Inosaki is one of the largest Phoenix Contact Distributors to provide terminal block, interface module, power supply and relay. And our best offer for terminal block types are Feed-through, Fuse Modular, Spring Cage, Double Level, and Multi-level, hence the series model references to PT Series, ST Series, TB Series, UT Series, UK Series. In additional for power supply are QUINT Power, STEP Power, Trio Power, and UNO Power. Please email us for catalog: sales@inosaki.my
Product Description
QUINT POWER power supply units – Superior system availability with SFB technology
Compact power supply units of the new QUINT POWER generation maximize the availability of your system. With the SFB technology (Selective Fuse Breaking Technology), six times the nominal current for 12 ms, even the standard power circuit-breakers can now also be triggered reliably and quickly. Faulty current paths are switched off selectively, the fault is located and important system parts continue to operate. Comprehensive diagnostics are provided through constant monitoring of output voltage and current. This preventive function monitoring visualizes critical operating modes and reports them to the control unit before an error can occur.
Dimensions
Article Number |
2320830 |
Width |
120 mm |
Height |
130 mm |
Depth |
125 mm |
Installation distance right/left |
5 mm / 5 mm |
Installation distance top/bottom |
50 mm / 50 mm |
Ambient conditions
Degree of protection |
IP20 |
Ambient temperature (operation) |
-25 °C … 70 °C (> 60 °C Derating: 2,5 %/K) |
Ambient temperature (storage/transport) |
-40 °C … 85 °C |
Max. permissible relative humidity (operation) |
≤ 95 % (at 25 °C, non-condensing) |
Climatic class |
3K3 (in acc. with EN 60721) |
Degree of pollution |
2 |
Installation height |
≤ 2000 m |
Input data
Nominal input voltage range |
2x 400 V AC … 500 V AC |
|
600 V DC |
Input voltage range |
2x 360 V AC … 575 V AC |
|
450 V DC … 840 V DC |
AC frequency range |
45 Hz … 65 Hz |
Frequency range DC |
0 Hz |
Current consumption |
2.5 A (400 V AC) |
|
2.1 A (500 V AC) |
Nominal power consumption |
888 VA |
Inrush current |
< 45 A (typical) |
Mains buffering time |
typ. 20 ms (400 V AC) |
Input fuse |
3.15 A (slow-blow, internal) |
Recommended breaker for input protection |
10 A … 16 A (Characteristic B, C) |
Type of protection |
Transient surge protection |
Protective circuit/component |
Varistor |
Output data
Nominal output voltage |
24 V DC ±1 % |
Setting range of the output voltage (USet) |
18 V DC … 29.5 V DC (UIN ≥ 360 V AC / 480 V DC) |
|
18 V DC … 26 V DC (< 480 V DC) |
Nominal output current (IN) |
20 A (-25 °C … 60 °C) |
POWER BOOST (IBoost) |
26 A (-25 °C … 40 °C permanent, UOUT = 24 V DC ) |
Selective Fuse Breaking (ISFB) |
120 A (20 ms) |
Derating |
60 °C … 70 °C (2.5%/K) |
Connection in parallel |
yes, for redundancy and increased capacity |
Connection in series |
yes |
Feedback voltage resistance |
< 35 V DC |
Protection against overvoltage at the output (OVP) |
< 35 V DC |
Max. capacitive load |
unlimited |
Active current limitation |
Approx. 27 A |
Control deviation |
< 1 % (change in load, static 10 % … 90 %) |
|
< 2 % (change in load, dynamic 10 % … 90 %) |
|
< 0.1 % (change in input voltage ±10 %) |
Residual ripple |
< 50 mVPP (with nominal values) |
Output power |
480 W |
Peak switching voltages nominal load |
< 50 mVPP (20 MHz) |
Maximum power dissipation in no-load condition |
11 W |
Power loss nominal load max. |
51 W |
General
Net weight |
2 kg |
Efficiency |
> 92 % (600 V DC) |
|
> 90.5 % (400 V AC) |
MTBF (IEC 61709, SN 29500) |
|
|
> 860000 h (40 °C) |
|
|
Insulation voltage input/output |
1.5 kV AC (type test) |
|
2 kV AC (routine test) |
Insulation voltage input / PE |
4 kV AC (type test) |
|
1.5 kV AC (routine test) |
Insulation voltage output / PE |
500 V DC (routine test) |
Degree of protection |
IP20 |
Protection class |
I |
Housing material |
Steel sheet, zinc-plated |
Mounting position |
horizontal DIN rail NS 35, EN 60715 |
Assembly instructions |
alignable: PN ≥50%, 5 mm horizontally, 15 mm next to active components, 50 mm vertically
alignable: PN <50%, 0 mm horizontally, 40 mm vertically top, 20 mm vertically bottom |
Connection data, input
Connection method |
Screw connection |
Conductor cross section solid min. |
0.2 mm² |
Conductor cross section solid max. |
6 mm² |
Conductor cross section flexible min. |
0.2 mm² |
Conductor cross section flexible max. |
4 mm² |
Conductor cross section AWG min. |
24 |
Conductor cross section AWG max. |
10 |
Stripping length |
8 mm |
Screw thread |
M3 |
Connection data, output
Connection method |
Screw connection |
Conductor cross section solid min. |
0.2 mm² |
Conductor cross section solid max. |
6 mm² |
Conductor cross section flexible min. |
0.2 mm² |
Conductor cross section flexible max. |
4 mm² |
Conductor cross section AWG min. |
12 |
Conductor cross section AWG max. |
10 |
Stripping length |
8 mm |
Screw thread |
M3 |
Connection data for signaling
Conductor cross section solid min. |
0.2 mm² |
Conductor cross section solid max. |
6 mm² |
Conductor cross section flexible min. |
0.2 mm² |
Conductor cross section flexible max. |
4 mm² |
Conductor cross section AWG min. |
24 |
Conductor cross section AWG max. |
10 |
Screw thread |
M3 |
Standards
Standard – Safety of transformers |
EN 61558-2-17 |
Standard – Electrical safety |
EN 60950-1/VDE 0805 (SELV) |
Standard – Electronic equipment for use in electrical power installations and their assembly into electrical power installations |
EN 50178/VDE 0160 (PELV) |
Standard – Safe isolation |
DIN VDE 0100-410 |
Rail applications |
EN 50121-4 |
Conformance/approvals
UL approvals |
UL/C-UL listed UL 508 |
|
UL/C-UL Recognized UL 60950-1 |
EMC data
Electromagnetic compatibility |
Conformance with EMC Directive 2014/30/EU |
Environmental Product Compliance
REACh SVHC |
Lead 7439-92-1 |