Safety Relay Unit – G9SE Series – Omron Safety Relay Unit
$ 158.84
SKU: N/A
Safety outputs | Auxiliary outputs *3 |
Max. OFF-delay time *1 |
Rated voltage | Model | |
---|---|---|---|---|---|
Instantaneous | OFF-delayed *2 | ||||
DPST-NO | – | 1 (Solid-state) | – | 24 VDC | G9SE-201 |
4PST-NO | G9SE-401 | ||||
DPST-NO | DPST-NO | 5 s | G9SE-221-T05 | ||
DPST-NO | DPST-NO | 30 s | G9SE-221-T30 |
Specification
Power Input
Model | G9SE-201 | G9SE-401 | G9SE-221-T[] |
---|---|---|---|
Rated supply voltage | 24 VDC | ||
Operating voltage range | -15% to 10% of rated supply voltage | ||
Rated power consumption *1 | 3 W max. | 4 W max. |
Outputs
Model | G9SE-201 | G9SE-401 | G9SE-221-T[] |
---|---|---|---|
Safety output OFF-delayed Safety output |
Contact output 250 VAC 5 A 30 VDC 5 A (resistive load) |
||
Auxiliary output | PNP transistor output Load current: 100 mA DC max. |
Characteristics
Model | G9SE-201 | G9SE-401 | G9SE-221-T[] | ||
---|---|---|---|---|---|
Operating time (OFF to ON state) *2 | 100 ms Max. *3 | ||||
Response time (ON to OFF state) *4 | 15 ms Max. | ||||
Accuracy of OFF-delay time | – | Within plus or minus 10% of the set value |
|||
Inputs | Input current | 5 mA Min. | |||
ON voltage | 11 VDC Min. | ||||
OFF voltage | 5 VDC Max. | ||||
OFF current | 1 mA Max. | ||||
Maximum cable length | 100 m Max. | ||||
Reset input time | 250 ms Min. | ||||
Contact outputs |
Contact resistance *5 | 100 mΩ | |||
Mechanical durability | 5,000,000 operations Min. | ||||
Electrical durability | 50,000 operations Min. | ||||
Switching specification Inductive load (IEC/EN60947-5-1) |
AC15: 240 VAC 2 A DC13: 24 VDC 1.5 A |
||||
Minimum applicable load | 24 VDC 4 mA | ||||
Conditional short-circuit current (IEC/EN60947-5-1) |
100 A *6 | ||||
Pollution degree | 2 | ||||
Over voltage category (IEC/EN60664-1) | Safety output: Class III, the others: Class II | ||||
Insulation specification |
Isolation voltage (Ui) | 250 VAC | |||
Impulse withstand voltage (IEC/ EN60947-5-1) |
Between input and output |
6 kV | |||
Between different poles of output |
6 kV (between 13-14/23-24 and 33-34/43-44 (37-38/47-48)) 4 kV (between 13-14 and 23-24, between 33-34 (37-38) and 43-44 (47-48)) |
||||
Dielectric strength |
Between input and output |
2,200 VDC | |||
Between different poles of output |
1,500 VAC | ||||
Insulation resistance | 100 MΩ | ||||
Vibration resistance *7 | Frequency: 10 to 55 to 10 Hz Amplitude: 0.35 mm half amplitude (0.7 mm double amplitude) |
||||
Mechanical shock re- sistance *7 |
Destruction | 300 m/s2 | |||
Malfunction | 100 m/s2 | ||||
Surrounding Air Temperature | -10 to 55°C (No freezing or condensation) | ||||
Ambient humidity | 25% to 85%RH | ||||
Degree of protection | IP20 | ||||
Weight | approx. 150 g | approx. 180 g |
*1 Power consumption of loads not included.
*2 The operating time is the time it takes for the safety contact to close after the safety inputs and feedback-reset input are turned ON. Not includes bounce time.
*3 This is in normal operation. When executing non-regular self-diagnosis for Safety output circuit, G9SE operating time become 500 ms max..
*4 The response time is the time it takes for the safety main contact to open after the safety input is turned OFF. Includes bouncetime.
*5 This is initial value using the voltage-drop method with 1A at 5VDC.
*6 Use for each contact output an 8A fuse that conforms to IEC 60127 as a short-circuit protection device. This fuse is not included with the G9SE.
*7 Condition: G9SE is mounted to mounting surface with screw and the screw mounting attachment. In the case of DIN rail mounting, mount DIN rail with G9SE to the place without big vibration. (Amplitude guideline: Less than 0.15 mm half amplitude (0.3 mm double amplitude))
*2 The operating time is the time it takes for the safety contact to close after the safety inputs and feedback-reset input are turned ON. Not includes bounce time.
*3 This is in normal operation. When executing non-regular self-diagnosis for Safety output circuit, G9SE operating time become 500 ms max..
*4 The response time is the time it takes for the safety main contact to open after the safety input is turned OFF. Includes bouncetime.
*5 This is initial value using the voltage-drop method with 1A at 5VDC.
*6 Use for each contact output an 8A fuse that conforms to IEC 60127 as a short-circuit protection device. This fuse is not included with the G9SE.
*7 Condition: G9SE is mounted to mounting surface with screw and the screw mounting attachment. In the case of DIN rail mounting, mount DIN rail with G9SE to the place without big vibration. (Amplitude guideline: Less than 0.15 mm half amplitude (0.3 mm double amplitude))