$ 78.20 – $ 187.68Price range: $ 78.20 through $ 187.68
| Main | |||
| Part Number | LRE482N | LRE483N | LRE484N |
| Product Series | Compact | Compact | Compact |
| product name | EasyPact TVS | EasyPact TVS | EasyPact TVS |
| product type | Type E 3 pole thermal overload relay | Type E 3 pole thermal overload relay | Type E 3 pole thermal overload relay |
| product short name | LRE | LRE | LRE |
| Relay application | Motor protection | Motor protection | Motor protection |
| phase loss sensitivity | 1.3 Ir on two phases, 0 on the other phase conforming to IEC 60947-4-1 | 1.3 Ir on two phases, 0 on the other phase conforming to IEC 60947-4-1 | 1.3 Ir on two phases, 0 on the other phase conforming to IEC 60947-4-1 |
| Additional information | |||
| The scope of products | LC1E120…630 | LC1E160…630 | LC1E200…630 |
| Network Type | AC | AC | AC |
| operating frequency | 50/60Hz | 50/60Hz | 50/60Hz |
| installation method | Mounting on the bottom plate of the contactor, with special accessories |
Mounting on the bottom plate of the contactor , with special accessories |
Mounting on the bottom plate of the contactor , with special accessories |
| Thermal release drag rating | Class 10A conforming to IEC 60947-4-1 | Class 10A conforming to IEC 60947-4-1 | Class 10A conforming to IEC 60947-4-1 |
| Signal indication function | Relay Trip Indicator | Relay Trip Indicator | Relay Trip Indicator |
| Relay setting range | 84…135A | 124…198A | 146…234A |
| Trip threshold | 1.14 ± 0.06 In conforming to IEC 60947-4-1 | 1.14 ± 0.06 In conforming to IEC 60947-4-1 | 1.14 ± 0.06 In conforming to IEC 60947-4-1 |
| Conventional thermal current [Ith] | 5 A for control circuits | 5 A for control circuits | 5 A for control circuits |
| Rated working voltage [Ue] | <= 690V AC | <= 690V AC | <= 690V AC |
| Fuses for use with relays | 5 A gG for control circuits 200 A gG for power circuits 160 A aM for power circuits |
5 A gG for control circuits 250 A gG for power circuits 200 A aM for power circuits |
5 A gG for control circuit 315 A gG for power circuit 250 A aM for power circuit |
| Rated insulation voltage [Ui] | 690 V conforming to IEC 60947-4-1 | 690 V conforming to IEC 60947-4-1 | 690 V conforming to IEC 60947-4-1 |
| Rated impulse withstand voltage [Uimp] | 6kV | 6kV | 6kV |
| control type | Stop: Red (push) button Reset: Green (push) button |
Stop: Red (push) button Reset: Green (push) button |
Stop: Red (push) button Reset: Green (push) button |
| Temperature compensation | -20…60°C | -20…60°C | -20…60°C |
| Phase spacing | 34.8 mm | 40 mm | 48 mm |
| Wiring capacity | Terminal busbar cross-section: 3 x 18 mm | Terminal busbar cross-section: 3 x 20 mm | Terminal busbar cross-section: 3 x 25 mm |
| Tightening torque | 27.5 Nm Via lug screw: M8 | 27.5 Nm Via lug screw: M8 | 35 Nm via lug screw: M10 |
| high | 141 mm | 131 mm | 134 mm |
| width | 180 mm | 180mm | 180 mm |
| depth | 134 mm | 134 mm | 134 mm |
| Product Weight | 1.67kg | 1.67kg | 1.67kg |
| environment | |||
| Standards compliant | IEC 60947-4-1 GB 14048 |
IEC 60947-4-1 GB 14048 |
GB 14048 IEC 60947-4-1 |
| certified product | CCC | CCC | CCC |
| Protective measures | TH conforms to IEC 60068 | TH conforms to IEC 60068 | TH conforms to IEC 60068 |
| IP protection class | IP00 conforming to IEC 60529 | IP00 conforming to IEC 60529 | IP00 conforming to IEC 60529 |
| ambient temperature | -20…60 °C without derating according to IEC 60947-4-1 -20…70 °C with derating |
-20…60 °C without derating according to IEC 60947-4-1 -20…70 °C with derating |
-20…60 °C without derating according to IEC 60947-4-1 -20…70 °C with derating |
| storage environment temperature | -60…80°C | -60…80°C | -60…80°C |
| Fire resistance and abnormal high temperature resistance | 850 °C conforming to IEC 60068-2-1 | 850 °C conforming to IEC 60068-2-1 | 850 °C conforming to IEC 60068-2-1 |
| Shock and vibration resistance | Shock resistance: 6 gn (11ms) conforming to IEC 60068-2-7 Shock resistance: 6 gn conforming to IEC 60068-2-6 |
Shock resistance: 6 gn (11ms) conforming to IEC 60068-2-7 Shock resistance: 6 gn conforming to IEC 60068-2-6 |
Shock resistance: 6 gn (11ms) conforming to IEC 60068-2-7 Shock resistance: 6 gn conforming to IEC 60068-2-6 |
| Insulation properties | 6 kV at 50 Hz conforming to IEC 60255-5 | 6 kV at 50 Hz conforming to IEC 60255-5 | 6 kV at 50 Hz conforming to IEC 60255-5 |
| electromagnetic compatibility | Impulse withstand voltage: 6 kV conforming to IEC 60801-5 | Impulse withstand voltage: 6 kV conforming to IEC 60801-5 | Impulse withstand voltage: 6 kV conforming to IEC 60801-5 |
| packaging unit | |||
| Unit Type of Package 1 | PCE | PCE | PCE |
| Number of Units in Package 1 | 1 | 1 | 1 |
| Package 1 Height | 16cm | 16cm | 16cm |
| Package 1 Width | 17.7cm | 17.7cm | 17.7cm |
| Package 1 Length | 27.5cm | 27.5cm | 27.5cm |
| Package 1 Weight | 2813g | 2811.25g | 2846.25 g |
| Unit Type of Package 2 | S03 | S03 | S03 |
| Number of Units in Package 2 | 2 | 2 | 2 |
| Package 2 Height | 30cm | 30cm | 30cm |
| Package 2 Width | 30cm | 30cm | 30cm |
| Package 2 Length | 40cm | 40cm | 40cm |
| Package 2 Weight | 6.184 kg | 6.18kg | 6.25kg |
| Unit Type of Package 3 | P06 | P06 | P06 |
| Number of Units in Package 3 | 16 | 16 | 16 |
| Package 3 Height | 75cm | 75cm | 75cm |
| Package 3 Width | 60cm | 60cm | 60cm |
| Package 3 Length | 80cm | 80cm | 80cm |
| Package 3 Weight | 59.468 kg | 59.44 kg | 60kg |
| contract warranty | |||