$ 418.83
| Signal type | Analog input |
| Safety Integrity Level (SIL) | SIL 2 |
| Connection | terminals 23, 24 | |
| Rated voltage | Ur | 20 … 90 V DC or 48 … 253 V AC |
| Power dissipation | 2 W / 3 VA | |
| Power consumption | 2.2 W / 4 VA |
| Programming interface | programming socket |
| Connection side | field side | ||||||||||
| Connection | terminals 1, 2, 3 | ||||||||||
| Input I | |||||||||||
|
|||||||||||
| Connection side | control side | ||||||||
| Connection | output I: terminals 10, 11, 12 output II: terminals 16, 17, 18 Output: analog terminals 8+, 7- |
||||||||
| Output signal | 0 … 20 mA or 4 … 20 mA | ||||||||
| Output I, II | signal, relay | ||||||||
|
|||||||||
| Output III | Signal, analog | ||||||||
|
|||||||||
| Energized/De-energized delay | 0 … 250 s , adjustable | ||||||||
| Input I | ||||||||||
|
||||||||||
| Output I, II | ||||||||||
|
||||||||||
| Output III | ||||||||||
|
||||||||||
| Input/Other circuits | reinforced insulation according to IEC/EN 61010-1, rated insulation voltage 300 Veff |
| Output I, II/other circuits | reinforced insulation according to IEC/EN 61010-1, rated insulation voltage 300 Veff |
| Mutual output I, II, III | reinforced insulation according to IEC/EN 61010-1, rated insulation voltage 300 Veff |
| Output III/power supply | reinforced insulation according to IEC/EN 61010-1, rated insulation voltage 300 Veff |
| Interface/power supply | reinforced insulation according to IEC/EN 61010-1, rated insulation voltage 300 Veff |
| Display elements | LEDs , display |
| Control elements | Control panel |
| Configuration | via operating buttons via PACTware |
| Labeling | space for labeling at the front |
| Electromagnetic compatibility | ||||
|
||||
| Low voltage | ||||
|
||||
| Electromagnetic compatibility | NE 21:2006 |
| Degree of protection | IEC 60529:2001 |
| Ambient temperature | -20 … 60 °C (-4 … 140 °F) |
| Degree of protection | IP20 | ||||||
| Connection | screw terminals | ||||||
| Mass | 300 g | ||||||
| Dimensions | 40 x 119 x 115 mm (1.6 x 4.7 x 4.5 inch) (W x H x D) , housing type C2 | ||||||
|
|||||||
| Mounting | on 35 mm DIN mounting rail acc. to EN 60715:2001 | ||||||
| Supplementary information | Observe the certificates, declarations of conformity, instruction manuals, and manuals where applicable. For information see www.pepperl-fuchs.com. |