Siemens Analog Input Modules ET 200SP Product Specifications:

Article number 6ES7134-6GF00-0AA1 6ES7134-6FB00-0BA1 6ES7134-6FF00-0AA1 6ES7134-6HD01-0BA1 6ES7134-6GB00-0BA1
ET 200SP, AI 8XI 2-/4-Wire Basic ET 200SP, AI 2xU Standard, PU 1 ET 200SP, AI 8xU Basic ET 200SP, AI 4xU/I 2-Wire ST, PU 1 ET 200SP, AI 2xI 2-/4-Wire ST, PU 1
General information
Product type designation AI 8xI 2-/4-wire BA AI 2xU ST AI 8xU BA AI 4x U/I 2-wire AI 2xI 2-/4-wire ST
HW functional status from FS04 from FS04 from FS04 From FS02 from FS04
Firmware version
● FW update possible Yes Yes Yes Yes Yes
usable BaseUnits BU type A0, A1 BU type A0, A1 BU type A0, A1 BU type A0, A1 BU type A0, A1
Color code for module-specific color identification plate CC01 CC00 CC02 CC03 CC05
Product function
● I&M data Yes; I&M0 to I&M3 Yes; I&M0 to I&M3 Yes; I&M0 to I&M3 Yes; I&M0 to I&M3 Yes; I&M0 to I&M3
● Isochronous mode No No No No No
● Measuring range scalable No No No No No
Engineering with
● STEP 7 TIA Portal configurable/integrated from version V13 SP1 V13 SP1 V13 SP1 V14 / – V13 SP1
● STEP 7 configurable/integrated from version V5.5 SP3 / – V5.5 SP3 / – V5.5 SP3 / – V5.6 and higher V5.5 SP3
● PCS 7 configurable/integrated from version V8.1 SP1
● PROFIBUS from GSD version/GSD revision One GSD file each, Revision 3 and 5 and higher One GSD file each, Revision 3 and 5 and higher One GSD file each, Revision 3 and 5 and higher One GSD file each, Revision 3 and 5 and higher One GSD file each, Revision 3 and 5 and higher
● PROFINET from GSD version/GSD revision GSDML V2.3 GSDML V2.3 GSDML V2.3 GSDML V2.3 V2.3 / –
Operating mode
● Oversampling No No No No No
● MSI No No No No No
CiR – Configuration in RUN
Reparameterization possible in RUN Yes Yes Yes Yes Yes
Calibration possible in RUN No No No No No
Supply voltage
Rated value (DC) 24 V 24 V 24 V 24 V 24 V
permissible range, lower limit (DC) 19.2 V 19.2 V 19.2 V 19.2 V 19.2 V
permissible range, upper limit (DC) 28.8 V 28.8 V 28.8 V 28.8 V 28.8 V
Reverse polarity protection Yes Yes Yes Yes Yes
Input current
Current consumption, max. 25 mA; without sensor supply 37 mA 25 mA 37 mA; without sensor supply 45 mA; without sensor supply
Encoder supply
24 V encoder supply
● 24 V Yes No Yes Yes
● Short-circuit protection Yes Yes Yes
● Output current, max. 0.7 A; total current of all encoders/channels 20 mA; max. 50 mA per channel for a duration < 10 s 50 mA; Total current for both channels (two-wire)
Additional 24 V encoder supply
● 24 V No Yes
● Short-circuit protection Yes; Module-wise
● Output current, max. 200 mA; Total current for both channels (four-wire)
Power loss
Power loss, typ. 0.7 W; Without encoder supply voltage 0.9 W 0.7 W 0.85 W; Without encoder supply voltage 1.1 W
Address area
Address space per module
● Address space per module, max. 16 byte 4 byte; + 1 byte for QI information 16 byte 8 byte; + 1 byte for QI information 4 byte; + 1 byte for QI information
Hardware configuration
Automatic encoding Yes Yes Yes Yes Yes
● Mechanical coding element Yes Yes Yes Yes Yes
● Type of mechanical coding element Type A Type A type B Type A Type A
Selection of BaseUnit for connection variants
● 1-wire connection BU type A0, A1 BU type A0, A1 BU type A0, A1 BU type A0, A1
● 2-wire connection BU type A0, A1 BU type A0, A1 BU type A0, A1 BU type A0, A1 BU type A0, A1
● 4-wire connection BU type A0, A1 + potential distributor module BU type A0, A1
Analog inputs
Number of analog inputs 8; Single-ended 2 8; Single-ended 4; Differential inputs 2
