KFD2-SR3-EX2.2S – Switch Amplifier – PEPPERL+FUCHS Intrinsic Safety Barriers

$ 164.12

SKU: KFD2-SR3-EX2.2S

Intrinsic safety barriers from Pepperl+Fuchs limit the energy that is supplied to a circuit and protect hazardous areas from excess energy. By limiting energy to a safe level, intrinsically safe circuits prevent the ignition of potentially explosive atmospheres. This simplifies maintenance and repair of Ex i circuits.

General specifications
Signal type Digital Input
Functional safety related parameters
Safety Integrity Level (SIL) SIL 2
Systematic capability (SC) SC 3
Supply
Connection Power Rail or terminals 14+, 15-
Rated voltage 19 … 30 V DC
Ripple ≤ 10 %
Rated current 30 … 20 mA
Power consumption < 600 mW
Input
Connection side field side
Connection terminals 1+, 2+, 3-; 4+, 5+, 6-
Rated values acc. to EN 60947-5-6 (NAMUR)
Open circuit voltage/short-circuit current approx. 10 V DC / approx. 8 mA
Switching point/switching hysteresis 1.2 … 2.1 mA / approx. 0.2 mA
Line fault detection breakage I ≤ 0.1 mA , short-circuit I ≥ 6.5 mA
Pulse/Pause ratio min. 20 ms / min. 20 ms
Output
Connection side control side
Connection output I: terminals 7, 8 ; output II: terminals 8, 9 ; output III: terminals 10, 11 ; output IV: terminals 11, 12
Output I, II, III, IV channel 1, 2; relay
Contact loading 48 V AC/1 A/cos φ > 0.7; 40 V DC/1 A resistive load
Minimum switch current 1 mA / 24 V DC
Energized/De-energized delay approx. 20 ms / approx. 20 ms
Mechanical life 108 switching cycles
Collective error message Power Rail
Transfer characteristics
Switching frequency ≤ 10 Hz
Galvanic isolation
Input/Output reinforced insulation according to IEC/EN 61010-1, rated insulation voltage 300 Veff
Input/power supply reinforced insulation according to IEC/EN 61010-1, rated insulation voltage 300 Veff
Output/power supply basic insulation according to IEC/EN 61010-1, rated insulation voltage 32 Veff , functional insulation, rated insulation voltage 50 Veff
Output/Output basic insulation according to IEC/EN 61010-1, rated insulation voltage 32 Veff , functional insulation, rated insulation voltage 50 Veff
Indicators/settings
Display elements LEDs
Control elements DIP switch
Configuration via DIP switches
Labeling space for labeling at the front
Directive conformity
Electromagnetic compatibility
Directive 2014/30/EU EN 61326-1:2013 (industrial locations)
Conformity
Electromagnetic compatibility NE 21:2012 , EN 61326-3-2:2008
Degree of protection IEC 60529:2001
Input EN 60947-5-6:2000
Ambient conditions
Ambient temperature -20 … 60 °C (-4 … 140 °F)
Mechanical specifications
Degree of protection IP20
Connection screw terminals
Mass approx. 150 g
Dimensions 20 x 119 x 115 mm (0.8 x 4.7 x 4.5 inch) (W x H x D) , housing type B2
Mounting on 35 mm DIN mounting rail acc. to EN 60715:2001
Data for application in connection with hazardous areas
EU-type examination certificate EXA 16 ATEX 0001 X
Marking Ex-Hexagon II 3(1)G Ex nA nC [ia Ga] IIC T4 Gc
Ex-Hexagon II (1)D [Ex ia Da] IIIC
Ex-Hexagon I (M1) [Ex ia Ma] I
Input Ex ia
Voltage 10.5 V
Current 17.1 mA
Power 45 mW (linear characteristic)
Supply
Maximum safe voltage 250 V AC (Attention! Um is no rated voltage.)
Output
Maximum safe voltage 250 V AC (Attention! The rated voltage can be lower.)
Galvanic isolation
Input/Output safe electrical isolation acc. to IEC/EN 60079-11, voltage peak value 375 V
Input/power supply safe electrical isolation acc. to IEC/EN 60079-11, voltage peak value 375 V
Directive conformity
Directive 2014/34/EU EN 60079-0:2012+A11:2013 , EN 60079-11:2012 , EN 60079-15:2010
International approvals
UL approval E106378
Control drawing 116-0423 (cULus)
IECEx approval
IECEx certificate IECEx EXA 16.0001X
IECEx marking Ex nA nC [ia Ga] IIC T4 Gc , [Ex ia Da] IIIC , [Ex ia Ma] I
General information
Supplementary information Observe the certificates, declarations of conformity, instruction manuals, and manuals where applicable. For information see www.pepperl-fuchs.com.

 

Associated Products: KFD2-SR3-Ex2.2S

Matching System Components

Interface for Power Rail, Supply current ≤ 4 A, Replaceable fuse, Relay contact output, reversible, LED status indication

Cable trunking is integrated in the mounting profile, Safe spacious separation of safe and hazardous signals, No additional cable guides necessary, Standard length 1.8 m (5.8 ft), simple to customize to application space, With mounting aids

Cable trunking with integrated Power Rail UPR-03, Safe spacious separation of safe and hazardous signals, No additional cable guides necessary, Provides DC supply voltage to all equipped K-System modules, Standard length 1.8 m (5.8 ft), simple to customize to application space, With end caps UPR-E, cover and mounting aids

Accessories

1-channel, Dry contact input, For line fault detection (LFD)

3-pin screw terminal, For KF modules of K-System, Packaging unit: 5 pieces green

3-pin screw terminal, For KF modules of K-System, Packaging unit: 5 pieces blue

Coding of K-System terminal blocks, Coding of LB/FB-System front sockets, Packaging unit: 20 x 6 coding pins

Weight 0.15 kg
Dimensions 11.5 × 2.0 × 11.9 cm