H3DK-M/-S – Multi-range, Multi-mode Timer – Omron Analog Timers

USD $ 39.48USD $ 53.76

SKU: N/A

List of Models

Supply
voltage
Control output Eight-mode Timer Four-mode Timer
24 to 240
VAC/DC
Contact output, DPDT (time-limit DPDT,
or time-limit SPDT + instantaneous SPDT)
Changed using a switch.
Model H3DK-M2 H3DK-S2
Contact output, SPDT (time-limit SPDT) Model H3DK-M1 H3DK-S1
12 VDC Contact output, DPDT (time-limit DPDT,
or time-limit SPDT + instantaneous SPDT)
Changed using a switch.
Model H3DK-M2A H3DK-S2A
Contact output, SPDT (time-limit SPDT) Model H3DK-M1A H3DK-S1A

 

 

Specifications

Time Ranges

Time range
setting
0.1 s 1 s 10 s 1 min 10 min 1 h 10 h 100 h
Set time
range
0.1 to 1.2 s 1 to 12 s 10 to 120 s 1 to 12 min 10 to 120 min 1 to 12 h 10 to 120 h 100 to 1,200 h
Scale
numbers
12

 

Note: When the main dial is set to “0” for all settings, the output will operate instantaneously

 

Ratings

Power supply voltage *1 24 to 240 VAC/DC, 50/60 Hz *2
12 VDC *2
Allowable voltage fluctuation
range
24 to 240 VAC/DC: 85% to 110% of rated voltage
12 VDC: 90% to 110% of rated voltage
Power reset Minimum power-OFF time: 0.1 s
Reset voltage 10% of rated voltage
Voltage input 24 to 240 VAC/DC
High level: 20.4 to 264 VAC/DC, Low level: 0 to 2.4 VAC/DC
12 VDC
High level: 10.8 to 13.2 VDC, Low level: 0 to 1.2 VDC
Power
consumption
*3
H3DK-M2/-S2 At 240 VAC: 6.6 VA max. *4
H3DK-M1/-S1 At 240 VAC: 4.5 VA max. *4
H3DK-M2A/-S2A At 12 VDC: 0.9 W max.
H3DK-M1A/-S1A At 12 VDC: 0.6 W max.
Control output Contact output:
5 A at 250 VAC with resistive load (cosφ = 1),
5 A at 30 VDC with resistive load *5,
0.15 A max. at 125 VDC with resistive load,
0.1A at 125 VDC with L/R of 7 ms.
The minimum applicable load is 10 mA at 5 VDC (P reference value).
Contact materials: Ag-alloy + Gold plating
Ambient operating temperature -20 to 55°C (with no icing)
Storage temperature -40 to 70°C (with no icing)
Ambient operating humidity 25% to 85%

 

*1. When using a 24-VDC power supply voltage, there will be an inrush current of approximately 0.25 A. Allow for this
inrush current when turning ON and OFF the power supply to the Timer with device with a solid-state output, such
as a sensor.
*2. DC ripple: 20% max.
*3. The power consumption is for mode A after the Timer times out.
For the H3DK-M[], the maximum power consumption is given, including the current consumed by the input circuit.
*4. Refer to DC Power Consumptions (Reference Information) on Catalog for DC power consumptions.
*5. The control output ratings are for one H3DK operating alone. If you operate two or more Timers side by side, refer
to Installation Pitch and Output Switching Capacity (Reference Values) on the Catalog.
*6. 125 VDC: 0.15 A max. with resistive load, 125 VDC: 0.1 A with L/R of 7 ms.
Minimum load: 10 mA at 5 VDC (P level, reference value)

 

Characteristics

Accuracy of operating time ±1% of FS max. (±1% ±10 ms max. at 1.2-s range) *
Setting error ±10% of FS ±0.05 s max. *
Minimum input signal width 50 ms* (start input)
Influence of voltage ±0.5% of FS max. (±0.5% ±10 ms max. at 1.2-s range)
Influence of temperature ±2% of FS max. (±2% ±10 ms max. at 1.2-s range)
Insulation resistance 100 MΩ min. at 500 VDC
Dielectric strength Between current-carrying metal parts and exposed non-current-carrying metal parts:
2,000 VAC 50/60 Hz for 1 min.
Between control output terminals and operating circuit: 2,000 VAC 50/60 Hz for 1 min.
Between contacts not located next to each other: 1,000 VAC 50/60 Hz for 1 min.
Impulse withstand voltage 24 to 240 VAC/VDC: 5 kV between power terminals, 5 kV between current-carrying
metal parts and exposed non-current-carrying metal parts
12 VDC: 1 kV between power terminals, 1.5 kV between current-carrying metal parts
and exposed non-current-carrying metal parts
Noise immunity Square-wave noise generated by noise simulator (pulse width: 100 ns/1 μs, 1-ns rise):
±1.5 kV
Static immunity Malfunction: 4 kV, Destruction: 8 kV
Vibration
resistance
Destruction 0.75-mm single amplitude at 10 to 55 Hz for 2 h each in 3 directions
Malfunction 0.5-mm single amplitude at 10 to 55 Hz for 10 min each in 3 directions
Shock
resistance
Destruction 1,000 m/s2 3 times each in 6 directions
Malfunction 100 m/s2 3 times each in 6 directions
Life
expectancy
Mechanical 10 million operations min. (under no load at 1,800 operations/h)
Electrical 100,000 operations min. (5 A at 250 VAC, resistive load at 360 operations/h)
Degree of protection IP30 (Terminal block: IP20)
Weight Approx. 120 g

 

* With the H3DK-M[], if the voltage exceeds 26.4 VAC/DC in mode C, D, or G, the OFF trigger signal characteristics are
as follows:
Accuracy of operating time: ±1% ±50 ms max.
Setting error: ±10% +100 ms, −50 ms max.
Minimum input signal width: 100 ms

Weight N/A
Model

, , ,