			$ 322.46 – $ 428.95Price range: $ 322.46 through $ 428.95
| Article number | 6EP1336-3BA10 | 
| Product | SITOP PSU8200 | 
| Power supply, type | 24 V/20 A | 
| Input | |
| type of the power supply network | 1-phase and 2-phase AC or DC | 
| supply voltage at AC | |
| ● minimum rated value | 120 V | 
| ● maximum rated value | 230 V | 
| ● initial value | 85 V; Derating of temperature necessary down to 50 °C at Vin < 100 V AC or DC | 
| ● full-scale value | 275 V | 
| supply voltage | |
| ● 1 at AC rated value | |
| ● 2 at AC rated value | |
| ● at DC | 110 … 220 V | 
| input voltage | |
| ● 1 at AC | |
| ● 2 at AC | |
| ● at DC | 88 … 350 V | 
| design of input wide range input | Yes | 
| operating condition of the mains buffering | at Vin = 230 V | 
| buffering time for rated value of the output current in the event of power failure minimum | 20 ms | 
| operating condition of the mains buffering | at Vin = 230 V | 
| line frequency | |
| ● 1 rated value | 50 Hz | 
| ● 2 rated value | 60 Hz | 
| line frequency | 45 … 65 Hz | 
| input current | |
| ● at rated input voltage 120 V | 4.6 A | 
| ● at rated input voltage 230 V | 2.5 A | 
| current limitation of inrush current at 25 °C maximum | 20 A | 
| I2t value maximum | 5 A²·s | 
| fuse protection type | Yes | 
| ● in the feeder | Recommended miniature circuit breaker at 1-phase operation: 10 A characteristic C; required at 2-phase operation: circuit breaker 2-pole connected or circuit breaker 3RV2711-1HD10 (UL 489) at 120 V or 3RV2711-1ED10 (UL 489) at 230 V | 
| Output | |
| voltage curve at output | Controlled, isolated DC voltage | 
| output voltage at DC rated value | 24 V | 
| output voltage | |
| ● at output 1 at DC rated value | 24 V | 
| relative overall tolerance of the voltage | 3 % | 
| relative control precision of the output voltage | |
| ● on slow fluctuation of input voltage | 0.1 % | 
| ● on slow fluctuation of ohm loading | 0.3 % | 
| residual ripple | |
| ● maximum | 100 mV | 
| ● typical | 80 mV | 
| voltage peak | |
| ● maximum | 200 mV | 
| ● typical | 100 mV | 
| adjustable output voltage | 24 … 28.8 V | 
| product function output voltage adjustable | Yes | 
| type of output voltage setting | via potentiometer | 
| display version for normal operation | Green LED for 24 V OK | 
| type of signal at output | Relay contact (NO contact, rating 60 V DC/ 0.3 A) for “24 V OK” | 
| behavior of the output voltage when switching on | No overshoot of Vout (soft start) | 
| response delay maximum | 1.5 s | 
| voltage increase time of the output voltage | |
| ● typical | 50 ms | 
| output current | |
| ● rated value | 20 A | 
| ● rated range | 0 … 20 A; +60 … +70 °C: Derating 3%/K | 
| supplied active power typical | 480 W | 
| short-term overload current | |
| ● on short-circuiting during the start-up typical | |
| ● at short-circuit during operation typical | 60 A | 
| duration of overloading capability for excess current | |
| ● on short-circuiting during the start-up | |
| ● at short-circuit during operation | 25 ms | 
| constant overload current | |
| ● on short-circuiting during the start-up typical | 30 A | 
| product feature | |
| ● bridging of equipment | Yes; switchable characteristic | 
| number of parallel-switched equipment resources for increasing the power | 2 | 
| Efficiency | |
| efficiency in percent | 93 % | 
| power loss [W] | |
| ● at rated output voltage for rated value of the output current typical | 42 W | 
| ● during no-load operation maximum | |
| Closed-loop control | |
| relative control precision of the output voltage with rapid fluctuation of the input voltage by +/- 15% typical | 0.5 % | 