● For current measurement 8 2
● For voltage measurement 2 8
permissible input voltage for voltage input (destruction limit), max. 30 V 30 V 30 V
permissible input current for current input (destruction limit), max. 50 mA 50 mA 50 mA
Cycle time (all channels), min. 1 ms; per channel 500 µs 1 ms; per channel Sum of the basic conversion times and additional processing times (depending on the parameterization of the active channels) 500 µs
Input ranges (rated values), voltages
● 0 to +10 V Yes; 15 bit Yes; 15 bit Yes; 15 bit
— Input resistance (0 to 10 V) 180 kΩ 100 kΩ 120 kΩ
● 1 V to 5 V Yes; 15 bit Yes; 15 bit
— Input resistance (1 V to 5 V) 180 kΩ 120 kΩ
● -10 V to +10 V Yes; 16 bit incl. sign Yes; 16 bit incl. sign Yes; 16 bit incl. sign
— Input resistance (-10 V to +10 V) 180 kΩ 100 kΩ 120 kΩ
● -5 V to +5 V Yes; 16 bit incl. sign Yes; 16 bit incl. sign
— Input resistance (-5 V to +5 V) 180 kΩ 120 kΩ
Input ranges (rated values), currents
● 0 to 20 mA Yes Yes; 15 bit Yes; 15 bit
— Input resistance (0 to 20 mA) 100 Ω; 15 bit 100 Ω; + approx. 0.7 V diode forward voltage 130 Ω; 90 ohms with two wires
● -20 mA to +20 mA Yes Yes; 16 bit incl. sign
— Input resistance (-20 mA to +20 mA) 100 Ω; 16 bit incl. sign 130 Ω
● 4 mA to 20 mA Yes Yes; 15 bit Yes; 15 bit
— Input resistance (4 mA to 20 mA) 100 Ω; 15 bit 100 Ω; + approx. 0.7 V diode forward voltage 130 Ω; 90 ohms with two wires
Cable length
● shielded, max. 200 m 200 m 200 m 1 000 m; 200 m for voltage measurement 1 000 m
Analog value generation for the inputs
Measurement principle Sigma Delta integrating (Sigma-Delta) Sigma Delta
Integration and conversion time/resolution per channel
● Resolution with overrange (bit including sign), max. 16 bit 16 bit 16 bit 16 bit 16 bit
● Integration time, parameterizable Yes Yes Yes Yes Yes
● Interference voltage suppression for interference frequency f1 in Hz 16.67 / 50 / 60 / 4 800 (16.67 / 50 / 60) 16.6 / 50 / 60 Hz / off 16.67 / 50 / 60 / 4 800 (16.67 / 50 / 60) 16.6 / 50 / 60 Hz 16.6 / 50 / 60 Hz / off
● Conversion time (per channel) 180 / 60 / 50 / 0.625 (67.5 / 22.5 / 18.75) ms 50 ms @ 60 Hz, 60 ms @ 50 Hz, 180 ms @ 16.6 Hz, 250 µs without filter 180 / 60 / 50 / 0.625 (67.5 / 22.5 / 18.75) ms 180 / 60 / 50 ms 50 ms @ 60 Hz, 60 ms @ 50 Hz, 180 ms @ 16.6 Hz, 500 µs without filter
Smoothing of measured values
● Number of smoothing levels 4; None; 4/8/16 times 4 4; None; 4/8/16 times 4; None; 4/8/16 times 4
● parameterizable Yes Yes Yes Yes Yes
● Step: None Yes; 1x cycle time Yes; 1x conversion time
● Step: low Yes; 4x cycle time Yes; 4x conversion time
● Step: Medium Yes; 8x cycle time Yes; 8x conversion time
● Step: High Yes; 16x cycle time Yes; 16x conversion time
Encoder
Connection of signal encoders
● for voltage measurement No Yes Yes Yes
● for current measurement as 2-wire transducer Yes Yes Yes
— Burden of 2-wire transmitter, max. 650 Ω 650 Ω 650 Ω
● for current measurement as 4-wire transducer Yes No No Yes
Errors/accuracies
Linearity error (relative to input range), (+/-) 0.01 % 0.01 % 0.01 % 0.01 % 0.01 %
Temperature error (relative to input range), (+/-) 0.005 %/K 0.005 %/K 0.005 %/K 0.005 %/K 0.005 %/K
Crosstalk between the inputs, min. 50 dB -50 dB -50 dB 50 dB -50 dB
Repeat accuracy in steady state at 25 °C (relative to input range), (+/-) 0.05 % 0.05 % 0.05 % 0.05 % 0.05 %
Operational error limit in overall temperature range
● Voltage, relative to input range, (+/-) 0.5 % 0.5 % 0.5 %
● Current, relative to input range, (+/-) 0.5 % 0.5 % 0.5 %
