SIMATIC S7-400 – SM 431 Analog Input Modules – Siemens
$ 708.81 – $ 1,858.01
SKU: N/A
Analog input modules can be used to connect the control to analog process signals. They are suitable for the connection of voltage and current sensors, thermocouples, resistors and resistance thermometers.
Siemens Analog Input Modules SIMATIC S7-400 Product Specifications:
Article number | 6ES7431-0HH00-0AB0 | 6ES7431-1KF20-0AB0 | 6ES7431-1KF00-0AB0 | 6ES7431-1KF10-0AB0 |
SIMATIC S7-400, ANALOG INPUT | SIMATIC S7-400, SM 431 | SIMATIC S7-400, SM 431 | SIMATIC S7-400, SM 431 | |
Supply voltage | ||||
Load voltage L+ | ||||
● Rated value (DC) | 24 V; Only required for supplying 2-wire transmitters | 24 V; Only required for supplying 2-wire transmitters | not necessary | 24 V; Only required for supplying 2-wire transmitters |
● Reverse polarity protection | Yes | Yes | Yes | |
Input current | ||||
from load voltage L+ (without load), max. | 400 mA; for 16 connected, fully controlled 2-wire transmitters | 200 mA; for 8 connected, fully controlled 2-wire transmitters | 200 mA; for 8 connected, fully controlled 2-wire transmitters | |
from backplane bus 5 V DC, max. | 100 mA | 1 000 mA | 350 mA | 600 mA |
Power loss | ||||
Power loss, typ. | 2 W | 4.9 W | 1.8 W | 3.5 W |
Analog inputs | ||||
Number of analog inputs | 16 | 8 | 8 | 8 |
● For voltage/current measurement | 16 | 8 | 8 | 8 |
● For resistance measurement | 4 | 4 | 4 | |
permissible input voltage for voltage input (destruction limit), max. | 20 V; 20 V DC permanent, 75 V DC for max. 1 s (duty factor 1:20) | 18 V; 18 V continuous, 75 V for 1 ms (mark to space ratio 1:20) | 50 V | 18 V; 18 V continuous, 75 V for 1 ms (mark to space ratio 1:20) |
permissible input current for current input (destruction limit), max. | 40 mA | 40 mA; Permanent | 50 mA; 40 mA continuous | 40 mA; Permanent |
Constant measurement current for resistance-type transmitter, typ. | 1.67 mA | 1.67 mA | 1.67 mA | 1.67 mA |
Input ranges | ||||
● Voltage | Yes | Yes | Yes | Yes |
● Current | Yes | Yes | Yes | Yes |
● Thermocouple | No | No | No | Yes |
● Resistance thermometer | No | No | No | Yes |
● Resistance | No | Yes | Yes | Yes |
Input ranges (rated values), voltages | ||||
● 1 V to 5 V | Yes | Yes | Yes | Yes |
— Input resistance (1 V to 5 V) | 100 kΩ | 10 MΩ | 200 kΩ | 1 MΩ |
● -1 V to +1 V | Yes | Yes | Yes | Yes |
— Input resistance (-1 V to +1 V) | 10 MΩ | 10 MΩ | 200 kΩ | 1 MΩ |
● -10 V to +10 V | Yes | Yes | Yes | Yes |
— Input resistance (-10 V to +10 V) | 100 kΩ | 100 kΩ | 200 kΩ | 1 MΩ |
● -2.5 V to +2.5 V | Yes | |||
— Input resistance (-2.5 V to +2.5 V) | 1 MΩ | |||
● -250 mV to +250 mV | Yes | |||
— Input resistance (-250 mV to +250 mV) | 1 MΩ | |||
● -5 V to +5 V | Yes | |||
— Input resistance (-5 V to +5 V) | 1 MΩ | |||
● -500 mV to +500 mV | Yes | |||
— Input resistance (-500 mV to +500 mV) | 1 MΩ | |||
● -80 mV to +80 mV | Yes | |||
— Input resistance (-80 mV to +80 mV) | 1 MΩ | |||
Input ranges (rated values), currents | ||||
● 0 to 20 mA | Yes | |||
