$ 241.50
| Signal type | Analog input |
| Safety Integrity Level (SIL) | SIL 2 |
| Connection | terminals 14+, 15- or power feed module/Power Rail | |
| Rated voltage | Ur | 20 … 30 V DC |
| Ripple | within the supply tolerance | |
| Power dissipation | ≤ 1.53 W | |
| Power consumption | max. 1.53 W |
| Programming interface | programming socket |
| Connection side | field side | ||||||||
| Connection | terminals 1, 2, 3; 4, 5, 6 | ||||||||
| RTD | type Pt10, Pt50, Pt100, Pt500, Pt1000 (EN 60751: 1995) type Pt10GOST, Pt50GOST, Pt100GOST, Pt500GOST, Pt1000GOST (6651-94) type Cu10, Cu50, Cu100 (P50353-92) type Ni100 (DIN 43760) |
||||||||
|
|||||||||
| Thermocouples | type B, E, J, K, N, R, S, T (IEC 584-1: 1995) type L (DIN 43710: 1985) type TXK, TXKH, TXA (P8.585-2001) |
||||||||
|
|||||||||
| Potentiometer | 0 … 20 kΩ (2-wire connection), 0.8 … 20 kΩ (3-wire connection) | ||||||||
| Voltage | selectable within the range -100 … 100 mV | ||||||||
| Input resistance | ≥ 1 MΩ (-100 … 100 mV) | ||||||||
| Connection side | control side | ||||||||
| Connection | output I: terminal 7: source (-), sink (+), terminal 8: source (+), terminal 9: sink(-) output II: terminal 10: source (-), sink (+), terminal 11: source (+), terminal 12: sink(-) |
||||||||
| Output I, II | Analog current output | ||||||||
|
|||||||||
| Deviation | |||||||||
|
|||||||||
| Reaction time | worst case value (sensor breakage and/or sensor short circuit detection enabled) mV: 1.2 s, thermocouples with CJC: 1.4 s, thermocouples with fixed ref. temp: 1.4 s, 3- or 4-wire RTD: 1.1 s, 2-wire RTD: 920 ms, Potentiometer: 3-wire connection 2.8 s, 2-wire connection 2.25 s |
||||||||
| Output/supply, programming input | functional insulation, rated insulation voltage 50 V AC There is no electrical isolation between the programming input and the supply. The programming cable provides galvanic isolation so that ground loops are avoided. |
| Display elements | LEDs |
| Configuration | via PACTware |
| Labeling | space for labeling at the front |
| Electromagnetic compatibility | ||||
|
||||
| Electromagnetic compatibility | NE 21:2006 |
| Degree of protection | IEC 60529:2001 |
| Protection against electrical shock | UL 61010-1:2004 |
| Ambient temperature | -20 … 60 °C (-4 … 140 °F) |
| Degree of protection | IP20 | ||||||
| Connection | screw terminals | ||||||
| Mass | approx. 130 g | ||||||
| Dimensions | 20 x 119 x 115 mm (0.8 x 4.7 x 4.5 inch) (W x H x D) , housing type B2 | ||||||
|
|||||||
| Mounting | on 35 mm DIN mounting rail acc. to EN 60715:2001 | ||||||
| EU-type examination certificate | CESI 04 ATEX 143 | ||||||
|
|||||||
| Inputs | terminals 1, 2, 3, 4, 5, 6 (for passive equipment) | ||||||
|
|||||||
| Analog outputs, power supply, collective error | |||||||
|
|||||||
| Interface | |||||||
|
|||||||
| Certificate | TÜV 02 ATEX 1797 X | ||||||
|
|||||||
| Galvanic isolation | |||||||
|
|||||||
| Directive conformity | |||||||
|
|||||||
| UL approval | ||||||
|
||||||
| CSA approval | ||||||
|
||||||
| IECEx approval | ||||||
|
||||||
| Supplementary information | Observe the certificates, declarations of conformity, instruction manuals, and manuals where applicable. For information see www.pepperl-fuchs.com. |