$ 991.07
Phoenix Contact develops terminal blocks, power supplies, relays, connectors, signal conditioners, controllers & PLCs, I/O systems, Industrial Ethernet, controller system cabling, PCB terminal blocks & connectors, and surge suppression.
| Item number | 2700988 |
| Packing unit | 1 pc |
| Minimum order quantity | 1 pc |
| Product key | DRAAEA |
| Catalog page | Page 44 (C-6-2019) |
| GTIN | 4046356731195 |
| Weight per piece (including packing) | 234.1 g |
| Weight per piece (excluding packing) | 244 g |
| Customs tariff number | 85371091 |
| Country of origin | DE |
| Note on application | |
| Note on application | Only for industrial use |
| Utilization restriction | |
| EMC note | EMC: class A product, see manufacturer’s declaration in the download area |
| Product type | Controller |
| Product family | Axiocontrol |
| Type | modular |
| Insulation characteristics | |
| Protection class | III (IEC 61140, EN 61140, VDE 0140-1) |
| Display | |
| Diagnostics display | no |
| Processor | AlteraNios® II, 1x 100 MHz |
| Retentive data storage | 48 kByte (NVRAM) |
| IEC 61131 runtime system | |
| Program memory | 2 Mbyte |
| Data storage system | 2 Mbyte |
| Number of control tasks | 8 |
| Axioline | |
| Amount of process data | max. 8192 bit (per station) |
| max. 4096 bit (Axioline F local bus (input)) | |
| max. 4096 bit (Axioline F local bus (output)) | |
| Number of supported devices | max. 63 (per station) |
| Number of local bus devices that can be connected | max. 63 (observe current consumption) |
| PROFINET | |
| Device function | PROFINET controller, PROFINET device |
| Specification | Version 2.3 |
| Update rate | min. 32 ms (16 devices) |
| min. 32 ms (8 devices) | |
| min. 16 ms (4 devices) | |
| min. 8 ms (2 devices) | |
| min. 4 ms (1 device) | |
| Conformance Class | A |
| Number of supported devices | max. 16 (at PROFINET controller) |
| Supported functions | MRP |
| MRP | |
| Device ID | 0093hex |
| Vendor ID | 00B0hex |
| Function | |
| Diagnostics display | no |
| Redundancy function | yes |
| Note on redundancy function | applicative system redundancy possible |
| Safety function | no |
| Functionality | |
| Programming languages supported | Instruction list (IL) |
| Symbolic flowchart (SFC) | |
| Ladder diagram (LD) | |
| Function block diagram (FBD) | |
| Structured text (ST) | |
| System requirements | |
| Engineering tool | PC Worx |
| PC Worx Express | |
| Configuration tool | Config+ Version 1.01 or later |
| Diagnostics tool | DIAG+ |
| Runtime system | eCLR |
| Application interface | OPC |
| Maximum power dissipation for nominal condition | 3.2 W |
| Real-time clock | |
| Realtime clock | yes |
| Description realtime clock | 1.73 s/day = 20 ppm at 25 °C |
| Potentials | |
| Protective circuit | Surge protection of the supply voltage; electronic |
| Polarity reversal protection of the supply voltage; electronic | |
| Potentials: Communications power UL feed-in (the supply of the Axioline F local bus UBus is generated from UL) | |
| Supply voltage | 24 V DC |
| Supply voltage range | 19.2 V DC … 30 V DC (including all tolerances, including ripple) |
| Current draw | max. 650 mA (with 2 A at UBus for the I/Os and UL = 24 V) |
| typ. 100 mA (without I/Os and UL = 24 V) | |
| Power consumption | max. 13.2 W (2.0 A on UBus, UL = 24 V) |
| Potentials: Axioline F local bus supply (UBus) | |
| Supply voltage | 5 V DC (via bus base module) |
| Power supply unit | 2 A |
| Connection method | Push-in connection |
| Axioline F connector | |
| Connection method | Push-in connection |
| Conductor cross section, rigid | 0.2 mm² … 1.5 mm² |
| Conductor cross section, flexible | 0.2 mm² … 1.5 mm² |
| Conductor cross section AWG | 24 … 16 |
| Stripping length | 8 mm |
| Web server | yes |
| Axioline F local bus | |
| Number of interfaces | 1 |
| Connection method | Bus base module |
| Transmission speed | 100 Mbps |
| Ethernet | |
| Bus system | RJ45 |
| Number of interfaces | 2 |
| Connection method | RJ45 jack |
| Note on the connection method | Auto negotiation and autocrossing |
| Transmission speed | 10/100 Mbps (half or full duplex (automatic detection)) |
| Transmission physics | Ethernet in RJ45 twisted pair |
| No. of channels | 2 |
| Service | |
| Bus system | USB |
| Number of interfaces | 1 |
| Connection method | Micro USB type B |
| Transmission speed | max. 115.2 kbps |
| No. of channels | 1 |
| Width | 45 mm |
| Height | 126.1 mm |
| Depth | 74 mm |
| Note on dimensions | The depth applies when a TH 35-7.5 DIN rail is used (in accordance with EN 60715). |
| Color | gray (RAL 7042) |
| Ambient conditions | |
| Degree of protection | IP20 |
| Ambient temperature (operation) | -25 °C … 60 °C up to 2000 m above mean sea level |
| -25 °C … 55 °C up to 3000 m above mean sea level | |
| Ambient temperature (storage/transport) | -40 °C … 85 °C |
| Permissible humidity (operation) | 5 % … 95 % (according to DIN EN 61131-2, non-condensing, no ice formation) |
| Permissible humidity (storage/transport) | 5 % … 95 % (according to DIN EN 61131-2, non-condensing, no ice formation) |
| Shock (operation) | 10g (Bump endurance test according to DIN EN 60068-2-27) |
| Vibration (operation) | 5g |
| Air pressure (operation) | 70 kPa … 106 kPa (up to 3000 m above sea level) |
| Air pressure (storage/transport) | 58 kPa … 106 kPa (up to 4500 m above mean sea level) |
| UL, USA/Canada | |
| Identification | cULus |
| Certificate | E238705 |
| Electromagnetic compatibility | Conformance with EMC Directive 2014/30/EU |
| Conformance with EMC directives | Immunity test in accordance with EN IEC 61000-6-2 Electrostatic discharge (ESD)IEC 61000-4-2 Criterion B, ±6 kV contact discharge, ±8 kV air discharge |
| Immunity test in accordance with EN IEC 61000-6-2 Electromagnetic fieldsIEC 61000-4-3 Criterion A, Field intensity: 10 V/m | |
| Immunity test in accordance with EN IEC 61000-6-2 Fast transients (burst)IEC 61000-4-4 Criterion B, ±2 kV | |
| Immunity test in accordance with EN IEC 61000-6-2 Transient overvoltage (surge)IEC 61000-4-5 Criterion B; DC supply lines: ±0.5 kV/±1.0 kV (symmetrical/asymmetrical), fieldbus cable shielding: ±1.0 kV | |
| Immunity test in accordance with EN IEC 61000-6-2 Conducted interferenceIEC 61000-4-6 Criterion A, Test voltage 10 V | |
| Noise emission test in accordance with EN IEC 61000-6-3 Class B |
| Mounting type | DIN rail mounting |