$ 90.42
Setting range | Power supply voltage | Model |
---|---|---|
1 to 10 V AC/DC 3 to 30 V AC/DC 15 to 150 V AC/DC |
24 VAC/DC | K8AK-VS2 24 VAC/DC |
100 to 240 VAC | K8AK-VS2 100-240 VAC | |
20 to 200 V AC/DC 30 to 300 V AC/DC 60 to 600 V AC/DC |
24 VAC/DC | K8AK-VS3 24 VAC/DC |
100 to 240 VAC | K8AK-VS3 100-240 VAC |
Model | Range * | Connection terminal |
Setting range | Input impedance | Overload capacity |
---|---|---|---|---|---|
K8AK-VS2 | 0 to 10 V AC/DC | V1-COM | 1 to 10 V AC/DC, 3 to 30 V AC/DC, 15 to 150 V AC/DC |
Approx. 120 kΩ | Continuous input at 115% of maximum input 10 s at 125% (up to 600 VAC) |
0 to 30 V AC/DC | V2-COM | Approx. 320 kΩ | |||
0 to 150 V AC/DC | V3-COM | Approx. 1.6 MΩ | |||
K8AK-VS3 | 0 to 200 V AC/DC | V1-COM | 20 to 200 V AC/DC, 30 to 300 V AC/DC, 60 to 600 V AC/DC |
Approx. 1.2 MΩ | |
0 to 300 V AC/DC | V2-COM | Approx. 1.7 MΩ | |||
0 to 600 V AC/DC | V3-COM | Approx. 3.1 MΩ |
* The range is selected using connected terminals.
Power supply voltage | Isolated power supply |
24 VAC/DC 100 to 240 VAC |
---|---|---|
Power consumption | 24 VAC/DC: 2.0 VA/1.1 W max. 100 to 240 VAC: 4.6 VA max. |
|
Operating value setting range (SV) | 10% to 100% of maximum setting range K8AK-VS2: 1 to 10 V AC/DC 3 to 30 V AC/DC 15 to 150 V AC/DC K8AK-VS3: 20 to 200 V AC/DC 30 to 300 V AC/DC 60 to 600 V AC/DC |
|
Operating value | 100% operation at set value | |
Reset value setting range (HYS.) | 5% to 50% of operating value | |
Reset method | Manual reset/automatic reset (switchable) Note: Manual reset: Turn OFF power supply for 1 s or longer. |
|
Operating time setting range (T) | 0.1 to 30 s | |
Power ON lock time (LOCK) | 1 s or 5 s (Switched using DIP switch.) | |
Indicators | Power (PWR): Green, Relay output (RY): Yellow, Alarm outputs (ALM): Red | |
Input impedance | Refer to Input Range. | |
Output relays | One SPDT relay (NO/NC switched using DIP switch.) | |
Output relay ratings | Rated load Resistive load 5 A at 250 VAC 5 A at 30 VDC Maximum switching capacity: 1,250 VA, 150 W Minimum load: 5 VDC, 10 mA (reference values) Mechanical life: 10 million operations min. Electrical life: 5 A at 250 VAC or 30 VDC: 50,000 operations 3 A at 250 VAC or 30 VDC: 100,000 operations |
|
Ambient operating temperature | -20 to 60°C (with no condensation or icing) | |
Storage temperature | -25 to 65°C (with no condensation or icing) | |
Ambient operating humidity | 25% to 85% (with no condensation) | |
Storage humidity | 25% to 85% (with no condensation) | |
Altitude | 2,000 m max. | |
Terminal screw tightening torque | 0.49 to 0.59 Nm | |
Terminal wiring method | Recommended wire Solid wire: 2.5 mm2 Twisted wires: AWG16, AWG18 Note: 1. Ferrules with insulating sleeves must be used with twisted wires. 2. Two wires can be twisted together. Recommended ferrules Al 1,5-8BK (for AWG16) manufactured by Phoenix Contact Al 1-8RD (for AWG18) manufactured by Phoenix Contact Al 0,75-8GY (for AWG18) manufactured by Phoenix Contact |
|
Case color | N1.5 | |
Case material | PC and ABS, UL 94 V-0 | |
Weight | Approx. 150 g | |
Mounting | Mounts to DIN Track. | |
Dimensions | 22.5 × 90 × 100 mm (W × H × D) |
Allowable operating voltage range | 85% to 110% of rated power supply voltage | |
---|---|---|
Allowable operating frequency range | 50/60 Hz ±5 Hz | |
Input frequency | 40 to 500 Hz | |
Overload capacity | Continuous input at 115% of maximum input, 10 s at 125% (up to 600 VAC). | |
Repeat accuracy |
Operating value | ±0.5% full scale (at 25°C and 65% humidity, rated power supply voltage, DC or 50/60 Hz sine wave input) |
Operating time | ±50 ms (at 25°C and 65% humidity, rated power supply voltage) | |
Applicable standards |
Conforming standards | EN 60947-5-1 Installation environment (pollution level 2, installation category III) |
EMC | EN 60947-5-1 | |
Safety standards | UL 508 (Recognition), Korean Radio Waves Act (Act 10564), CSA: C22.2 No.14, CCC: GB/T 14048.5 |
|
Insulation resistance | 20 MΩ min. Between external terminals and case Between power supply terminals and input terminals Between power supply terminals and output terminals Between input terminals and output terminals |
|
Dielectric strength | 2,000 VAC for one minute Between external terminals and case Between power supply terminals and input terminals Between power supply terminals and output terminals Between input terminals and output terminals |
|
Noise immunity | 1,500 V power supply terminal common/normal mode Square-wave noise of ±1 μs/100 ns pulse width with 1-ns rise time |
|
Vibration resistance | Frequency: 10 to 55 Hz, 0.35-mm single amplitude 10 sweeps of 5 min each in X,Y, and Z directions |
|
Shock resistance | 100 m/s2, 3 times each in 6 directions along 3 axes | |
Degree of protection | Terminals: IP20 |
Dimensions | N/A |
---|---|
Model |
INOSAKI Limited
RM B 5/F Gaylord Comm,
Bldg 114-118 Lockhart Rd.
Hong Kong
INOSAKI Sdn. Bhd.
2-1-9, Ground Floor, One Square, Tingkat Mahsuri 1,
11900 Bayan Lepas, Penan
INOSAKI Pte. Ltd.
101 Upper Cross Street,
No. 06-17, People’s Park Centre,
Singapore (058357)