| relative control precision of the output voltage load step of resistive load 50/100/50 % typical | 1 % | 
| setting time | |
| ● load step 50 to 100% typical | 1 ms | 
| ● load step 100 to 50% typical | 1 ms | 
| relative control precision of the output voltage at load step of resistive load 10/90/10 % typical | |
| setting time | |
| ● load step 10 to 90% typical | |
| ● load step 90 to 10% typical | |
| ● maximum | 5 ms | 
| Protection and monitoring | |
| design of the overvoltage protection | < 33 V | 
| ● typical | 21.5 A | 
| property of the output short-circuit proof | Yes | 
| design of short-circuit protection | Alternatively, constant current characteristic approx. 23 A or latching shutdown | 
| enduring short circuit current RMS value | |
| ● typical | 23 A | 
| overcurrent overload capability in normal operation | overload capability 150 % Iout rated up to 5 s/min | 
| display version for overload and short circuit | LED yellow for “overload”, LED red for “latching shutdown” | 
| Safety | |
| galvanic isolation between input and output | Yes | 
| galvanic isolation | Safety extra-low output voltage Uout acc. to EN 60950-1 and EN 50178 | 
| operating resource protection class | Class I | 
| leakage current | |
| ● maximum | 3.5 mA | 
| ● typical | 1 mA | 
| protection class IP | IP20 | 
| Approvals | |
| certificate of suitability | |
| ● CE marking | Yes | 
| ● UL approval | Yes; cULus-Listed (UL 508, CSA C22.2 No. 107.1), File E197259; cCSAus (CSA C22.2 No. 60950-1, UL 60950-1) | 
| ● CSA approval | Yes; cULus-Listed (UL 508, CSA C22.2 No. 107.1), File E197259; cCSAus (CSA C22.2 No. 60950-1, UL 60950-1) | 
| ● cCSAus, Class 1, Division 2 | No | 
| ● ATEX | No | 
| certificate of suitability | |
| ● IECEx | No | 
| ● NEC Class 2 | No | 
| ● ULhazloc approval | No | 
| ● FM registration | No | 
| type of certification CB-certificate | Yes | 
| certificate of suitability | |
| ● EAC approval | Yes | 
| certificate of suitability shipbuilding approval | Yes | 
| shipbuilding approval | ABS, DNV GL | 
| Marine classification association | |
| ● American Bureau of Shipping Europe Ltd. (ABS) | Yes | 
| ● French marine classification society (BV) | No | 
| ● DNV GL | Yes | 
| ● Lloyds Register of Shipping (LRS) | No | 
| ● Nippon Kaiji Kyokai (NK) | No | 
| EMC | |
| standard | |
| ● for emitted interference | EN 55022 Class B | 
| ● for mains harmonics limitation | EN 61000-3-2 | 
| ● for interference immunity | EN 61000-6-2 | 
| environmental conditions | |
| ambient temperature | |
| ● during operation | -25 … +70 °C; With natural convection; startup tested starting from -40 °C nominal voltage | 
| ● during transport | -40 … +85 °C | 
| ● during storage | -40 … +85 °C | 
| environmental category according to IEC 60721 | Climate class 3K3, 5 … 95% no condensation | 
| Mechanics | |
| type of electrical connection | screw-type terminals | 
| ● at input | L, N, PE: 1 screw terminal each for 0.2 … 4 mm² single-core/finely stranded | 
| ● at output | +, -: 2 screw terminals each for 0.2 … 4 mm² | 
| ● for auxiliary contacts | 13, 14 (alarm signal): 1 screw terminal each for 0.14 … 1.5 mm² | 
| width of the enclosure | 90 mm | 
| height of the enclosure | 125 mm | 
| depth of the enclosure | 125 mm | 
| required spacing | |
| ● top | 50 mm | 
| ● bottom | 50 mm | 
| ● left | 0 mm | 
| ● right | 0 mm | 
| net weight | 1.2 kg | 
| product feature of the enclosure housing can be lined up | Yes | 
| fastening method | Snaps onto DIN rail EN 60715 35×7.5/15 | 
| electrical accessories | Buffer module | 
| mechanical accessories | Device identification label 20 mm × 7 mm, TI-grey 3RT2900-1SB20 | 
| MTBF at 40 °C | 667 048 h | 
