SIMATIC HMI TP1500 Comfort Outdoor, Comfort Panel, Touch operation, 15″ widescreen TFT display, 16 million colors, PROFINET interface, MPI/PROFIBUS DP interface, 12 MB configuration memory, Windows CE 6.0 (Microsoft Support included Security updates discontinued) configurable from WinCC Comfort V13 SP1, HSP
| Article number | 6AV2124-0QC13-0AX0 | |
| SIMATIC HMI TP1500 Comfort Outdoor | ||
| General information | ||
| Product type designation | TP1500 Comfort Outdoor | |
| Display | ||
| Design of display | TFT, bonded, daylight-readable | |
| Screen diagonal | 15.4 in | |
| Display width | 331.2 mm | |
| Display height | 207 mm | |
| Number of colors | 16 777 216 | |
| Resolution (pixels) | ||
| ● Horizontal image resolution | 1 280 pixel | |
| ● Vertical image resolution | 800 pixel | |
| Backlighting | ||
| ● MTBF backlighting (at 25 °C) | 50 000 h | |
| ● Backlight dimmable | Yes; LED, can be dimmed manually or automatically | |
| Control elements | ||
| Keyboard fonts | ||
| ● Function keys | ||
| — Number of function keys | 0 | |
| — Number of function keys with LEDs | 0 | |
| ● Keys with LED | No | |
| ● System keys | No | |
| ● Numeric keyboard | Yes; Onscreen keyboard | |
| ● alphanumeric keyboard | Yes; Onscreen keyboard | |
| Touch operation | ||
| ● Design as touch screen | Yes; Analog-resistive | |
| Expansions for operator control of the process | ||
| ● DP direct LEDs (LEDs as S7 output I/O) | ||
| — F1…Fx | 0 | |
| ● Direct keys (keys as S7 input I/O) | ||
| — F1…Fx | 0 | |
| ● Direct keys (touch buttons as S7 input I/O) | 40 | |
| Installation type/mounting | ||
| Mounting position | vertical | |
| Mounting in portrait format possible | Yes | |
| Mounting in landscape format possible | Yes | |
| maximum permissible angle of inclination without external ventilation | 35° | |
| Supply voltage | ||
| Type of supply voltage | DC | |
| Rated value (DC) | 24 V | |
| permissible range, lower limit (DC) | 19.2 V | |
| permissible range, upper limit (DC) | 28.8 V | |
| Input current | ||
| Current consumption (rated value) | 1.3 A | |
| Starting current inrush I²t | 0.5 A²·s | |
| Power | ||
| Active power input, typ. | 32 W | |
| Processor | ||
| Processor type | X86 | |
| Memory | ||
| Flash | Yes | |
| RAM | Yes | |
| Memory available for user data | 12 Mbyte | |
| Type of output | ||
| Info LED | No | |
| Power LED | No | |
| Error LED | No | |
| Acoustics | ||
| ● Buzzer | No | |
| ● Speaker | Yes | |
| Time of day | ||
| Clock | ||
| ● Hardware clock (real-time) | Yes | |
| ● Software clock | No | |
| ● retentive | Yes; Back-up duration typically 6 weeks | |
| ● synchronizable | Yes | |
| Interfaces | ||
| Number of industrial Ethernet interfaces | 2 | |
| Number of RS 485 interfaces | 1; RS 422 / 485 combined | |
| Number of RS 422 interfaces | 1 | |
| Number of RS 232 interfaces | 0 | |
| Number of USB interfaces | 2; USB 2.0 | |
| ● USB Mini B | 1; 5-pole | |
| Number of 20 mA interfaces (TTY) | 0 | |
| Number of parallel interfaces | 0 | |
| Number of other interfaces | 0 | |
| Number of SD card slots | 2 | |
| With software interfaces | No | |
| Industrial Ethernet | ||
| ● Industrial Ethernet status LED | 2 | |
| ● Number of ports of the integrated switch | 2 | |
| Protocols | ||
| PROFINET | Yes | |