— Input resistance (0 to 20 mA) | 50 Ω | |||
● -20 mA to +20 mA | Yes | Yes | Yes | |
— Input resistance (-20 mA to +20 mA) | 50 Ω | 50 Ω | 80 Ω | |
● 4 mA to 20 mA | Yes | Yes | Yes | Yes |
— Input resistance (4 mA to 20 mA) | 50 Ω | 50 kΩ | 80 Ω | 50 Ω |
Input ranges (rated values), thermocouples | ||||
● Type B | Yes | |||
— Input resistance (Type B) | 1 MΩ | |||
● Type E | Yes | |||
— Input resistance (Type E) | 1 MΩ | |||
● Type J | Yes | |||
— Input resistance (type J) | 1 MΩ | |||
● Type K | Yes | |||
— Input resistance (Type K) | 1 MΩ | |||
● Type L | Yes | |||
— Input resistance (Type L) | 1 MΩ | |||
● Type N | Yes | |||
— Input resistance (Type N) | 1 MΩ | |||
● Type R | Yes | |||
— Input resistance (Type R) | 1 MΩ | |||
● Type S | Yes | |||
— Input resistance (Type S) | 1 MΩ | |||
● Type T | Yes | |||
— Input resistance (Type T) | 1 MΩ | |||
● Type U | Yes | |||
— Input resistance (Type U) | 1 MΩ | |||
Input ranges (rated values), resistance thermometer | ||||
● Ni 100 | Yes | |||
— Input resistance (Ni 100) | 1 MΩ | |||
● Ni 1000 | Yes | |||
— Input resistance (Ni 1000) | 1 MΩ | |||
● Pt 100 | Yes | |||
— Input resistance (Pt 100) | 1 MΩ | |||
● Pt 1000 | Yes | |||
● Pt 10000 | Yes | |||
● Pt 200 | Yes | |||
— Input resistance (Pt 200) | 1 MΩ | |||
● Pt 500 | Yes | |||
— Input resistance (Pt 500) | 1 MΩ | |||
Input ranges (rated values), resistors | ||||
● 0 to 48 ohms | Yes | |||
— Input resistance (0 to 48 ohms) | 1 MΩ | |||
● 0 to 150 ohms | Yes | |||
— Input resistance (0 to 150 ohms) | 1 MΩ | |||
● 0 to 300 ohms | Yes | |||
— Input resistance (0 to 300 ohms) | 1 MΩ | |||
● 0 to 600 ohms | Yes | Yes | Yes | |
— Input resistance (0 to 600 ohms) | usable up to 500 ohms | 1 MΩ | ||
● 0 to 6000 ohms | Yes; Usable up to 5000 Ohm | |||
— Input resistance (0 to 6000 ohms) | 1 MΩ | |||
Thermocouple (TC) | ||||
Temperature compensation | ||||
— parameterizable | Yes | |||
— internal temperature compensation | No | |||
— external temperature compensation with Pt100 | Yes | |||
— external temperature compensation with compensations socket | Yes | |||
— dynamic reference temperature value | Yes | |||
Characteristic linearization | ||||
● parameterizable | Yes | |||
— for thermocouples | Type B, E, J, K, L, N, R, S, T, U | |||
— for resistance thermometer | Pt100, Pt200, Pt500, Pt1000, Ni100, Ni1000 | |||
Cable length | ||||
● shielded, max. | 200 m | 200 m | 200 m | 200 m; 50 m with thermocouples and input ranges ≤ 80 mV |
Analog value generation for the inputs | ||||
Integration and conversion time/resolution per channel | ||||
● Resolution with overrange (bit including sign), max. | 13 bit | 14 bit; 14 / 14 / 14 | 13 bit | 14 bit; with activated filtering: 16 bit |
● Integration time, parameterizable | Yes | Yes | Yes | Yes |
● Basic conversion time (ms) | 55 / 65 ms | 52 µs | 23 / 25 ms | 20.1 / 23.5 ms |
● Integration time (ms) | 50 / 60 ms | 16,7 / 20 ms | 16,7 / 20 ms | |
● Interference voltage suppression for interference frequency f1 in Hz | 50 / 60 Hz | none / 400 / 60 / 50 Hz | 50 / 60 Hz | 50 / 60 Hz |