| other information | Specifications at rated input voltage and ambient temperature +25 °C (unless otherwise specified) | 
| Article number | 6EP3334-8SB00-0AY0 | 
| Product | SITOP PSU8200 | 
| Input | |
| type of the power supply network | 1-phase AC | 
| supply voltage at AC | |
| ● initial value | Automatic range selection | 
| supply voltage | |
| ● 1 at AC rated value | 120 V | 
| ● 2 at AC rated value | 230 V | 
| input voltage | |
| ● 1 at AC | 85 … 132 V | 
| ● 2 at AC | 170 … 264 V | 
| design of input wide range input | No | 
| operating condition of the mains buffering | at Vin = 120/230 V | 
| buffering time for rated value of the output current in the | 35 ms | 
| event of power failure minimum | |
| operating condition of the mains buffering | at Vin = 120/230 V | 
| line frequency | |
| ● 1 rated value | 50 Hz | 
| ● 2 rated value | 60 Hz | 
| line frequency | 47 … 63 Hz | 
| input current | |
| ● at rated input voltage 120 V | 4A | 
| ● at rated input voltage 230 V | 1.9A | 
| current limitation of inrush current at 25 °C maximum | 10A | 
| I2t value maximum | 0.3 A²·s | 
| fuse protection type | T 6.3 A (not accessible) | 
| ● in the feeder | Recommended miniature circuit breaker at 1-phase operation: from 6 A (10 A) characteristic C (B); required at 2-phase operation: circuit breaker 2-pole connected or circuit breaker 3RV2011-1EA10 (setting 3.8 A) or 3RV2711-1ED10 (UL 489) at 230 V; 3RV2011-1DA10 (setting 3 A) or 3RV2711-1DD10 (UL 489) at 400/500 V | 
| Output | |
| voltage curve at output | Controlled, isolated DC voltage | 
| output voltage at DC rated value | 24v | 
| output voltage | |
| ● at output 1 at DC rated value | 24V | 
| relative overall tolerance of the voltage | 3% | 
| relative control precision of the output voltage | |
| ● on slow fluctuation of input voltage | 0.1% | 
| ● on slow fluctuation of ohm loading | 0.3% | 
| residual ripple | |
| ● maximum | 50 mV | 
| voltage peak | |
| ● maximum | 200 mV | 
| adjustable output voltage | 24 … 28.8 V | 
| product function output voltage adjustable | Yes | 
| type of output voltage setting | via potentiometer; max. 240 W | 
| display version for normal operation | Green LED for 24 V OK | 
| type of signal at output | Relay contact (NO contact, rating 60 V DC/ 0.3 A) for “24 V OK” | 
| behavior of the output voltage when switching on | Overshoot of Vout approx. 3 % | 
| response delay maximum | 1.5 s | 
| voltage increase time of the output voltage | |
| ● typical | 70 ms | 
| output current | |
| ● rated value | 10A | 
| ● rated range | 0 … 10 A; +60 … +70 °C: Derating 2%/K; as of Ua>24 V: 4% [Ia]/V [Ua]; at Ue<100 V/<200 V: 80% Ia rated | 
| supplied active power typical | 240 W | 
| short-term overload current | |
| ● at short-circuit during operation typical | 30 A | 
| duration of overloading capability for excess current | |
| ● at short-circuit during operation | 25 ms | 
| constant overload current | |
| ● on short-circuiting during the start-up typical product feature | 12 A | 
| ● bridging of equipment | Yes; switchable characteristic | 
| number of parallel-switched equipment resources for increasing the power | 2 | 
| Efficiency | |
| efficiency in percent | 94% | 
| power loss [W] | |
| ● at rated output voltage for rated value of the output current typical | 18 W | 
| ● during no-load operation maximum | 1.5 W | 
| Closed-loop control | |
| relative control precision of the output voltage with rapid fluctuation of the input voltage by +/- 15% typical | 0.1% | 
| relative control precision of the output voltage load step of | 4% | 
| resistive load 50/100/50 % typical | |
| setting time | |
| ● load step 50 to 100% typical | 0.25 ms | 
