 
| supply voltage at AC | |
| ● minimum rated value | 100 V | 
| ● maximum rated value | 240 V | 
| ● initial value | 85 V | 
| ● full-scale value | 264 V | 
| input voltage | |
| ● at DC | 110 … 300 V | 
| design of input wide range input | Yes | 
| overvoltage overload capability | 300 V AC for 1 s | 
| operating condition of the mains buffering | at Vin = 187 V | 
| buffering time for rated value of the output current in the | 40 ms | 
| event of power failure minimum | |
| operating condition of the mains buffering | at Vin = 187 V | 
| line frequency | |
| ● 1 rated value | 50 Hz | 
| ● 2 rated value | 60 Hz | 
| line frequency | 47 … 63 Hz | 
| input current | |
| ● at rated input voltage 120 V | 1.95 A | 
| ● at rated input voltage 230 V | 0.97 A | 
| current limitation of inrush current at 25 °C maximum | 31 A | 
| I2t value maximum | 2.5 A²·s | 
| fuse protection type | internal | 
| ● in the feeder | Recommended miniature circuit breaker: from 10 A characteristic B or from 6 A characteristic C | 
| Output | |
| voltage curve at output | Controlled, isolated DC voltage | 
| output voltage at DC rated value | 24 V | 
| output voltage | |
| ● at output 1 at DC rated value | 24 V | 
| relative overall tolerance of the voltage | 3% | 
| relative control precision of the output voltage | |
| ● on slow fluctuation of input voltage | 0.1% | 
| ● on slow fluctuation of ohm loading | 0.1% | 
| residual ripple | |
| ● maximum | 200 mV | 
| ● typical | 30 mV | 
| voltage peak | |
| ● maximum | 300 mV | 
| ● typical | 50 mV | 
| adjustable output voltage | 22.2 … 26.4 V | 
| product function output voltage adjustable | Yes | 
| type of output voltage setting | via potentiometer | 
| display version for normal operation | Green LED for output voltage OK | 
| behavior of the output voltage when switching on | No overshoot of Vout (soft start) | 
| response delay maximum | 0.5 s | 
| voltage increase time of the output voltage | |
| ● typical | 100 ms | 
| output current | |
| ● rated value | 4 A | 
| ● rated range | 0 … 4 A; +55 … +70 °C: Derating 2%/K | 
| supplied active power typical | 96 W | 
| product feature | |
| ● bridging of equipment | Yes | 
| number of parallel-switched equipment resources for | 2 | 
| increasing the power | |
| Efficiency | 89% | 
| efficiency in percent | |
| power loss [W] | 12 W | 
| ● at rated output voltage for rated value of the output | |
| current typical | 0.3 W | 
| ● during no-load operation maximum | |
| Closed-loop control | 0.2% | 
| relative control precision of the output voltage with rapid | |
| fluctuation of the input voltage by +/- 15% typical | |
| relative control precision of the output voltage at load step | 2% | 
| of resistive load 10/90/10 % typical | |
| setting time | |
| ● load step 10 to 90% typical | 1 ms | 
| ● load step 90 to 10% typical | 1 ms | 
| Protection and monitoring | |
| design of the overvoltage protection | Yes, according to EN 60950-1 | 
| response value current limitation typical | 5 A | 
| property of the output short-circuit proof | Yes | 
| design of short-circuit protection | Constant current characteristic | 
| enduring short circuit current RMS value | |
| ● maximum | 5 A | 
| overcurrent overload capability in normal operation | overload capability 150% lout rated typ. 200 ms | 
| display version for overload and short circuit | – | 
| measuring point for output current | 50 mV =^ 4 A | 
| overcurrent overload capability when switching on | 150% Iout rated typ. 200 ms | 
| Safety | |
| galvanic isolation between input and output | Yes | 
| galvanic isolation | Safety extra-low output voltage Uout acc. to EN 60950-1 and EN 50178 | 
| operating resource protection class | Class II (without protective conductor) | 
| protection class IP | IP20 | 
| Approvals | |
| certificate of suitability | |
| ● CE marking | Yes | 
| ● UL approval | Yes; cULus-Listed (UL 508, CSA C22.2 No. 107.1), File E197259; cURus-Recognized (UL 60950, CSA C22.2 No. 60950), File E151273 | 
| ● CSA approval | Yes; cULus-Listed (UL 508, CSA C22.2 No. 107.1), File E197259; cURus-Recognized (UL 60950, CSA C22.2 No. 60950), File E151273 | 
| ● cCSAus, Class 1, Division 2 | No | 
| ● ATEX | No | 
| certificate of suitability | |
| ● IECEx | No | 
| ● NEC Class 2 | No | 
| ● ULhazloc approval | No | 
| ● FM registration | No | 
| type of certification CB-certificate Y | Yes | 
| certificate of suitability | |
| ● EAC approval | Yes | 
| certificate of suitability shipbuilding approval | Yes | 
| shipbuilding approval | ABS, BV, DNV GL, LRS | 
| Marine classification association | |
| ● American Bureau of Shipping Europe Ltd. (ABS) | Yes | 
| ● French marine classification society (BV) | Yes | 
| ● DNV GL | Yes | 
| ● Lloyds Register of Shipping (LRS) | Yes | 
| ● Nippon Kaiji Kyokai (NK) | No | 
| EMC | |
| standard | |
| ● for emitted interference | EN 55022 Class B | 
| ● for mains harmonics limitation | EN 61000-3-2 | 
| ● for interference immunity | EN 61000-6-2 | 
| environmental conditions | |
| ambient temperature | |
| ● during operation | -25 … +70 °C; with natural convection | 
| ● during transport | -40 … +85 °C | 
| ● during storage | -40 … +85 °C | 
| environmental category according to IEC 60721 | Climate class 3K3, 5 … 95% no condensation | 
| Mechanics | |
| type of electrical connection | screw-type terminals | 
| ● at input | L, N: 1 screw terminal each for 0.5 … 2.5 mm2 single-core/finely stranded | 
| ● at output | +, -: 1 screw terminal each for 0.5 … 2.5 mm² | 
| ● for auxiliary contacts | – | 
| width of the enclosure | 72 mm | 
| height of the enclosure | 90 mm | 
| depth of the enclosure | 53 mm | 
| required spacing | |
| ● top | 20 mm | 
| ● bottom | 20 mm | 
| ● left | 0 mm | 
| ● right | 0 mm | 
| net weight | 0.29 kg | 
| product feature of the enclosure housing can be lined up | Yes | 
| fastening method | Snaps onto DIN rail EN 60715 35×7.5/15, direct mounting in different mounting positions | 
| MTBF at 40 °C | 2 391 480 h | 
| other information | Specifications at rated input voltage and ambient temperature +25 °C (unless otherwise specified) |