Encoder | ||||
Connection of signal encoders | ||||
● for voltage measurement | Yes; possible | Yes; possible | Yes; possible | Yes; possible |
● for current measurement as 2-wire transducer | Yes | Yes; with external transmitter supply | Yes | |
● for current measurement as 4-wire transducer | Yes | Yes | Yes | Yes |
● for resistance measurement with two-wire connection | Yes; Line resistances are also measured | Yes; Line resistances are also measured | Yes; Line resistances are also measured | |
● for resistance measurement with three-wire connection | Yes; Line resistances are also measured | Yes; Line resistances are also measured | Yes | |
● for resistance measurement with four-wire connection | Yes | Yes | Yes | |
Errors/accuracies | ||||
Operational error limit in overall temperature range | ||||
● Voltage, relative to input range, (+/-) | 0.65 %; 1.0 % at 1 to 5 V; 0.65 % at ±1 V, ±10 V | 0.7 %; ±0.7 % at ±1 V; ±0.9 % at ±10 V, 1 to 5 V | 1 %; ±1.0 % at ±1 V; ±0.6 % at ±10 V; ±0.7 % at 1 to 5 V | 0.38 %; ±0.38 % at ±80 mV; ±0.35 % at ±250 mV, ±500 mV, ±1 V, ±2,5 V, ±5 V, 1 to 5 V, ±10 V |
● Current, relative to input range, (+/-) | 0.65 % | 0.8 %; at ±20 mA, 4 to 20 mA | 1 %; at ±20 mA, 4 to 20 mA | 0.35 %; ±20 mA, 0 to 20 mA, 4 to 20 mA |
● Resistance, relative to input range, (+/-) | 1 % | 1.25 %; 0 to 500 ohms (4-conductor measurement, in range of 600 ohms) | 0.5 % | |
● Resistance thermometer, relative to input range, (+/-) | 0.5 % | |||
● Thermocouple, relative to input range, (+/-) | TC Type B (±14.8 K), TC Type R (±9.4 K), TC Type S (±10.6 K), TC Type T (±2.2 K), TC Type E (±4.0 K), TC Type J (±5.2 K), TC Type K (±7.6 K), TC Type U (±3.5 K), TC Type L (±5.1 K), TC Type N (±5.5 K) | |||
Basic error limit (operational limit at 25 °C) | ||||
● Voltage, relative to input range, (+/-) | 0.25 %; 0.5% at 1 to 5 V; 0.25% at ±1 V, ±10 V | 0.6 %; 0.6 % at ±1 V; 0.75 % at ±10 V, 1 to 5 V | 0.7 %; 0.7% at ±1 V; 0.4% at ±10 V; 0.5% at 1 to 5 V | 0.15 %; ±0.15 % (±250 mV, ±500 mV, ±1 V, ±2.5 V, ±5 V, 1 to 5 V, ±10 V); ±0.17% (±80 mV) |
● Current, relative to input range, (+/-) | 0.25 %; at ±20 mA, 4 to 20 mA | 0.7 %; at ±20 mA, 4 to 20 mA | 0.7 %; at ±20 mA, 4 to 20 mA | 0.15 %; ±20 mA, 0 to 20 mA, 4 to 20 mA |
● Resistance, relative to input range, (+/-) | 0.7 %; 0 to 600 ohms | 0.8 %; 0 to 500 ohms (4-conductor measurement, in range of 600 ohms) | 0.15 %; ±0.15 % at 0 to 48 ohms (4-conductor measurement), 0 to 150 ohms (4-conductor measurement), 0 to 300 ohms (4-conductor measurement), 0 to 600 ohms (4-conductor measurement), 0 to 5000 ohms (4-conductor measurement, in range of 6000 ohms); ±0.3 % at 0 to 300 ohms (3-conductor measurement), 0 to 600 ohms (3-conductor measurement), 0 to 5000 ohms (3-conductor measurement, in range of 6000 ohms) | |
● Resistance thermometer, relative to input range, (+/-) | 0.3 % | |||
● Thermocouple, relative to input range, (+/-) | TC Type B (±8.2 K), TC Type R (±5.2 K), TC Type S (±5.9 K), TC Type T (±1.2 K), TC Type E (±1.8 K), TC Type J (±2.3 K), TC Type K (±3.4 K), TC Type U (±1.8 K), TC Type L (±2.3 K), TC Type N (±2.9 K) | |||
