QUINT-PS/1AC/24DC/10/CO – 2320911 – Phoenix Contact Power Supply, with Protective Coating

$ 469.48

SKU: Phoenix Contact 2320911

Inosaki is one of the largest Phoenix Contact Distributors to provide terminal block, interface module, power supply and relay. And our best offer for terminal block types are Feed-through, Fuse Modular, Spring Cage, Double Level, and Multi-level, hence the series model references to  PT Series, ST Series, TB Series, UT Series, UK Series. In additional for power supply are QUINT Power, STEP Power, Trio Power, and UNO Power. Please email us for catalog: sales@inosaki.my

Product Description

QUINT POWER power supplies with maximum functionality
QUINT POWER circuit breakers magnetically and therefore quickly trip at six times the nominal current, for selective and therefore cost-effective system protection. In addition, the high system availability is ensured by preventive function monitoring which reports critical operating states before errors can occur.
Reliable starting of heavy loads takes place via the static power reserve POWER BOOST. Thanks to the adjustable voltage, all ranges between 18 V DC … 29.5 V DC are covered.

Dimensions

Article Number 2320911
Width 60 mm
Height 130 mm
Depth 125 mm
Width with alternative assembly 122 mm
Height with alternative assembly 130 mm
Depth with alternative assembly 63 mm
Installation distance right/left 5 mm / 5 mm
Installation distance top/bottom 50 mm / 50 mm

Ambient conditions

Degree of protection IP20
Ambient temperature (operation) -40 °C … 70 °C (> 60 °C Derating: 2,5 %/K)
Ambient temperature (storage/transport) -40 °C … 85 °C
Max. permissible relative humidity (operation) 100 % (at 25 °C, non-condensing)
Climatic class 3K3 (in acc. with EN 60721)
Degree of pollution 2
Installation height ≤ 5000 m

Input data

Nominal input voltage range 100 V AC … 240 V AC
110 V DC … 250 V DC
Input voltage range 85 V AC … 264 V AC
90 V DC … 410 V DC +5 % (UL 508: ≤ 250 V DC)
Dielectric strength maximum 300 V AC
AC frequency range 50 Hz … 60 Hz
Discharge current to PE < 3.5 mA
Current consumption 4 A (100 V AC)
1.7 A (240 V AC)
2.2 A (120 V AC)
1.3 A (230 V AC)
2.5 A (110 V DC)
1.2 A (220 V DC)
3.4 A (110 V DC)
1.5 A (250 V DC)
Nominal power consumption 303 VA
Inrush current < 15 A
Mains buffering time typ. 36 ms (120 V AC)
typ. 36 ms (230 V AC)
Input fuse 10 A (slow-blow, internal)
Recommended breaker for input protection 10 A … 20 A (AC: Characteristics B, C, D, K)
Type of protection Transient surge protection
Protective circuit/component Varistor, gas-filled surge arrester

Output data

Nominal output voltage 24 V DC ±1 %
Setting range of the output voltage (USet) 18 V DC … 29.5 V DC (> 24 V DC, constant capacity)
Nominal output current (IN) 10 A (-25 °C … 60 °C, UOUT = 24 V DC)
POWER BOOST (IBoost) 15 A (-25 °C … 40 °C permanent, UOUT = 24 V DC )
Selective Fuse Breaking (ISFB) 60 A (12 ms)
Derating 60 °C … 70 °C (2.5%/K)
Connection in parallel yes, for redundancy and increased capacity
Connection in series yes
Feedback voltage resistance ≤ 35 V DC
Protection against overvoltage at the output (OVP) ≤ 32 V DC
Control deviation < 1 % (change in load, static 10 % … 90 %)
< 2 % (change in load, dynamic 10 % … 90 %)
< 0.1 % (change in input voltage ±10 %)
Residual ripple < 50 mVPP (with nominal values)
Output power 240 W
Typical response time < 0.15 s
Maximum power dissipation in no-load condition 9.1 W
Power loss nominal load max. 22 W

General

Net weight 1.1 kg
Efficiency typ. 92.5 % (230 V AC)
MTBF (IEC 61709, SN 29500) > 940000 h (25 °C)
> 530000 h (40 °C)
> 230000 h (60 °C)
Insulation voltage input/output 4 kV AC (type test)
2 kV AC (routine test)
Insulation voltage input / PE 3.5 kV AC (type test)
2 kV AC (routine test)
Insulation voltage output / PE 500 V DC (routine test)
Degree of protection IP20
Protection class I
Mounting position horizontal DIN rail NS 35, EN 60715
Assembly instructions alignable: PN ≥50%, 5 mm horizontally, 15 mm next to active components, 50 mm vertically
alignable: PN <50%, 0 mm horizontally, 40 mm vertically top, 20 mm vertically bottom

