Inosaki is one of the largest Phoenix Contact Distributors to provide terminal block, interface module, power supply and relay. And our best offer for terminal block types are Feed-through, Fuse Modular, Spring Cage, Double Level, and Multi-level, hence the series model references to PT Series, ST Series, TB Series, UT Series, UK Series. In additional for power supply are QUINT Power, STEP Power, Trio Power, and UNO Power. Please email us for catalog: sales@inosaki.my
Feed-through terminal block, nom. voltage: 690 V, nominal current: 24 A, connection method: Screw connection, number of connections: 2, cross section: 0.2 mm² – 4 mm², AWG: 24 – 12, width: 6.2 mm, color: gray, mounting type: NS 35/7,5, NS 35/15
General
Article Number |
3001035 |
Number of levels |
1 |
Number of connections |
2 |
Potentials |
1 |
Nominal cross section |
2.5 mm² |
Color |
gray |
Insulating material |
PA |
Flammability rating according to UL 94 |
V0 |
Mounting type |
NS 35/7,5 |
Rated surge voltage |
8 kV |
Degree of pollution |
3 |
Overvoltage category |
III |
Insulating material group |
I |
Nominal current IN |
24 A |
Nominal voltage UN |
690 V |
Open side panel |
Yes |
Shock protection test specification |
IEC 60529:2001-02 |
Back of the hand protection |
guaranteed |
Finger protection |
guaranteed |
Result of surge voltage test |
Test passed |
Result of power-frequency withstand voltage test |
Test passed |
Power frequency withstand voltage setpoint |
1.89 kV |
Result of the test for mechanical stability of terminal points (5 x conductor connection) |
Test passed |
Result of flexion and pull-out test |
Test passed |
Bending test rotation speed |
10 rpm |
Bending test turns |
135 |
Bending test conductor cross section/weight |
0.2 mm² / 0.2 kg |
|
2.5 mm² / 0.7 kg |
Tensile test result |
Test passed |
Result of tight fit on support |
Test passed |
Tight fit on carrier |
NS 32/NS 35 |
Setpoint |
1 N |
Result of voltage-drop test |
Test passed |
Result of temperature-rise test |
Test passed |
Requirement temperature-rise test |
Increase in temperature ≤ 45 K |
Short circuit stability result |
Test passed |
Conductor cross section short circuit testing |
2.5 mm² |
Short-time current |
0.3 kA |
Conductor cross section short circuit testing |
4 mm² |
Short-time current |
0.48 kA |
Result of thermal test |
Test passed |
Proof of thermal characteristics (needle flame) effective duration |
30 s |
Relative insulation material temperature index (Elec., UL 746 B) |
130 °C |
Temperature index of insulation material (DIN EN 60216-1 (VDE 0304-21)) |
130 °C |
Static insulating material application in cold |
-60 °C |
Surface flammability NFPA 130 (ASTM E 162) |
passed |
Specific optical density of smoke NFPA 130 (ASTM E 662) |
passed |
Calorimetric heat release NFPA 130 (ASTM E 1354) |
28 MJ/kg |
Smoke gas toxicity NFPA 130 (SMP 800C) |
passed |
Fire protection for rail vehicles (DIN EN 45545-2) R22 |
HL 1 – HL 3 |
Fire protection for rail vehicles (DIN EN 45545-2) R23 |
HL 1 – HL 3 |
Fire protection for rail vehicles (DIN EN 45545-2) R24 |
HL 1 – HL 3 |
Fire protection for rail vehicles (DIN EN 45545-2) R26 |
HL 1 – HL 3 |
Dimensions
Width |
6.2 mm |
End cover width |
1.5 mm |
Length |
42.5 mm |
Height NS 35/7,5 |
42 mm |
Height NS 35/15 |
49.5 mm |
Height NS 32 |
47 mm |
Connection data
Connection method |
Screw connection |
Screw thread |
M3 |
Stripping length |
7 mm |
Tightening torque, min |
0.6 Nm |
Tightening torque max |
0.8 Nm |
Conductor cross section solid min. |
0.2 mm² |
Conductor cross section solid max. |
4 mm² |
Conductor cross section AWG min. |
24 |
Conductor cross section AWG max. |
12 |
Conductor cross section flexible min. |
0.2 mm² |
Conductor cross section flexible max. |
2.5 mm² |
Min. AWG conductor cross section, flexible |
24 |
Max. AWG conductor cross section, flexible |
14 |
Conductor cross section flexible, with ferrule without plastic sleeve min. |
0.25 mm² |
Conductor cross section flexible, with ferrule without plastic sleeve max. |
2.5 mm² |
Conductor cross section flexible, with ferrule with plastic sleeve min. |
0.25 mm² |
Conductor cross section flexible, with ferrule with plastic sleeve max. |
1 mm² |
2 conductors with same cross section, solid min. |
0.2 mm² |
2 conductors with same cross section, solid max. |
1 mm² |
2 conductors with same cross section, stranded min. |
0.25 mm² |
2 conductors with same cross section, stranded max. |
1 mm² |
Two conductors with the same cross section, flexible, with TWIN ferrules, with plastic sleeve, minimum |
0.5 mm² |
Two conductors with the same cross section, flexible, with TWIN ferrules, with plastic sleeve, maximum |
1.5 mm² |
Two conductors with the same cross section stranded, with ferrule and without plastic sleeve, minimum |
0.25 mm² |
Two conductors with the same cross section stranded, with ferrule and without plastic sleeve, maximum |
1 mm² |
Connection in acc. with standard |
UL |
Conductor cross section AWG min. |
30 |
Conductor cross section AWG max. |
12 |
Internal cylindrical gage |
A3 |
Ambient conditions
Operating temperature |
-60 °C … 105 °C (max. short-term operating temperature 130°C) |
Ambient temperature (storage/transport) |
-25 °C … 60 °C (for a short time, not exceeding 24 h, -60 °C to +70 °C) |
Permissible humidity (storage/transport) |
30 % … 70 % |
Ambient temperature (assembly) |
-5 °C … 70 °C |
Ambient temperature (actuation) |
-5 °C … 70 °C |
Standards and Regulations
Connection in acc. with standard |
CSA |
|
UL |
Flammability rating according to UL 94 |
V0 |
Environmental Product Compliance
REACh SVHC |
Lead 7439-92-1 |
China RoHS |
Environmentally Friendly Use Period = 50 years |
|
For details about hazardous substances go to tab “Downloads”, Category “Manufacturer’s declaration” |