Basic error limit (operational limit at 25 °C)
● Voltage, relative to input range, (+/-) 0.3 % 0.3 % 0.3 %
● Current, relative to input range, (+/-) 0.3 % 0.3 % 0.3 %
Interference voltage suppression for f = n x (f1 +/- 1 %), f1 = interference frequency
● Series mode interference (peak value of interference < rated value of input range), min. 70 dB; With conversion time 67.5 / 22.5 / 18.75 ms: 40 dB 70 dB 70 dB; With conversion time 67.5 / 22.5 / 18.75 ms: 40 dB 70 dB 70 dB
● Common mode voltage, max. 10 V 10 V 10 V
● Common mode interference, min. 90 dB 90 dB 90 dB
Interrupts/diagnostics/status information
Diagnostics function Yes Yes Yes Yes Yes
Alarms
● Diagnostic alarm Yes Yes Yes Yes Yes
● Limit value alarm No No No No No
Diagnoses
● Monitoring the supply voltage Yes Yes Yes Yes Yes
● Wire-break Yes; at 4 to 20 mA No No Yes; at 4 to 20 mA Yes; at 4 to 20 mA
● Short-circuit Yes; Sensor supply to M; module by module Yes; at 1 to 5 V No Yes; with 1 to 5 V or 2-wire mode: Short-circuit of the encoder supply to ground or of an input to the encoder supply Yes; Short-circuit of the encoder supply
● Group error Yes Yes Yes Yes Yes
● Overflow/underflow Yes Yes Yes Yes Yes
Diagnostics indication LED
● Monitoring of the supply voltage (PWR-LED) Yes; green LED Yes; green PWR LED Yes; green PWR LED Yes; green LED Yes; green PWR LED
● Channel status display Yes; green LED Yes; green LED Yes; green LED Yes; green LED Yes; green LED
● for channel diagnostics No No No No No
● for module diagnostics Yes; green/red DIAG LED Yes; green/red DIAG LED Yes; green/red DIAG LED Yes; green/red LED Yes; green/red DIAG LED
Potential separation
Potential separation channels
● between the channels No No No Yes; channel group-specific between 2-wire current input group and voltage input group No
● between the channels and backplane bus Yes Yes Yes Yes Yes
● between the channels and the power supply of the electronics No Yes No Yes; only for voltage inputs Yes
Permissible potential difference
between the inputs (UCM) 10 Vpp 10 V DC 10 Vpp
Isolation
Isolation tested with 707 V DC (type test) 707 V DC (type test) 707 V DC (type test) 707 V DC (type test) 707 V DC (type test)
Standards, approvals, certificates
Suitable for applications according to AMS 2750 Yes; Declaration of Conformity, see online support entry 109757262
Suitable for applications according to CQI-9 Yes
Ambient conditions
Ambient temperature during operation
● horizontal installation, min. -30 °C; < 0 °C as of FS04 -30 °C; < 0 °C as of FS04 -30 °C; < 0 °C as of FS04 -30 °C; < 0 °C as of FS02 -30 °C; < 0 °C as of FS04
● horizontal installation, max. 60 °C 60 °C 60 °C 60 °C 60 °C
● vertical installation, min. -30 °C; < 0 °C as of FS04 -30 °C; < 0 °C as of FS04 -30 °C; < 0 °C as of FS04 -30 °C; < 0 °C as of FS02 -30 °C; < 0 °C as of FS04
● vertical installation, max. 50 °C 50 °C 50 °C 50 °C 50 °C
Altitude during operation relating to sea level
● Installation altitude above sea level, max. 5 000 m; Restrictions for installation altitudes > 2 000 m, see manual 5 000 m; Restrictions for installation altitudes > 2 000 m, see manual 5 000 m; Restrictions for installation altitudes > 2 000 m, see manual 5 000 m; Restrictions for installation altitudes > 2 000 m, see manual 5 000 m; Restrictions for installation altitudes > 2 000 m, see manual
Dimensions
Width 15 mm 15 mm 15 mm 15 mm 15 mm
Height 73 mm 73 mm 73 mm 73 mm 73 mm
Depth 58 mm 58 mm 58 mm 58 mm 58 mm
Weights
Weight, approx. 31 g 31 g 31 g 31 g 32 g
Weight N/A
Dimensions N/A