$ 133.40
| Signal type | Analog input |
| Safety Integrity Level (SIL) | SIL 2 |
| Connection | terminals 9+, 10- or power feed module/Power Rail | |
| Rated voltage | Ur | 19 … 30 V DC |
| Ripple | within the supply tolerance | |
| Power dissipation | ≤ 0.98 W | |
| Power consumption | max. 0.98 W |
| Programming interface | programming socket |
| Connection side | field side | ||||||||
| Connection | terminals 1, 2, 3, 4 | ||||||||
| RTD | type Pt10, Pt50, Pt100, Pt500, Pt1000 (EN 60751: 1995) type Pt10GOST, Pt50GOST, Pt100GOST, Pt500GOST, Pt1000GOST (6651-94) type Cu10, Cu50, Cu100 (P50353-92) type Ni100 (DIN 43760) |
||||||||
|
|||||||||
| Thermocouples | type B, E, J, K, N, R, S, T (IEC 584-1: 1995) type L (DIN 43710: 1985) type TXK, TXKH, TXA (P8.585-2001) |
||||||||
|
|||||||||
| Potentiometer | 0 … 20 kΩ (2-wire connection), 0.8 … 20 kΩ (3-wire connection) | ||||||||
| Voltage | selectable within the range -100 … 100 mV | ||||||||
| Input resistance | ≥ 1 MΩ (-100 … 100 mV) | ||||||||
| Connection side | control side | ||||||||
| Connection | terminal 5: source (-), terminal 6: source (+), terminal 7: sink(-), terminal 8: sink (+) | ||||||||
| Output | Analog current output | ||||||||
|
|||||||||
| Deviation | |||||||||
|
|||||||||
| Reaction time | worst case value (sensor breakage and/or sensor short circuit detection enabled) mV: 1 s, thermocouples with CJC: 1.1 s, thermocouples with fixed reference temperature: 1.1 s, 3- or 4-wire RTD: 920 ms, 2-wire RTD: 800 ms, Potentiometer: 2.05 s |
||||||||
| Output/supply, programming input | functional insulation, rated insulation voltage 50 V AC There is no electrical isolation between the programming input and the supply. The programming cable provides galvanic isolation so that ground loops are avoided. |
| Display elements | LEDs |
| Configuration | via PACTware |
| Labeling | space for labeling at the front |
| Electromagnetic compatibility | ||||
|
||||
| Electromagnetic compatibility | NE 21:2012 EN 61326-3-2:2008 |
| Degree of protection | IEC 60529:2001 |
| Protection against electrical shock | UL 61010-1:2004 |
| Ambient temperature | -20 … 70 °C (-4 … 158 °F) |
| Degree of protection | IP20 | ||||||
| Connection | screw terminals | ||||||
| Mass | approx. 100 g | ||||||
| Dimensions | 12.5 x 119 x 114 mm (0.5 x 4.7 x 4.5 inch) (W x H x D) , housing type A2 | ||||||
|
|||||||
| Mounting | on 35 mm DIN mounting rail acc. to EN 60715:2001 | ||||||
| EU-type examination certificate | BASEEFA 13 ATEX 0102 X | ||||||
|
|||||||
| Inputs | terminals 1, 2, 3, 4 | ||||||
|
|||||||
| Analog outputs, power supply, collective error | |||||||
|
|||||||
| Interface | |||||||
|
|||||||
| Certificate | BASEEFA 13 ATEX 0103 X | ||||||
|
|||||||
| Galvanic isolation | |||||||
|
|||||||
| Directive conformity | |||||||
|
|||||||
| UL approval | ||||||
|
||||||
| IECEx approval | ||||||
|
||||||
| Supplementary information | Observe the certificates, declarations of conformity, instruction manuals, and manuals where applicable. For information see www.pepperl-fuchs.com. |