| Supports protocol for PROFINET IO | Yes | |
| IRT | Yes; WinCC V13 SP1 HSP or higher | |
| PROFIBUS | Yes | |
| EtherNet/IP | Yes | |
| MPI | Yes | |
| Protocols (Ethernet) | ||
| ● TCP/IP | Yes | |
| ● DHCP | Yes | |
| ● SNMP | Yes | |
| ● DCP | Yes | |
| ● LLDP | Yes | |
| WEB characteristics | ||
| ● HTTP | Yes | |
| ● HTTPS | No | |
| ● HTML | Yes | |
| ● XML | No | |
| ● CSS | Yes | |
| ● Active X | No | |
| ● JavaScript | Yes | |
| ● Java VM | No | |
| Redundancy mode | ||
| Media redundancy | ||
| — MRP | Yes; WinCC V13 SP1 HSP or higher | |
| Further protocols | ||
| ● CAN | No | |
| ● MODBUS | Yes | |
| EMC | ||
| Emission of radio interference acc. to EN 55 011 | ||
| ● Limit class A, for use in industrial areas | Yes | |
| ● Limit class B, for use in residential areas | No | |
| Degree and class of protection | ||
| IP (at the front) | IP66 | |
| IP (rear) | IP20 | |
| NEMA (front) | ||
| ● Enclosure Type 4 at the front | Yes | |
| ● Enclosure Type 4x at the front | Yes | |
| Standards, approvals, certificates | ||
| CE mark | Yes | |
| cULus | Yes | |
| RCM (formerly C-TICK) | Yes | |
| KC approval | Yes | |
| Use in hazardous areas | ||
| ● ATEX Zone 2 | Yes; For inscription on device rating plate | |
| ● ATEX Zone 22 | Yes; For inscription on device rating plate | |
| ● IECEx Zone 2 | Yes; For inscription on device rating plate | |
| ● IECEx Zone 22 | Yes; For inscription on device rating plate | |
| ● cULus Class I Zone 1 | No | |
| ● cULus Class I Zone 2, Division 2 | Yes; For inscription on device rating plate | |
| ● FM Class I Division 2 | Yes; For inscription on device rating plate | |
| Marine approval | ||
| ● Germanischer Lloyd (GL) | Yes | |
| ● American Bureau of Shipping (ABS) | Yes | |
| ● Bureau Veritas (BV) | Yes; Available soon | |
| ● Det Norske Veritas (DNV) | Yes | |
| ● Korean Register of Shipping (KRS) | No; Available soon | |
| ● Lloyds Register of Shipping (LRS) | Yes | |
| ● Nippon Kaiji Kyokai (Class NK) | Yes; Available soon | |
| ● Polski Rejestr Statkow (PRS) | No | |
| ● Chinese Classification Society (CCS) | Yes; Available soon | |
| ● Compass working clearance | 5 m | |
| Ambient conditions | ||
| Suited for indoor use | Yes | |
| Suited for outdoor use | Yes; Powder-coated, UV resistant | |
| Ambient temperature during operation | ||
| Operation (vertical installation) | ||
| — For vertical installation, min. | -30 °C | |
| — For vertical installation, max. | 60 °C; (55 °C, see entry ID: 64847814) | |
| Operation (max. tilt angle) | ||
| — At maximum tilt angle, min. | -30 °C | |
| — At maximum tilt angle, max. | 50 °C | |
| Operation (vertical installation, portrait format) | ||
| — For vertical installation, min. | -30 °C | |
| — For vertical installation, max. | 50 °C | |
| Operation (max. tilt angle, portrait format) | ||
| — At maximum tilt angle, min. | -30 °C | |
| — At maximum tilt angle, max. | 45 °C | |
| Ambient temperature during storage/transportation | ||
| ● min. | -30 °C | |
| ● max. | 70 °C | |
| Altitude during operation relating to sea level | ||
| ● Installation altitude above sea level, max. | 3 000 m; Depending on the operating temperature | |
| Relative humidity | ||
| ● Operation, max. | 90 %; no condensation | |
| Operating systems | ||
| proprietary | No | |
| pre-installed operating system | ||