Interrupts/diagnostics/status information | ||||
Diagnostics function | No | No | No | No |
Potential separation | ||||
Potential separation analog inputs | ||||
● Potential separation analog inputs | No | Yes; internal/external | Yes; internal/external | Yes; internal/external |
● between the channels | No | No | No | No |
● between the channels and backplane bus | No | Yes | Yes | Yes |
● Between the channels and load voltage L+ | No | Yes | Yes | |
Isolation | ||||
Isolation tested with | 500 V AC/707 V DC, type test | 2 120 V DC between bus and analog section; 500 V DC between bus and local ground; 500 V DC between analog part and L+/M; 2 120 V DC between analog part and local ground; 2 120 V DC between L+/M and local ground | 2 120 V DC between bus and analog part; 500 V DC between bus and local ground; 2 120 V DC between analog part and local ground | 2 120 V DC between bus and L+/M; 2 120 V DC between bus and analog section; 500 V DC between bus and local ground; 500 V DC between analog section and L+/M; 2 120 V DC between analog section and local ground; 2 120 V DC between L+/M and local ground |
Dimensions | ||||
Width | 25 mm | 25 mm | 25 mm | 25 mm |
Height | 290 mm | 290 mm | 290 mm | 290 mm |
Depth | 210 mm | 210 mm | 210 mm | 210 mm |
Weights | ||||
Weight, approx. | 500 g | 500 g | 500 g | 500 g |
Article number | 6ES7431-7QH00-0AB0 | 6ES7431-7KF00-0AB0 | 6ES7431-7KF10-0AB0 |
SIMATIC S7-400, SM 431 | SM 431, 8AI, U/I/THERMO, 16BIT | SM 431, 8AI, RESIST./PT100, 16BIT, | |
Supply voltage | |||
Load voltage L+ | |||
● Rated value (DC) | 24 V; Only required for supplying 2-wire transmitters | ||
● Reverse polarity protection | Yes | ||
Input current | |||
from load voltage L+ (without load), max. | 400 mA; for 16 connected, fully controlled 2-wire transmitters | ||
from backplane bus 5 V DC, max. | 700 mA | 1 200 mA | 650 mA |
Power loss | |||
Power loss, typ. | 4.5 W | 4.6 W | 3.3 W |
Analog inputs | |||
Number of analog inputs | 16 | 8 | 8 |
● For voltage/current measurement | 16 | 8 | |
● For resistance measurement | 8 | 8 | |
permissible input voltage for voltage input (destruction limit), max. | 18 V; 18 V continuous, 75 V for 1 ms (mark to space ratio 1:20) | 35 V; 35 V continuous, 75 V for max. 1 s (mark to space ratio 1:20) | 35 V; 35 V continuous, 75 V for max. 1 s (mark to space ratio 1:20) |
permissible input current for current input (destruction limit), max. | 40 mA | 32 mA | |
Constant measurement current for resistance-type transmitter, typ. | 1.67 mA | 1 mA | |
Input ranges | |||
● Voltage | Yes | Yes | No |
● Current | Yes | Yes | No |
● Thermocouple | Yes | Yes | No |
● Resistance thermometer | Yes | No | Yes |
● Resistance | Yes | No | Yes |
Input ranges (rated values), voltages | |||
● 1 V to 5 V | Yes | Yes | |
— Input resistance (1 V to 5 V) | 1 MΩ | > 2 000 ohms | |
● -1 V to +1 V | Yes | Yes | |
— Input resistance (-1 V to +1 V) | 1 MΩ | ||
● -10 V to +10 V | Yes | Yes | |
