$ 3,185.96
transfer rate | |
transfer rate | 10 Mbit/s, 100 Mbit/s, 1000 Mbit/s |
interfaces | |
number of electrical connections | |
● at the 1st interface / according to Industrial Ethernet | 2 |
● for power supply | 1 |
type of electrical connection | |
● at the 1st interface / according to Industrial Ethernet | RJ45 port |
● of the backplane bus | PCI Express x1 |
● for power supply | 2-pole terminal block |
supply voltage, current consumption, power loss | |
type of voltage / of the supply voltage | DC |
type of voltage supply / optional external power supply | Yes |
supply voltage | |
● 1 / from backplane bus | 3.3 V |
● 2 / from backplane bus | 12 V |
● external | 24 V |
● external | 10.5 … 32 V |
relative symmetrical tolerance / at DC | |
● at 3.3 V | 9 % |
● at 5 V | 5 % |
● at 12 V | 8 % |
● at 24 V | 33 % |
consumed current | |
● 1 / from backplane bus / at DC / maximum | 0.85 A |
● 2 / from backplane bus / at DC / maximum | 0.4 A |
● from external supply voltage / at DC / at 12 V / maximum | 0.55 A |
● from external supply voltage / at DC / at 24 V / maximum | 0.3 A |
power loss [W] | 7.6 W |
power loss [W] / in switch mode / maximum | 7.2 W |
ambient conditions | |
ambient temperature | |
● during operation | 5 … 55 °C |
● during storage | -20 … +60 °C |
● during transport | -20 … +60 °C |
relative humidity / at 25 °C / without condensation / during operation / maximum |
95 % |
protection class IP | IP00 |
design, dimensions and weights | |
module format | PCI Express x1 (half length) |
width | 18 mm |
height | 111 mm |
depth | 167 mm |
net weight | 124 g |
product features, product functions, product components / general | |
number of plug-in cards of same design / plug-in / per PC station |
4 |
number of units / note | – |
performance data / open communication | |
software / for open communication / by means of SEND/RECEIVE / required |
Yes, HARDNET-IE S7 (S7-1613) |
number of possible connections / for open communication / by means of SEND/RECEIVE / maximum |
120 |
performance data / S7 communication | |
software / for S7 communication / required | Yes, HARDNET-IE S7 (S7-1613) |
number of possible connections / for S7/PG communication / maximum |
120 |
number of possible connections / for optimized S7 communication / maximum |
40 |
performance data / multi-protocol mode | |
number of active connections / with multi-protocol mode | 120 |
number of configurable connections / per PC station | 207 |
performance data / PROFINET CBA | |
software / for PROFINET CBA communication / required | Yes, PN CBA OPC server |
number of remote connection partners / with PROFINET CBA | 228 |
number of connections / with PROFINET CBA / total | 10000 |
product functions / management, configuration, engineering | |
product function / MIB support | Yes |
protocol / is supported | |
● SNMP v1 | Yes |
● SNMP v3 | No |
● DCP | Yes |
● LLDP | No |
configuration software / required | Included in the scope of delivery of the required software product |
configuration software / for PROFINET CBA / required | Yes, SIMATIC iMAP |
identification & maintenance function | |
● I&M0 – device-specific information | Yes |
● I&M1 – higher level designation/location designation | Yes |
● I&M2 – installation date | No |
● I&M3 – comment | No |
● I&M4 – signature | No |
● I&M4 – OEM data | No |
product functions / switch | |
product feature / switch | Yes |
product function / switch-managed | No |
product function / with IRT / PROFINET IO switch | No |
product functions / redundancy | |
software / for redundancy function / required | Yes, HARDNET-IE S7-REDCONNECT for communication with SIMATIC S7 H systems |
product functions / time | |
product function / SICLOCK support | Yes |
protocol / is supported / NTP | No |
standards, specifications, approvals | |
reference code | |
● according to IEC 81346-2:2019 | KEC |
standards, specifications, approvals / Environmental Product Declaration | |
Environmental Product Declaration | Yes |
global warming potential [CO2 eq] | |
● total | 241.26 kg |
● during manufacturing | 33.23 kg |
● during operation | 207.97 kg |
● after end of life | 0.06 kg |