| ● load step 100 to 50% typical | 0.5 ms | 
| relative control precision of the output voltage at load step | 4% | 
| of resistive load 10/90/10 % typical | |
| setting time | |
| ● load step 10 to 90% typical | 0.25 ms | 
| ● load step 90 to 10% typical | 0.5 ms | 
| ● maximum | 1 ms | 
| Protection and monitoring | |
| design of the overvoltage protection | < 33 V | 
| ● typical | 12 A | 
| property of the output short-circuit proof | Yes | 
| design of short-circuit protection | Alternatively, constant current characteristic approx. 12 A or latching shutdown | 
| enduring short circuit current RMS value | |
| ● typical | 12 A | 
| overcurrent overload capability in normal operation | overload capability 150 % Iout rated up to 5 s/min | 
| display version for overload and short circuit | LED yellow for “overload”, LED red for “latching shutdown” | 
| Safety | |
| galvanic isolation between input and output | Yes | 
| galvanic isolation | Safety extra-low output voltage Uout acc. to EN 60950-1 and EN 50178 | 
| operating resource protection class | Class I | 
| leakage current | |
| ● maximum | 3.4 mA | 
| ● typical | 1 mA | 
| protection class IP | IP20 | 
| Approvals | |
| certificate of suitability | |
| ● CE marking | Yes | 
| ● UL approval | Yes; cULus-Listed (UL 508, CSA C22.2 No. 107.1), File E197259; cCSAus (CSA C22.2 No. 60950-1, UL 60950-1) | 
| ● CSA approval | Yes; cULus-Listed (UL 508, CSA C22.2 No. 107.1), File E197259; cCSAus (CSA C22.2 No. 60950-1, UL 60950-1) | 
| ● cCSAus, Class 1, Division 2 | No | 
| ● ATEX | No | 
| certificate of suitability | |
| ● IECEx | No | 
| ● NEC Class 2 | No | 
| ● ULhazloc approval | No | 
| ● FM registration | No | 
| type of certification CB-certificate | Yes | 
| certificate of suitability | |
| ● EAC approval | Yes | 
| certificate of suitability shipbuilding approval | Yes | 
| shipbuilding approval | ABS, DNV GL | 
| Marine classification association | |
| ● American Bureau of Shipping Europe Ltd. (ABS) | Yes | 
| ● French marine classification society (BV) | No | 
| ● DNV GL | Yes | 
| ● Lloyds Register of Shipping (LRS) | No | 
| ● Nippon Kaiji Kyokai (NK) | No | 
| EMC | |
| standard | |
| ● for emitted interference | EN 55022 Class B | 
| ● for mains harmonics limitation | EN 61000-3-2 | 
| ● for interference immunity | EN 61000-6-2 | 
| environmental conditions | |
| ambient temperature | |
| ● during operation | -25 … +70 °C; With natural convection; startup tested starting from -40 °C nominal voltage | 
| ● during transport | -40 … +85 °C | 
| ● during storage | -40 … +85 °C | 
| environmental category according to IEC 60721 | Climate class 3K3, 5 … 95% no condensation | 
| Mechanics | |
| type of electrical connection | screw-type terminals | 
| ● at input | L, N, PE: 1 screw terminal each for 0.2 … 2.5 mm² single-core/finely stranded | 
| ● at output | +, -: 2 screw terminals each for 0.2 … 2.5 mm² | 
| 13, 14 (alarm signal): 1 screw terminal each for 0.14 … 1.5 mm²; 15, 16 (Remote): 1 screw terminal each for 0.14 … 1.5 mm² | |
| width of the enclosure | 55 mm | 
| height of the enclosure | 125 mm | 
| depth of the enclosure | 125 mm | 
| required spacing | |
| ● top | 50 mm | 
| ● bottom | 50 mm | 
| ● left | 0 mm | 
| ● right | 0 mm | 
| net weight | 1kg | 
| product feature of the enclosure housing can be lined up | Yes | 
| fastening method | Snaps onto DIN rail EN 60715 35×7.5/15 | 
| electrical accessories | Buffer module | 
| mechanical accessories | Device identification label 20 mm × 7 mm, TI-grey 3RT2900-1SB20 | 
| MTBF at 40 °C | 1 292 102 h | 
| other information | Specifications at rated input voltage and ambient temperature +25 °C (unless otherwise specified) |