| ● Windows CE | Yes | |
| configuration / header | ||
| Message indicator | Yes | |
| Alarm system (incl. buffer and acknowledgment) | Yes | |
| Process value display (output) | Yes | |
| Process value default (input) possible | Yes | |
| Recipe management | Yes | |
| Configuration software | ||
| ● STEP 7 Basic (TIA Portal) | No | |
| ● STEP 7 Professional (TIA Portal) | No | |
| ● WinCC flexible Compact | No | |
| ● WinCC flexible Standard | No | |
| ● WinCC flexible Advanced | No | |
| ● WinCC Basic (TIA Portal) | No | |
| ● WinCC Comfort (TIA Portal) | Yes; WinCC V13 SP1 Update 7 + HSP or higher | |
| ● WinCC Advanced (TIA Portal) | Yes; WinCC V13 SP1 Update 7 + HSP or higher | |
| ● WinCC Professional (TIA Portal) | Yes; WinCC V13 SP1 Update 7 + HSP or higher | |
| Languages | ||
| Online languages | ||
| ● Number of online/runtime languages | 32 | |
| Project languages | ||
| ● Languages per project | 32 | |
| Functionality under WinCC (TIA Portal) | ||
| Libraries | Yes | |
| Applications/options | ||
| ● Web browser | Yes | |
| ● Pocket Word | Yes | |
| ● Pocket Excel | Yes | |
| ● PDF Viewer | Yes | |
| ● Media Player | Yes | |
| ● SIMATIC WinCC Sm@rtServer | Yes | |
| ● SIMATIC WinCC Audit | Yes | |
| Number of Visual Basic Scripts | Yes | |
| Task planner | ||
| ● time-controlled | Yes | |
| ● task-controlled | Yes | |
| Message system | ||
| ● Number of alarm classes | 32 | |
| ● Bit messages | ||
| — Number of bit messages | 4 000 | |
| ● Analog messages | ||
| — Number of analog messages | 200 | |
| ● S7 alarm number procedure | Yes | |
| ● System messages HMI | Yes | |
| ● System event, more (SIMATIC S7, SINUMERIK, SIMOTION, … ) | Yes | |
| ● Number of characters per message | 80 | |
| ● Number of process values per message | 8 | |
| ● Acknowledgment groups | Yes | |
| ● Message indicator | Yes | |
| Recipe management | ||
| ● Number of recipes | 300 | |
| ● Data records per recipe | 500 | |
| ● Entries per data record | 1 000 | |
| ● Size of internal recipe memory | 2 Mbyte | |
| ● Recipe memory expandable | Yes | |
| Variables | ||
| ● Number of variables per device | 2 048 | |
| ● Number of variables per screen | 400 | |
| ● Limit values | Yes | |
| ● Multiplexing | Yes | |
| ● Structures | Yes | |
| ● Arrays | Yes | |
| Images | ||
| ● Number of configurable images | 500 | |
| ● Permanent window/default | Yes | |
| ● Global image | Yes | |
| ● Image selection by PLC | Yes | |
| ● Image number in the PLC | Yes | |
| Image objects | ||
| ● Number of objects per image | 400 | |
| ● Text fields | Yes | |
| ● I/O fields | Yes | |
| ● Graphic I/O fields (graphics list) | Yes | |
| ● Symbolic I/O fields (text list) | Yes | |
| ● Date/time fields | Yes | |
| ● Switches | Yes | |
| ● Buttons | Yes | |
| ● Graphic display | Yes | |
| ● Icons | Yes | |
| ● Geometric objects | Yes | |
| Complex image objects | ||
| ● Number of complex objects per screen | 20 | |
| ● Alarm view | Yes | |
| ● Trend view | Yes | |
| ● User view | Yes | |
| ● Status/control | Yes | |
| ● Sm@rtClient view | Yes | |
| ● Recipe view | Yes | |
| ● f(x) trend view | Yes | |
| ● System diagnostics view | Yes | |
| ● Media Player | Yes | |
| ● HTML browser | ||
| ● PDF display | ||
| ● IP camera display | Yes; Webcam type see FAQs | |
| ● Bar graphs | Yes | |