Connection data, input

Connection method Screw connection
Conductor cross section solid min. 0.2 mm²
Conductor cross section solid max. 2.5 mm²
Conductor cross section flexible min. 0.2 mm²
Conductor cross section flexible max. 2.5 mm²
Conductor cross section AWG min. 16
Conductor cross section AWG max. 12
Stripping length 7 mm
Screw thread M3

Connection data, output

Connection method Screw connection
Conductor cross section solid min. 0.2 mm²
Conductor cross section solid max. 2.5 mm²
Conductor cross section flexible min. 0.2 mm²
Conductor cross section flexible max. 2.5 mm²
Conductor cross section AWG min. 16
Conductor cross section AWG max. 12
Stripping length 7 mm
Screw thread M3

Connection data for signaling

Conductor cross section solid min. 0.2 mm²
Conductor cross section solid max. 2.5 mm²
Conductor cross section flexible min. 0.2 mm²
Conductor cross section flexible max. 2.5 mm²
Conductor cross section AWG min. 16
Conductor cross section AWG max. 12
Screw thread M3

Standards

EMC requirements for noise immunity EN 61000-6-1
EN 61000-6-2
EMC requirements for noise emission EN 61000-6-3
EN 61000-6-4
HART FSK Physical Layer Test Specification Compliance Output voltage UOut compliant
Standard – Electrical safety IEC 61010-2-201 (SELV)
Standard – safety for equipment for measurement, control, and laboratory use IEC 61010-1
Standard – Safety extra-low voltage IEC 61010-1 (SELV)
IEC 61010-2-201 (PELV)
Standard – Safe isolation IEC 61010-2-201
Standard – Limitation of mains harmonic currents EN 61000-3-2
Standard – Equipment safety BG (design tested)
Explosive atmosphere EN 60079-15 (Zone 2)
Mains variation/undervoltage SEMI F47-0706 Compliance Certificate
Rail applications EN 50121-4
EN 50121-3-2
Overvoltage category EN 61010-1 II (≤ 5000 m)
Overvoltage category EN 62477-1 III (≤ 2000 m)

Conformance/approvals

UL approvals UL/C-UL listed UL 508
UL/C-UL Recognized UL 60950-1
UL ANSI/ISA-12.12.01 Class I, Division 2, Groups A, B, C, D (Hazardous Location)
CSA CAN/CSA-C22.2 No. 60950-1-07
CSA-C22.2 No. 107.1-01
SIQ BG (type approved)
Shipbuilding approval DNV GL (EMC B), ABS, LR, RINA, NK, BV
DeviceNet approval DeviceNet™ Power Supply Conformance Tested

EMC data

Electromagnetic compatibility Conformance with EMC Directive 2014/30/EU
Low Voltage Directive Conformance with Low Voltage Directive 2014/35/EC
Electrostatic discharge EN 61000-4-2
Contact discharge 8 kV (Test Level 4)
Discharge in air 15 kV (Test Level 4)
Electromagnetic HF field EN 61000-4-3
Frequency range 80 MHz … 1 GHz
Test field strength 20 V/m (Test Level 3)
Frequency range 1 GHz … 2 GHz
Test field strength 10 V/m (Test Level 3)
Frequency range 2 GHz … 3 GHz
Test field strength 10 V/m (Test Level 3)
Comments Criterion A
Fast transients (burst) EN 61000-4-4
Input 4 kV (Test Level 4 – asymmetrical)
Output 2 kV (Test Level 3 – asymmetrical)
Signal 2 kV (Test Level 4 – asymmetrical)
Comments Criterion A
Surge voltage load (surge) EN 61000-4-5
Input 2 kV (Test Level 3 – symmetrical)
4 kV (Test Level 4 – asymmetrical)
Output 1 kV (Test Level 2 – symmetrical)
2 kV (Test Level 3 – asymmetrical)
Signal 1 kV (Test Level 2 – asymmetrical)
Comments Criterion A
Conducted interference EN 61000-4-6
I/O/S asymmetrical
Frequency range 0.15 MHz … 80 MHz
Voltage 10 V (Test Level 3)
Comments Criterion A
Criterion A Normal operating behavior within the specified limits.
Criterion B Temporary impairment to operational behavior that is corrected by the device itself.

Environmental Product Compliance

REACh SVHC Lead 7439-92-1
China RoHS Environmentally Friendly Use Period = 25;
For details about hazardous substances go to tab “Downloads”, Category “Manufacturer’s declara