$ 348.04
Sensors used in the automation industry transmit a wide range of digital and analog signals. In many counting and control processes, these signals need to be clearly displayed, monitored, or processed. To help you find the perfect solution for such applications, we offer a wide range of counters, process displays, signal converters, and switch amplifiers that are all optimized for use with our sensors. The user-friendliness and durability of our products is always a priority at Pepperl+Fuchs.
Functional safety related parameters | ||
---|---|---|
MTTFd | 100 a | |
Supply | ||
Rated voltage | 200 … 230 V AC ; 100 … 130 V AC; 50/60 Hz 20 VDC … 30 VDC |
|
Fusing | external fusing 4 A | |
Power consumption | AC: < 5 VA DC: < 5 W |
|
Input 1 | ||
Connection | terminals 8-, 9+ | |
Connectable sensor types | NAMUR sensors according to DIN EN 60947-5-6 | |
Open loop voltage | 8.2 V DC | |
Short-circuit current | 6.5 mA | |
Switching point | 1.2 … 2.1 mA Switching hysteresis approx. 0.2 mA | |
Input frequency | 0.002 … 10000 Hz, pulse length/duration: ≥ 20µs | |
Impedance | 1.2 kΩ | |
Input 2 | ||
Switching point | high: 16 … 30 V DC; max.10 mA due to integrated constant current sink; Ri ≅ 3 kΩ low: 0 … 6 V DC |
|
Input frequency | 0.002 … 40000 Hz, pulse length/duration: ≥ 12µs | |
Connection | terminals 7+, 13- sensor supply terminals 14, 15 NPN/PNP input (galvanically isolated) |
|
Connectable sensor types | Two, three, or four-wire proximity switch, incremental rotary encoder, or externally generated pulses 16 … 30 V | |
Sensor supply | 19 … 28 V DC non-stabilised; ≤ 30 mA short-circuit protected | |
Input 3 | ||
Start-up override | Triggering by external signal 16 … 30 V or Place jumper between terminals 2/3 or by switching on supply voltage (terminal 2 and terminal 3 permanently bridged) | |
Hold-up time | 0.1 … 999.9 s (External trigger signal) | |
Output | ||
Relay | 1 changeover contact NO, NC, COM |
|
Sensor supply | 24 V DC ± 10 %, 30 mA , short-circuit protected | |
Contact loading | 250 V AC/2 A/ cos φ ≥ 0.7 40 V DC/2 A |
|
Delay | ≤ 20 ms (incl. calculation time) | |
Mechanical life | ≥ 30.000.000 switching cycles | |
Transfer characteristics | ||
Changing interval | 5 ms (Internal processing time) | |
Time delay before availability | ≤ 400 ms | |
Measuring error | 0 … 40000 Hz: ≤ ±0,10% Display: ±1 digit |
|
Timer function | ON-delay, OFF-delay, one shot, pulse extension | |
Time | 0 … 999.9 s ; mode of operation reversible | |
Standard conformity | ||
Electromagnetic compatibility | acc. to EN 50081-2 / EN 50082-2 | |
Ambient conditions | ||
Ambient temperature | -25 … 40 °C (-13 … 104 °F) | |
Storage temperature | -40 … 85 °C (-40 … 185 °F) | |
Relative humidity | max. 80 %, not condensing | |
Altitude | 0 … 2000 m | |
Operating conditions | The device has only to be used in an indoor area. | |
Mechanical specifications | ||
Connection assembly | Caution: Please be aware that the device may only be connected to a switchable power supply. The switch or circuit breaker must be easy to reach and identified as the separator for the device. | |
Degree of protection | IP20 | |
Connection | coded, removable terminals , max. core cross section 0.34 … 2.5 mm2 | |
Construction type | modular terminal housing in Makrolon, System KF For use in the switch cabinet/switch cabinet module |
|
Mounting | snap-on to 35 mm standard rail or screw fixing |
INOSAKI Limited
RM B 5/F Gaylord Comm,
Bldg 114-118 Lockhart Rd.
Hong Kong
INOSAKI Sdn. Bhd.
2-1-9, Ground Floor, One Square, Tingkat Mahsuri 1,
11900 Bayan Lepas, Penan
INOSAKI Pte. Ltd.
101 Upper Cross Street,
No. 06-17, People’s Park Centre,
Singapore (058357)