SIMATIC S7-1500 – System Power Supply – Siemens Power Supply
$ 300.20 – $ 882.28
SKU: N/A
Power supplies (PS) supply the internal electronics of the S7-1500 modules with power via the backplane bus. They are required, for example, if the power supplied by the CPU or the interface modules to the backplane bus is not sufficient to supply all connected modules, or if more than one power segment in the S7-1500 configuration or in distributed configuration in ET 200MP should be implemented.
In addition, the PS 60W 24/48/60V DC HF allows all S7-1500 CPUs to retentively store their entire work memory (data) thanks to an appropriate power buffer.
Siemens Power Supplies S7-1500 Product Specifications:
Article number | 6ES7505-0KA00-0AB0 | 6ES7505-0RA00-0AB0 | 6ES7505-0RB00-0AB0 | 6ES7507-0RA00-0AB0 | |
S7-1500, PS 25W 24V DC | S7-1500, PS 60W 24/48/60V DC | S7-1500, PS 60W 24/48/60V DC HF | S7-1500, PS 60W 120/230V AC/DC | ||
General information | |||||
Product type designation | PS 25W 24VDC | PS 60 W 24/48/60 V DC | PS 60 W 24/48/60 V DC HF | PS 60 W 120/230 V AC/DC | |
HW functional status | FS02 | FS03 | E01 | E01 | |
Firmware version | V1.0.0 | V1.0.0 | V1.0.0 | V1.0.0 | |
Engineering with | |||||
● STEP 7 TIA Portal configurable/integrated from version | V12 / V12 | V12 / V12 | V14 SP1 | V12 / V12 | |
● STEP 7 configurable/integrated from version | V5.5 SP3 or higher | V5.5 SP3 or higher | V5.5 SP3 or higher | ||
Installation type/mounting | |||||
Rail mounting | Yes | Yes | |||
Supply voltage | |||||
Rated value (DC) | 24 V | 24 V / 48 V / 60 V | 24 V / 48 V / 60 V | 120 V / 230 V | |
permissible range, lower limit (DC) | 19.2 V; Static 19.2 V, dynamic 18.5 V | 19.2 V; Static 19.2 V, dynamic 18.5 V | 19.2 V; Static 19.2 V, dynamic 18.5 V | 88 V | |
permissible range, upper limit (DC) | 28.8 V; Static 28.8 V, dynamic 30.2 V | 72 V; Static 72 V, dynamic 75.5 V | 72 V; Static 72 V, dynamic 75.5 V | 300 V | |
Rated value (AC) | 120 V / 230 V | ||||
permissible range, lower limit (AC) | 85 V | ||||
permissible range, upper limit (AC) | 264 V | ||||
Reverse polarity protection | Yes | Yes | Yes | ||
Short-circuit protection | Yes | Yes | Yes | Yes | |
Line frequency | |||||
● Rated value 50 Hz | Yes | ||||
● permissible range, lower limit | 47 Hz | ||||
● permissible range, upper limit | 63 Hz | ||||
Mains buffering | |||||
● Mains/voltage failure stored energy time | 20 ms | 20 ms | 20 ms | 20 ms | |
Input current | |||||
Rated value at 24 V DC | 1.3 A | 3 A | 3 A | ||
Rated value at 48 V DC | 1.5 A | 1.5 A | |||
Rated value at 60 V DC | 1.2 A | 1.2 A | |||
Rated value at 120 V DC | 0.6 A | ||||
Rated value at 230 V DC | 0.3 A | ||||
Rated value at 120 V AC | 0.6 A | ||||
Rated value at 230 V AC | 0.34 A | ||||
Inrush current, max. | ≤ 8 A for t ≤ 1 s | ||||
Output current | |||||
Short-circuit protection | Yes | Yes | Yes | Yes | |
Power | |||||
Infeed power to the backplane bus | 25 W | 60 W | 60 W | 60 W | |
Power loss | |||||
Power loss at nominal rating conditions | 6.2 W | 12 W | 12 W | 12 W | |
Interrupts/diagnostics/status information | |||||
Status indicator | Yes | Yes | Yes | Yes | |
Potential separation | |||||
primary/secondary | Yes | Yes; Electrical isolation for 230 V AC (reinforced isolation) | Yes | ||
Isolation | |||||
Isolation tested with | 707 V DC (type test) | 2 500 V DC/2 s (routine test) | 2 500 V DC (type test) | 2 500 V DC/2 s (routine test) | |
EMC | |||||
Interference immunity against voltage surge | |||||
● Interference immunity on supply lines acc. to IEC 61000-4-5 | Yes; ±1 kV (acc. to IEC 61000-4-5; 1995; surge symm.), ±2 kV (acc. to IEC 61000-4-5; 1995; surge asymm.), no external protective circuit required | Yes; ±1 kV (acc. to IEC 61000-4-5; 1995; surge symm.), ±2 kV (acc. to IEC 61000-4-5; 1995; surge asymm.), no external protective circuit required | Yes; ±1 kV (acc. to IEC 61000-4-5; 1995; surge symm.), ±2 kV (acc. to IEC 61000-4-5; 1995; surge asymm.), no external protective circuit required | Yes; ±1 kV (acc. to IEC 61000-4-5; 1995; surge symm.), ±2 kV (acc. to IEC 61000-4-5; 1995; surge asymm.), no external protective circuit required | |
Degree and class of protection | |||||
IP degree of protection | IP20 | IP20 | IP20 | IP20 | |
Equipment protection class | III, with protective conductor | I, with protective conductor | I, with protective conductor | I, with protective conductor | |
Ambient conditions | |||||
Altitude during operation relating to sea level | |||||
● Installation altitude above sea level, max. | 5 000 m; Restrictions for installation altitudes > 2 000 m, see manual | ||||
Dimensions | |||||
Width | 35 mm | 70 mm | 105 mm | 70 mm | |
Height | 147 mm | 147 mm | 147 mm | 147 mm | |
Depth | 129 mm | 129 mm | 129 mm | 129 mm | |
Weights | |||||
Weight, approx. | 350 g | 600 g | 865 g | 600 g |
Weight | N/A |
---|---|
Dimensions | N/A |
Related products
-
Select options This product has multiple variants. The options may be chosen on the product page Details
-
Select options This product has multiple variants. The options may be chosen on the product page Details
-
Select options This product has multiple variants. The options may be chosen on the product page Details