CTEU-CC – Bus Node – Festo Remote I/O and Network Interface Components
$ 344.08
Manufacturer Part Number: Festo 1544198
Festo Remote I/O and Network Interface Components: CTEU-CC
OEM Spec Ref
The Festo CTEU-CC, with MPN 1544198 remote I/O and network interface component, is an advanced remote I/O module designed to enhance the capabilities of automated systems through superior network interfacing. Crafted for seamless integration into various industrial applications, this module ensures efficient communication and control within complex automation networks.
Key Features:
- Versatile Network Connectivity: Supports a wide array of fieldbus protocols, making it adaptable to diverse automation environments and enhancing system compatibility.
- Robust and Reliable: Built to withstand the harsh conditions typical in industrial settings, ensuring durability and long-term operational stability.
- Compact Design: Its compact size facilitates easy installation in tight spaces, maximizing space efficiency without compromising performance.
- Easy Configuration and Maintenance: Engineered for simplicity, it features user-friendly configuration options and can be easily maintained, reducing downtime and technical challenges.
- High-Speed Data Transmission: Ensures rapid data transfer rates, which is crucial for real-time monitoring and control of industrial processes.
Benefits:
- Enhanced System Efficiency: By facilitating seamless communication between various components, it improves the overall efficiency and responsiveness of automation systems.
- Cost Savings: Reduces installation and maintenance costs thanks to its easy integration and minimal upkeep requirements.
- Improved Operational Reliability: Offers reliable operation under a range of environmental conditions, minimizing the risk of system failures.
- Scalability: Allows for future expansion and upgrades without significant system overhauls, protecting investment and adapting to evolving technological needs.
Applications:
- Industrial Automation: Ideal for use in manufacturing facilities requiring robust and reliable communication across various control systems.
- Process Control: Plays a crucial role in process industries where precise control and seamless integration of network components are vital.
- Machine Building: Essential in the design and operation of complex machinery, providing reliable and efficient connectivity solutions.
- Data Acquisition Systems: Suitable for systems that depend on accurate and timely data collection and transmission for effective decision-making.
The Festo CTEU-CC remote I/O and network interface component stands out as a key component in enhancing the operational capabilities of modern industrial systems, offering a reliable and efficient solution for managing complex network communications and optimizing performance across various applications.
Technical Data
Feature | Specification |
---|---|
Protocol | CC-LINK® |
Dimensions W x L x H | 40 mm x 91 mm x 50 mm |
Width dimension | 40 mm |
Type of mounting | On electrical interface On electrical sub-base |
Product weight | 90 g |
Ambient temperature | -5 °C … 50 °C |
Storage temperature | -20 °C … 70 °C |
Degree of protection | IP65 IP67 |
Note on degree of protection | In mounted state Unused connections sealed |
Corrosion resistance class (CRC) | 2 – Moderate corrosion stress |
LABS (PWIS) conformity | VDMA24364 zone III |
CE marking (see declaration of conformity) | As per EU EMC directive As per EU RoHS directive |
UKCA marking (see declaration of conformity) | To UK instructions for EMC To UK RoHS instructions |
KC characters | KC EMC |
Certification | RCM compliance mark c UL us – Listed (OL) |
Note on materials | RoHS-compliant |
Housing material | PA |
LED display (product-specific) | PS: operating voltage for electronics and load supply X1: module system status at I-Port 1 X2: module system status at I-Port 2 |
LED display (bus-specific) | Err: data transmission error Run: bus active |
Diagnostics | Communication error System diagnostics Undervoltage |
Control elements | DIL switch |
Note on fieldbus interface | Open style (screw terminal, 5-pin, degree of protection: IP20) Optional connection technology with accessories: |
Fieldbus interface, type | Serial interface |
Fieldbus interface, protocol | CC-LINK® |
Fieldbus interface, function | Bus connection, incoming/forwarding |
Fieldbus interface, connection type | Socket |
Fieldbus interface, connection technology | Sub-D |
Fieldbus interface, connection pattern | 00995638 |
Fieldbus interface, number of poles/wires | 9 |
Fieldbus interface, galvanic isolation | yes |
Fieldbus interface, transmission rate | 156 – 10000 kbit/s |
Max. address capacity inputs | 16 byte |
Max. address capacity outputs | 16 byte |
Parameterization | Activate diagnostics Fail-safe and idle response |
Internal cycle time | 1 ms per 1 byte of user data |
Additional functions | System status can be indicated via process data |
Power supply, function | Electronics and load |
Power supply, type of connection | Plug |
Power supply, connection technology | M12x1, A-coded as per EN 61076-2-101 |
Power supply, connection pattern | 00995383 |
Power supply, number of pins/wires | 5 |
DC operating voltage range | 18 V … 30 V |
Nominal operating voltage DC | 24 V |
Max. power supply | 4 A |
Intrinsic current consumption at nominal operating voltage | Typ. 70 mA |
Weight | 0.09 kg |
---|