— Input resistance (-10 V to +10 V) | 1 MΩ | ||
● -100 mV to +100 mV | Yes | ||
● -2.5 V to +2.5 V | Yes | Yes | |
— Input resistance (-2.5 V to +2.5 V) | 1 MΩ | ||
● -20 mV to +20 mV | Yes | ||
● -25 mV to +25 mV | Yes | ||
— Input resistance (-25 mV to +25 mV) | 1 MΩ | ||
● -250 mV to +250 mV | Yes | Yes | |
— Input resistance (-250 mV to +250 mV) | 1 MΩ | ||
● -5 V to +5 V | Yes | Yes | |
— Input resistance (-5 V to +5 V) | 1 MΩ | ||
● -50 mV to +50 mV | Yes | Yes | |
— Input resistance (-50 mV to +50 mV) | 1 MΩ | ||
● -500 mV to +500 mV | Yes | Yes | |
— Input resistance (-500 mV to +500 mV) | 1 MΩ | ||
● -80 mV to +80 mV | Yes | Yes | |
— Input resistance (-80 mV to +80 mV) | 1 MΩ | ||
Input ranges (rated values), currents | |||
● 0 to 20 mA | Yes | Yes | |
— Input resistance (0 to 20 mA) | 50 Ω | ||
● -10 mA to +10 mA | Yes | Yes | |
— Input resistance (-10 mA to +10 mA) | 50 Ω | ||
● -20 mA to +20 mA | Yes | Yes | |
— Input resistance (-20 mA to +20 mA) | 50 Ω | ||
● -3.2 mA to +3.2 mA | Yes | ||
● 4 mA to 20 mA | Yes | Yes | |
— Input resistance (4 mA to 20 mA) | 50 Ω | 50 Ω | |
● -5 mA to +5 mA | Yes | Yes | |
— Input resistance (-5 mA to +5 mA) | 50 Ω | ||
Input ranges (rated values), thermocouples | |||
● Type B | Yes | Yes | |
— Input resistance (Type B) | 1 MΩ | > 2 000 ohms | |
● Type E | Yes | Yes | |
— Input resistance (Type E) | 1 MΩ | ||
● Type J | Yes | Yes | |
— Input resistance (type J) | 1 MΩ | ||
● Type K | Yes | Yes | |
— Input resistance (Type K) | 1 MΩ | ||
● Type L | Yes | Yes | |
— Input resistance (Type L) | 1 MΩ | ||
● Type N | Yes | Yes | |
— Input resistance (Type N) | 1 MΩ | > 2 000 ohms | |
● Type R | Yes | Yes | |
— Input resistance (Type R) | 1 MΩ | ||
● Type S | Yes | Yes | |
— Input resistance (Type S) | 1 MΩ | ||
● Type T | Yes | Yes | |
— Input resistance (Type T) | 1 MΩ | ||
● Type U | Yes | Yes | |
— Input resistance (Type U) | 1 MΩ | ||
Input ranges (rated values), resistance thermometer | |||
● Ni 100 | Yes | Yes | |
— Input resistance (Ni 100) | 1 MΩ | > 10 000 ohms | |
● Ni 1000 | Yes | Yes; Different characteristics selectable: Europe/U.S. | |
— Input resistance (Ni 1000) | 1 MΩ | > 10 000 ohms | |
● Pt 100 | Yes | Yes | |
— Input resistance (Pt 100) | 1 MΩ | > 10 000 ohms | |
● Pt 1000 | Yes | Yes | |
— Input resistance (Pt 1000) | 1 MΩ | > 10 000 ohms | |
● Pt 200 | Yes | Yes | |
— Input resistance (Pt 200) | 1 MΩ | > 10 000 ohms | |
● Pt 500 | Yes | Yes | |
— Input resistance (Pt 500) | 1 MΩ | > 10 000 ohms | |
Input ranges (rated values), resistors | |||
● 0 to 48 ohms | Yes | ||
— Input resistance (0 to 48 ohms) | 1 MΩ | ||
● 0 to 150 ohms | Yes | ||
— Input resistance (0 to 150 ohms) | 1 MΩ | ||
● 0 to 300 ohms | Yes | ||
— Input resistance (0 to 300 ohms) | 1 MΩ | ||
● 0 to 600 ohms | Yes | ||
— Input resistance (0 to 600 ohms) | 1 MΩ | ||
● 0 to 6000 ohms | Yes; Usable up to 5000 Ohm | ||
— Input resistance (0 to 6000 ohms) | 1 MΩ | ||
Thermocouple (TC) | |||
Temperature compensation | |||
— parameterizable | Yes | Yes | |
