Classification Model Rated voltage
Input (bifurcated contact) SPST-NO G7T-1122S (see note 2) 12 VDC
24 VDC
100/110 VAC
200/220 VAC
Output (single contact) SPST-NO G7T-1112S (see note 2) 12 VDC
24 VDC
SPST-NC G7T-1012S 12 VDC
24 VDC
SPDT G7T-112S 12 VDC
24 VDC

 

Note: 1. When ordering, add the rated voltage to the model number. Rated voltages are given in the coil ratings table in
Specifications.

 

G7T Lineup 3

 

           2. The G7T-1122S and G7T-1112S are approved by UL and CSA. Contact your OMRON representative for the coil
ratings of other models. The G7T-112S cannot be used in place of the G7TC. The G7T-112S can only be used
with the P7TF-05 Socket.
3. “Input” and “output” indicate the I/O relationship to a PLC. Input Relays are mainly suitable for input signals to
a PLC or other device. Output Relays are mainly suitable to switching loads that receive output signals from a
PLC or other device. The Input and Output Relays have different switching performances. Select a suitable
Relay for the application.
Ratings

Coil Ratings (Common to Both Input and Output)

Rated voltage (V) Rated current Coil
resistance
Must operate
voltage
Must release
voltage
Max.
voltage
Power
consumption
50 Hz 60 Hz
AC 100/110 8.2/9 mA 7/7.7 mA 8,700 Ω 80% max. of
rated value
30% min. of
rated value
110% of
rated value
0.7 VA
200/220 4.1/4.5 mA 3.5/3.85 mA 33,300 Ω
DC 12 42 mA 290 Ω 80% max. of
rated value
10% min. of
rated value
110% of
rated value
0.5 W
24 21 mA 1,150 Ω
100/110 5 mA 20,000 Ω 80% max. of
rated value
10% min. of
rated value
110% of
rated value
0.5 W
Note: 1. The rated current and coil resistance values are measured at a coil temperature of 23°C. Tolerances of AC rated
current are +15%, –20% and tolerances of coil resistance are ±15%.
2. Four rated voltages or currents are available to single AC models used with the P7TF-05 Socket. Only three
rated voltages or currents are available, however, when the Relay is used in place of the G7TC.
3. The operating characteristics values are for a coil temperature of 23°C.
4. The maximum voltage is one that is applicable to the Relay coil instantaneously at 23°C and not continuously.

 

Contact Ratings

Classification For input For output
Resistive load
(cosφ = 1)
Inductive load
(L/R = 7 ms)
Resistive load
(cosφ = 1)
Inductive load
(cosφ = 0.4, L/R = 7 ms)
Contact mechanism Crossbar bifurcated Single
Contact material Au-clad Ag AgSnIn
Rated load 1 A at 24 VDC 0.5 A at 24 VDC 5 A at 24 VDC
2 A at 220 VAC
2 A at 24 VDC
1 A at 220 VAC
Rated carry current 1 A 5 A
Max. switching voltage 250 VAC, 125 VDC
Max. switching current 1 A 5 A
Failure rate (reference value) 100 μA at 1 VDC 10 mA at 5 VDC

 

Characteristics

Contact resistance (see note 2) 50 mΩ max.
Operate time (see note 3) 15 ms max.
Release time (see note 3) 15 ms max.
Max. operating frequency Mechanical: 18,000 operations/hour
Electrical: 1,800 operations/hour (under rated load)
Insulation resistance (see note 4) 100 MΩ (at 500 VDC)
Dielectric strength Between coil and contacts: 2,000 VAC, 50/60 Hz for 1 minute
Between contacts of same polarity: 1,000 VAC, 50/60 Hz for 1 minute
Vibration resistance Malfunction: 10 to 55 to 10 Hz, 0.5 mm single amplitude (1.0 mm double
amplitude)
Shock resistance Malfunction: 200 m/s2
Mechanical endurance 50,000,000 operations
Electrical endurance (see note 5) Input:10,000,000 operations (10 mA) or 50,000 operations (1 A) with resistive load
2,500,000 operations (10 mA) or 20,000 operations (0.5 A) with inductive load
Output:1,000,000 operations with rated load
Error rate (level P) (Reference
value) (see note 6)
Input: 100 μA at 1 VDC
Output: 10 mA at 5 VDC
Ambient temperature Operating: -40°C to 70°C (with no icing or condensation)
Ambient humidity Operating: 5% to 85% (with no icing or condensation)
Weight Approx. 17 g

 

 

Note: 1. The above values are all initial values.
2. The contact resistance was measured with 1 A at 5 VDC using the voltage drop method.
3. The operate and the release times were measured with the rated voltage imposed with any contact bounce
ignored at an ambient temperature of 23°C.
4. The insulation resistance was measured with a 500-VDC megger applied to the same places as those used
for checking the dielectric strength.
5. The electrical endurance was measured at an ambient temperature of 23°C.
6. This value was measured at a switching frequency of 120 operations per minute.

 

Weight N/A
Model

G7T-1012S-DC24, G7T-1112S-DC24, G7T-1122S-DC24, G7T-112S-DC24