Acti9 – iCT – Modular Contactor – Schneider Contactors & Reversing Contactors

$ 33.44$ 327.58

SKU: N/A

Specifications

Main
Part Number

A9C22712

A9C20884

range of product Acti9 Acti9
Product name Acti9 iCT Acti9 iCT
Product type Contactors Contactors
Short name of the product ICT ICT
Product application Motor heating and lighting Heating-low inductive load
Poles 2P 4P
Rated operating current [IE] 16 A AC-7A
6 A AC-7B
100 A AC-7A
Loop contact type 2 NO 4 NO
Network type AC AC
Control type Remote control Remote control
Control loop voltage 230…240 V AC 50 Hz 220…240 V AC 50 Hz
Supplemental Information
Network frequency 50 Hz 50 Hz
Rated operating voltage [UE] 250 V AC 50 Hz 400 V AC 50 Hz
Maximum power 1.2 W in… On 250 V AC AC-7A: 4.2 W in… Up to 400 V AC 50 Hz
Rated insulation voltage [UI] 500 V AC 50 Hz 500 V AC 50 Hz
Rated impulse withstand voltage [UIMP] 4 kV 4 kV
Control signal type Self-holding Self-holding
Switching frequency Number of switching operations/per day Number of switching operations/per day
Local signal indication Trip indicator window Trip indicator window
Pull-in power (VA) 2.7 VA 13 VA
(~50Hz Bonded) Power Consumption (VA) 9.2 VA 106 VA
Installation type The locking clip is locked The locking clip is locked
Installation method 35 mm DIN rail 35 mm DIN rail
Width (multiple of 9mm) 2 12
height 81 mm 85 mm
width 18 mm 108 mm
depth 68.5 mm 60 mm
color White White
Mechanical life 1000000,<>,<> times N/A
Electrical life 100000 times IEC/EN 61095 16 A 50 Hz AC-7A
30000 times IEC/EN 61095 6 A 50 Hz AC-7B
30000 times IEC/EN 61095 50 Hz AC-7C
100000 times EN/IEC 60947-4-1 50 Hz AC-1
30000 EN/IEC 60947-4-1 50 Hz AC-3 30000 EN/IEC 60947-4-1 50 Hz AC-5a30000 EN/IEC 60947-4-1 50 Hz AC-5b
30000 times EN 61095 400 V 16 A AC 50 Hz AC-7A 30000 times UTE C 61-481 400 V 6 A AC 50 Hz AC-7A 30000 times IEC 61095 400 V AC 50 Hz AC-7A
Wiring capability Control loop: Tunnel terminal 2 Cable 1.5 mm² Single stranded hard wire
power loop: Tunnel terminal 1 Cable 1… 4 mm² cord
power circuit: tunnel terminal 1 Cable 1.5… 6 mm² single-stranded hardwire
control loop: tunnel terminal 1 Cable 1.5… 2.5 mm² single-strand hardwire
control loop: tunnel terminal 2 cable 1.5… 2.5 mm² cord
Control loop: Tunnel terminal 2 Cable 1.5 mm² Single strand hard wire
control loop: Tunnel terminal 1 Cable 1.5… 2.5 mm² single-strand hardwire
control loop: tunnel terminal 2 cable 1.5… 2.5 mm² cord
power circuit: tunnel terminal 1 Cable 6… 35 mm² hard or soft
Tightening torque 0.8 N.m Control Loop: 0.8 N.m Power Loop: 3.5 N.m power loop: 0.8 N.m A1 / A2 control loop:
Scope of application IACTs IACTp
IACTs
IATEt
IACTc
Model ICT ICT
Market share Small commercial
residences
Small commercial
residences
environment
Compliance with standards IEC/EN 61095 EN 61095
IEC 61095
UTE C 61-481
Noise level 30 dB 30 dB
Heat dissipation 0.9 W in… Up to 50/60 Hz 4.2 W in… Up to 50/60 Hz
IP protection rating IP20 conforming to IEC 60529
IP40 (modular housing) conforming to IEC 60529
IP20 conforming to IEC 60529
IP40 (modular housing) conforming to IEC 60529
Pollution level 2 2
Resistance to humidity and heat 2 Complies with IEC 60068-1
2
2 Complies with EN 60947-4-1
relative humidity 95 % in… Up to 55 °C 95 % in… Up to 55 °C
Working altitude 2000 meters 2000 meters
Operating temperature -5… 60 °C -5… 60 °C
Storage ambient temperature -40… 70 °C -40… 70 °C
Packaging unit
Unit Type of Package 1 PCE PCE
Number of Units in Package 1 1 1
Package 1 Height 1.8 cm 6.8 cm
Package 1 Width 7 cm 8.8 cm
Package 1 Length 8.3 cm 10.9 cm
Package 1 Weight 116 g 621 g
Unit Type of Package 2 BB1 BB1
Number of Units in Package 2 12 2
Package 2 Height 2.85 cm 8.3 cm
Package 2 Width 30 cm 9.8 cm
Package 2 Length 20 cm 23.2 cm
Package 2 Weight 1.468 kg 1.304 kg
Unit Type of Package 3 S03 S03
Number of Units in Package 3 144 16
Package 3 Height 30 cm 30 cm
Package 3 Width 30 cm 30 cm
Package 3 Length 40 cm 40 cm
Package 3 Weight 17.779 kg 10.919 kg
Contract warranty
Warranty 18 months 18 months

 

Weight N/A
Dimensions N/A