— internal temperature compensation | Yes | ||
— external temperature compensation with Pt100 | Yes | ||
— external temperature compensation with compensations socket | Yes | Yes | |
— dynamic reference temperature value | Yes | Yes | |
Characteristic linearization | |||
● parameterizable | Yes | Yes | Yes |
— for thermocouples | Type B, E, J, K, L, N, R, S, T, U | Type B, E, J, K, L, N, R, S, T, U | |
— for resistance thermometer | Pt100, Pt200, Pt500, Pt1000, Ni100, Ni1000 | Pt100, Pt200, Pt500, Pt1000, Ni100, Ni1000; different characteristics selectable (Europe/U.S.) | |
Cable length | |||
● shielded, max. | 200 m; 50 m with thermocouples and input ranges ≤ 80 mV | 200 m | 200 m; 50 m with thermocouples and input ranges ±80 mV |
Analog value generation for the inputs | |||
Integration and conversion time/resolution per channel | |||
● Resolution with overrange (bit including sign), max. | 16 bit; 16 / 16 / 16 | 16 bit | 16 bit |
● Integration time, parameterizable | Yes | Yes | Yes |
● Basic conversion time (ms) | 6 / 20,1 / 23,5 ms | 10 / 16,7 / 20 / 100 | 8 / 23 / 25 ms |
● Integration time (ms) | 2,5 / 16,7 / 20 ms | 2,5 / 16,7 / 20 / 100 | 20 ms at 50 Hz (entire module incl. wire break) |
● Interference voltage suppression for interference frequency f1 in Hz | 400 / 60 / 50 Hz | 400 / 60 / 50 / 10 Hz | none/ 60 / 50 Hz |
Encoder | |||
Connection of signal encoders | |||
● for voltage measurement | Yes; possible | Yes; possible | |
● for current measurement as 2-wire transducer | Yes | ||
● for current measurement as 4-wire transducer | Yes | Yes | |
● for resistance measurement with two-wire connection | Yes; Line resistances are also measured | ||
● for resistance measurement with three-wire connection | Yes | Yes | |
● for resistance measurement with four-wire connection | Yes | Yes | Yes |
Errors/accuracies | |||
Operational error limit in overall temperature range | |||
● Voltage, relative to input range, (+/-) | 0.3 %; ±0.3 % at ±250 mV, ±500 mV, ±1 V, ±2.5 V, ±5 V, 1 to 5 V, ±10 V; ±0.31 % at ±80 mV; ±0.32 % at ±50 mV; ±0.35 % at ±25 mV | 0.3 % | |
● Current, relative to input range, (+/-) | 0.3 %; at 0 to 20 mA, ±5 mA, ±10 mA, ±20 mA, 4 to 20 mA | 0.5 % | |
● Resistance, relative to input range, (+/-) | 0.3 %; ±0.3% at 0 to 48 Ohm (4-conductor measurement), 0 to 150 Ohm (4-conductor measurement), 0 to 300 Ohm (4-conductor measurement), 0 to 600 Ohm (4-conductor measurement), 0 to 5000 Ohm (4-conductor measurement, in range of 6000 Ohm); ±0.4% at 0 to 300 Ohm (3-conductor measurement), 0 to 600 Ohm (3-conductor measurement), 0 to 5000 Ohm (3-conductor measurement, in range of 6000 Ohm); | ||
● Resistance thermometer, relative to input range, (+/-) | 0.4 % | ±1 °C | |
● Thermocouple, relative to input range, (+/-) | TC Type B (±11.5 K), TC Type R (±7.3 K), TC Type S (±8.3 K), TC Type T (±1.7 K), TC Type E (±3.2 K), TC Type J (±4.3 K), TC Type K (±6.2 K), TC Type U (±2.8 K), TC Type L (±4.2 K), TC Type N (±4.4 K) | ||
Basic error limit (operational limit at 25 °C) | |||