| ● Sliders | Yes | |
| ● Pointer instruments | Yes | |
| ● Analog/digital clock | Yes | |
| Lists | ||
| ● Number of text lists per project | 500 | |
| ● Number of entries per text list | 500 | |
| ● Number of graphics lists per project | 500 | |
| ● Number of entries per graphics list | 500 | |
| Archiving | ||
| ● Number of archives per device | 50 | |
| ● Number of entries per archive | 20 000 | |
| ● Message archive | Yes | |
| ● Process value archive | Yes | |
| ● Archiving methods | ||
| — Sequential archive | Yes | |
| — Short-term archive | Yes | |
| ● Memory location | ||
| — Memory card | Yes | |
| — USB memory | Yes | |
| — Ethernet | Yes | |
| ● Data storage format | ||
| — CSV | Yes | |
| — TXT | Yes | |
| — RDB | Yes | |
| Security | ||
| ● Number of user groups | 50 | |
| ● Number of user rights | 32 | |
| ● Number of users | 50 | |
| ● Password export/import | Yes | |
| ● SIMATIC Logon | Yes | |
| Logging through printer | ||
| ● Alarms | Yes | |
| ● Report (shift log) | Yes | |
| ● Hardcopy | Yes | |
| ● Electronic print to file | Yes; PDF, HTML | |
| Character sets | ||
| ● Keyboard fonts | ||
| — US English | Yes | |
| Transfer (upload/download) | ||
| ● MPI/PROFIBUS DP | Yes | |
| ● USB | Yes | |
| ● Ethernet | Yes | |
| ● using external storage medium | Yes; Backup/restore | |
| Process coupling | ||
| ● S7-1200 | Yes | |
| ● S7-1500 | Yes | |
| ● S7-200 | Yes | |
| ● S7-300/400 | Yes | |
| ● LOGO! | Yes | |
| ● WinAC | Yes | |
| ● SINUMERIK | Yes; with SINUMERIK option package | |
| ● SIMOTION | Yes | |
| ● Allen Bradley (EtherNet/IP) | Yes | |
| ● Allen Bradley (DF1) | Yes | |
| ● Mitsubishi (MC TCP/IP) | Yes | |
| ● Mitsubishi (FX) | Yes | |
| ● OMRON (FINS TCP) | No | |
| ● OMRON (LINK/Multilink) | Yes | |
| ● Modicon (Modbus TCP/IP) | Yes | |
| ● Modicon (Modbus) | Yes | |
| ● OPC UA Client | Yes | |
| ● OPC UA Server | Yes | |
| Service tools/configuration aids | ||
| ● Backup/Restore manually | Yes | |
| ● Backup/Restore automatically | Yes | |
| ● Simulation | Yes | |
| ● Device switchover | Yes | |
| Peripherals/Options | ||
| Printer | Yes | |
| SIMATIC HMI MM memory card: Multi Media Card | Yes | |
| SIMATIC HMI SD memory card: Secure Digital memory card | Yes | |
| SIMATIC HMI CF memory card Compact Flash Card | No | |
| USB memory | Yes; e.g. USB RFID reader, see FAQ entry ID: 99808171 | |
| SIMATIC IPC USB Flashdrive (USB stick) | Yes | |
| SIMATIC HMI USB stick | Yes | |
| Network camera | Yes; See FAQ Entry ID: 62383298 and entry ID: 65647473 | |
| Accessories | ||
| Expansion module | Optional e.g. USB RFID reader, see FAQ entry ID: 99808171 | |
| Further accessories are available | Yes; Mounting clips and 2-pin power supply connector | |
| Mechanics/material | ||
| Enclosure material (front) | ||
| ● Plastic | No | |
| ● Aluminum | Yes; Powder-coated, UV resistant | |
| ● Stainless steel | No | |
| Dimensions | ||
| Width of the housing front | 415 mm | |
| Height of housing front | 310 mm | |
| Mounting cutout, width | 396 mm | |
| Mounting cutout, height | 291 mm | |
| Overall depth | 77 mm | |
| Weights | ||
| Weight (without packaging) | 4 kg | |
| Weight (with packaging) | 6.2 kg | |
| Other | ||
| Note: | Power, quantity structure and performance correspond to a standard 12″ Comfort Panel | |