General specifications |
Signal type |
Digital Input |
Functional safety related parameters |
Safety Integrity Level (SIL) |
SIL 2 |
Systematic capability (SC) |
SC 3 |
Supply |
Connection |
Power Rail or terminals 14+, 15- |
Rated voltage |
19 … 30 V DC |
Ripple |
≤ 10 % |
Rated current |
≤ 50 mA |
Power dissipation |
≤ 1 W |
Power consumption |
≤ 1 W |
Input |
Connection side |
field side |
Connection |
terminals 1+, 2+, 3-; 4+, 5+, 6- |
Rated values |
acc. to EN 60947-5-6 (NAMUR) |
Open circuit voltage/short-circuit current |
approx. 8 V DC / approx. 8 mA |
Switching point/switching hysteresis |
1.2 … 2.1 mA / approx. 0.2 mA |
Line fault detection |
breakage I ≤ 0.1 mA , short-circuit I > 6 mA |
Pulse/Pause ratio |
min. 20 ms / min. 20 ms |
Output |
Connection side |
control side |
Connection |
output I: terminals 7, 8, 9 ; output II: terminals 10, 11, 12 |
Output I, II |
signal, relay |
Contact loading |
250 V AC/2 A/cos φ > 0.75; 126.5 V AC/4 A/cos φ > 0.75; 40 V DC/2 A resistive load |
Minimum switch current |
2 mA / 24 V DC |
Energized/De-energized delay |
approx. 20 ms / approx. 20 ms |
Mechanical life |
107 switching cycles |
Collective error message |
Power Rail |
Transfer characteristics |
Switching frequency |
≤ 10 Hz |
Galvanic isolation |
Input/Output |
reinforced insulation according to IEC/EN 61010-1, rated insulation voltage 300 Veff |
Input/power supply |
reinforced insulation according to IEC/EN 61010-1, rated insulation voltage 300 Veff |
Output/power supply |
reinforced insulation according to IEC/EN 61010-1, rated insulation voltage 300 Veff |
Output/Output |
reinforced insulation according to IEC/EN 61010-1, rated insulation voltage 300 Veff |
Indicators/settings |
Display elements |
LEDs |
Control elements |
DIP switch |
Configuration |
via DIP switches |
Labeling |
space for labeling at the front |
Directive conformity |
Electromagnetic compatibility |
|
Directive 2014/30/EU |
EN 61326-1:2013 (industrial locations) |
Low voltage |
|
Directive 2014/35/EU |
EN 61010-1:2010+A1:2019+A1:2019/AC:2019 |
Conformity |
Electromagnetic compatibility |
NE 21:2017 , EN 61326-3-1:2017 , EN IEC 61326-3-2:2018 |
Degree of protection |
IEC 60529:1989+A1:1999+A2:2013 |
Functional safety |
IEC/EN 61508:2010 |
Input |
EN 60947-5-6:2000 |
Ambient conditions |
Ambient temperature |
-20 … 70 °C (-4 … 158 °F) |
Mechanical specifications |
Degree of protection |
IP20 |
Connection |
screw terminals |
Mass |
approx. 150 g |
Dimensions |
20 x 119 x 115 mm (0.8 x 4.7 x 4.5 inch) (W x H x D) , housing type B2 |
Mounting |
on 35 mm DIN mounting rail acc. to EN 60715:2001 |
Data for application in connection with hazardous areas |
EU-type examination certificate |
PTB 00 ATEX 2080 |
Marking |
II (1)G [Ex ia Ga] IIC
II (1)D [Ex ia Da] IIIC
I (M1) [Ex ia Ma] I |
Input |
Ex ia |
Voltage |
10.5 V |
Current |
13 mA |
Power |
34 mW (linear characteristic) |
Supply |
|
Maximum safe voltage |
253 V AC / 125 V DC (Attention! Um is no rated voltage.) |
Output |
|
Maximum safe voltage |
253 V AC (Attention! The rated voltage can be lower.) |
Fault indication output |
|
Maximum safe voltage |
40 V DC (Attention! Um is no rated voltage.) |
Certificate |
PF 08 CERT 0803 |
Marking |
II (3)G [Ex ic Gc] IIC |
Input |
Ex ic |
Voltage |
10.5 V |
Current |
13 mA |
Power |
34 mW (linear characteristic) |
Certificate |
TÜV 99 ATEX 1493 X |
Marking |
II 3G Ex ec nC IIC T4 Gc |
Galvanic isolation |
|
Input/Output |
safe electrical isolation acc. to IEC/EN 60079-11, voltage peak value 375 V |
Input/power supply |
safe electrical isolation acc. to IEC/EN 60079-11, voltage peak value 375 V |
Directive conformity |
|
Directive 2014/34/EU |
EN IEC 60079-0:2018+AC:2020 , EN 60079-7:2015+A1:2018 , EN 60079-11:2012 , EN IEC 60079-15:2019 |
International approvals |
FM approval |
|
FM certificate |
FM19US0207X |
Control drawing |
116-0035 |
UL approval |
E106378 |
Control drawing |
116-0473 (cULus) |
Contact loading |
250 V AC/2 A/cos φ > 0.75; 126.5 V AC/4 A/cos φ > 0.75; 30 V DC/2 A resistive load |
IECEx approval |
|
IECEx certificate |
IECEx PTB 11.0034 , IECEx TUN 19.0013X |
IECEx marking |
[Ex ia Ga] IIC[Ex ia Da] IIIC[Ex ia Ma] I
Ex ec nC IIC T4 Gc |
General information |
Supplementary information |
Observe the certificates, declarations of conformity, instruction manuals, and manuals where applicable. For information see www.pepperl-fuchs.com. |