WAGO 857-801 Temperature Signal Conditioner

USD 285.18

RTD temperature transmitter with configurable current/voltage output, 2-/3-/4-wire input, 3-way isolation, and 24 VDC supply.

SKU Wago-857-801 Category
Top Brands > WAGO > Temperature Signal Conditioners

WAGO 857-801 Temperature Signal Conditioner

Model Identifier 857-801
Official Part Number 857-801
GTIN Standard 4045454502713

Technical Overview

Temperature signal conditioner for RTD sensors with configurable current or voltage analog output. The module supports Pt100, Pt200, Pt500, and Pt1000 sensors, as well as resistors up to 4.5 kΩ, and can be configured via DIP switch or WAGO Interface Configuration Software. It accepts 2-, 3-, and 4-wire sensor connections, provides 3-way electrical isolation, and includes diagnostic functions for wire break, short circuit, and measurement range underflow/overflow. The device is DIN-rail mounted and powered from 24 VDC.

Key Features

  • Supports Pt100, Pt200, Pt500, and Pt1000 sensors
  • Accepts resistors from 0 to 4.5 kΩ
  • Configurable 2-wire, 3-wire, and 4-wire sensor connection
  • Analog output selectable for current or voltage signals
  • DIP switch and software configuration
  • Detects calibrated measurement range switching
  • Detects sensor wire break and short circuit
  • Detects measurement range underflow and overflow
  • Clipping function for analog output limitation
  • 3-way electrical isolation with 2.5 kV test voltage
  • DIN-35 rail mounting
  • Push-in CAGE CLAMP connection technology

Converts RTD and resistance inputs into configurable analog current or voltage outputs with 3-way isolation and built-in diagnostics.

Technical Specification Matrix

ParameterValue
Item number857-801
Supply voltage24 VDC
Nominal supply voltage Us24 VDC
Supply voltage range±30 %
Current consumption at nominal supply voltage≤ 50 mA
Input signal typePt sensors; Resistance
Sensor types (RTD)Pt100; Pt200; Pt500; Pt1000
Sensor connection2-wire; 3-wire; 4-wire (switchable)
Sensor power supply (RTD) max.≤ 0.5 mA
Temperature measurement range (RTD)-200 … +850 °C
Measurement span (RTD) min.50 K
Input range (resistor)0 … 1 kΩ; 0 … 4.5 kΩ
Measurement span (resistor) min.50 Ω
Output signal typeCurrent; Voltage
Output signal (voltage)0 … 5 V; 1 … 5 V; 0 … 10 V; 2 … 10 V
Output signal (current)0 … 10 mA; 2 … 10 mA; 0 … 20 mA; 4 … 20 mA
Load impedance (voltage output)≥ 2 kΩ
Load impedance (current output)≤ 600 Ω
Step response (typ.)180 ms (2-wire); 360 ms (3-wire)
Transmission error (typ.)≤ 0.1 % at full measurement span
Transmission error for set measurement range≤ ((10 K/set measurement range [K]) + 0.1) %
Temperature coefficient≤ 0.02 %/K
Rated voltage300 V
Protection typeIP20
Test voltage2.5 kVAC; 50 Hz; 1 min
Overvoltage categoryII
Pollution degree2
Insulation type (input/analog output/supply)Functional insulation
Insulation type (adjacent devices)Reinforced insulation (safe isolation)
Connection technologyPush-in CAGE CLAMP®
Solid conductor0.08 … 2.5 mm² / 28 … 14 AWG
Fine-stranded conductor0.34 … 2.5 mm² / 22 … 14 AWG
Strip length9 … 10 mm / 0.35 … 0.39 inches
Width6 mm / 0.236 inches
Height94 mm / 3.701 inches
Depth from upper-edge of DIN-rail97.8 mm / 3.85 inches
Mounting typeDIN-35 rail
Colorlight gray
Insulation material (main housing)Polyamide (PA66)
Flammability class per UL94V0
Fire load0.486 MJ
Weight35.1 g
Ambient temperature (operation)-25 … +70 °C
Ambient temperature (storage)-40 … +85 °C
Relative humidity5 … 95 % (no condensation permissible)
Operating altitude (max.)2000 m
Conformity markingCE
EMC immunity to interferenceEN 61000-6-2
EMC emission of interferenceEN 61000-6-4
Standards/specificationsDNV
GTIN4045454502713

Industrial Applications

1. RTD-to-PLC analog temperature interface

Converts Pt100/Pt1000 field sensors into a standard 4–20 mA or 0–10 V signal for PLC analog input cards.

Problem Solved

Eliminates direct RTD wiring to the control cabinet and standardizes diverse temperature sensors into one analog format.

Pt100Pt10004-20 mA0-10 VPLC analog inputRTD transmitter

2. Long-distance temperature monitoring on DIN-rail panels

Used in remote panels where low-level RTD signals need conditioning before transmission over longer analog runs.

Problem Solved

Reduces susceptibility to noise and cable resistance effects by converting the sensor signal into a robust analog output with isolation.

3-way isolationpush-in terminalsshielded cablemeasurement errorDIN-35 rail

3. Multi-sensor retrofit for process skids

Supports mixed RTD and resistor inputs with configurable wire modes, making it suitable for skid upgrades and instrumentation retrofits.

Problem Solved

Allows replacement of older temperature measurement loops without changing the downstream analog infrastructure.

2-wire3-wire4-wireresistance inputindustrial retrofitsignal conditioner