$ 174.80
| Signal type | Analog output |
| Safety Integrity Level (SIL) | SIL 2 |
| Systematic capability (SC) | SC 3 |
| Connection | Power Rail or terminals 14+, 15- | |
| Rated voltage | Ur | 19 … 30 V DC |
| Ripple | ≤ 10 % | |
| Rated current | Ir | ≤ 30 mA at 24 V |
| Power dissipation | ≤ 600 mW at 20 mA and 500 Ω load | |
| Power consumption | ≤ 700 mW |
| Connection side | control side |
| Connection | terminals 7-, 8+, (9+) |
| Input signal | 4 … 20 mA , limited to approx. 30 mA |
| Input voltage | open loop voltage of the control system ≤ 30 V |
| Voltage drop | approx. 6 V at 20 mA |
| Input resistance | field wiring open circuit : > 100 kΩ field wiring < 50 Ω : > 100 kΩ when using terminals 1 and 2 |
| Connection side | field side |
| Connection | terminals 1+, 2- terminals 3+, 2- (no short circuit detection) |
| Voltage | ≥ 13 V at 20 mA |
| Current | 4 … 20 mA |
| Load | 100 … 650 Ω , for terminals 1, 2 0 … 550 Ω , for terminals 2, 3 |
| Ripple | 20 mV rms |
| Line fault detection | breakage, load > 100 kΩ, short-circuit, load < 50 Ω |
| Output type | open collector transistor (internal fault bus) |
| Deviation | at 20 °C (68 °F), 4 … 20 mA < 0.1 % of full scale, incl. non-linearity and hysteresis |
||
|
|||
| Frequency range | field side into the control side: bandwidth with 0.5 Vpp signal 0 … 3 kHz (-3 dB) control side into the field side: bandwidth with 0.5 Vpp signal 0 … 3 kHz (-3 dB) |
||
| Rise time | 10 to 90 % ≤ 10 ms | ||
| Input/Output | basic insulation according to IEC/EN 61010-1, rated insulation voltage 300 Veff |
| Input/power supply | basic insulation according to IEC/EN 61010-1, rated insulation voltage 300 Veff |
| Output/power supply | reinforced insulation according to IEC/EN 61010-1, rated insulation voltage 300 Veff |
| Display elements | LEDs |
| Labeling | space for adhesive label at the front |
| Electromagnetic compatibility | ||||
|
||||
| Electromagnetic compatibility | NE 21:2017 EN 61326-3-2:2018 |
| Degree of protection | IEC 60529 |
| Protection against electrical shock | UL 61010-1:2012 |
| Ambient temperature | -40 … 70 °C (-40 … 158 °F) |
| Degree of protection | IP20 |
| Connection | screw terminals |
| Mass | approx. 115 g |
| Dimensions | 20 x 124 x 115 mm (0.8 x 4.9 x 4.5 inch) (W x H x D) , housing type B2 |
| Mounting | on 35 mm DIN mounting rail acc. to EN 60715:2001 |
| EU-type examination certificate | BAS 00 ATEX 7240 X | |||||||||||||||||||||
|
||||||||||||||||||||||
| Supply | ||||||||||||||||||||||
|
||||||||||||||||||||||
| Input | ||||||||||||||||||||||
|
||||||||||||||||||||||
| Certificate | FIDI 22 ATEX 0002 X | |||||||||||||||||||||
|
||||||||||||||||||||||
| Galvanic isolation | ||||||||||||||||||||||
|
||||||||||||||||||||||
| Directive conformity | ||||||||||||||||||||||
|
||||||||||||||||||||||
| UL approval | E106378 | ||||
|
|||||
| IECEx approval | |||||
|
|||||
| Supplementary information | Observe the certificates, declarations of conformity, instruction manuals, and manuals where applicable. For information see www.pepperl-fuchs.com. |