● Voltage, relative to input range, (+/-) | 0.15 %; ±0.15% at ±250 mV, ±500 mV, ±1 V, ±2.5 V, ±5 V, 1 V to 5 V, ±10 V; ±0.17% at ±80 mV; ±0.19% at ±50 mV; ±0.23% at ±25 mV | 0.1 % | |
● Current, relative to input range, (+/-) | 0.15 %; at 0 to 20 mA, ±5 mA, ±10 mA, ±20 mA, 4 to 20 mA | 0.17 % | |
● Resistance, relative to input range, (+/-) | 0.15 %; ±0.15 % at 0 to 48 ohms (4-conductor measurement), 0 to 150 ohms (4-conductor measurement), 0 to 300 ohms (4-conductor measurement), 0 to 5000 ohms (4-conductor measurement, in range of 6000 ohms); ±0.3 % at 0 to 300 ohms (3-conductor measurement), 0 to 600 ohms (3-conductor measurement), 0 to 5000 ohms (3-conductor measurement, in range of 6000 ohms) | ||
● Resistance thermometer, relative to input range, (+/-) | 0.3 % | ±0,2 °C | |
● Thermocouple, relative to input range, (+/-) | TC Type B (±7.6 K), TC Type R (±4.8 K) TC Type S (±5.4 K), TC Type T (±1.1 K), TC Type E (±1.8 K), TC Type J (±2.3 K), TC Type K (±3.4 K), TC Type U (±1.7 K), TC Type L (±2.3 K), TC Type N (±2.6 K) | ||
Interrupts/diagnostics/status information | |||
Diagnostics function | Yes; Parameterizable | Yes; Parameterizable | Yes; Parameterizable |
Alarms | |||
● Diagnostic alarm | Yes; Parameterizable | Yes; Parameterizable | Yes; Parameterizable |
● Limit value alarm | Yes; Parameterizable | Yes | Yes |
● Hardware interrupt | Yes; Parameterizable | Yes; Parameterizable | Yes; Parameterizable |
Diagnoses | |||
● Diagnostic information readable | Yes | Yes; possible | Yes; possible |
Diagnostics indication LED | |||
● internal fault INTF (red) | Yes | ||
● external fault EXTF (red) | Yes | ||
Potential separation | |||
Potential separation analog inputs | |||
● Potential separation analog inputs | Yes; internal/external | Yes; internal/external | Yes; internal/external |
● between the channels | No | Yes | No |
● between the channels and backplane bus | Yes | Yes | Yes |
● Between the channels and load voltage L+ | Yes | ||
Isolation | |||
Isolation tested with | 2 120 V DC between bus and L+/M; 2 120 V DC between bus and analog section; 500 V DC between bus and local ground; 500 V DC between analog section and L+/M; 2 120 V DC between analog section and local ground; 2 120 V DC between L+/M and local ground | 1 500 V DC | 500 V DC |
Dimensions | |||
Width | 25 mm | 25 mm | 25 mm |
Height | 290 mm | 290 mm | 290 mm |
Depth | 210 mm | 210 mm | 210 mm |
Weights | |||
Weight, approx. | 500 g | 650 g | 650 g |
Weight | N/A |
---|---|
Dimensions | N/A |
Related products
-
Select options This product has multiple variants. The options may be chosen on the product page Details
-
Select options This product has multiple variants. The options may be chosen on the product page Details
-
Select options This product has multiple variants. The options may be chosen on the product page Details
-
Select options This product has multiple variants. The options may be chosen on the product page Details
-
Select options This product has multiple variants. The options may be chosen on the product page Details