Specifications

Item Description
AFPG2543H / AFPG2543HTM AFPG2643H / AFPG2643HTM AFPG2423H / AFPG2423HTM AFPG2653H / AFPG2653HTM
Number of
controllable
I/O points
Control unit 32 points (DC input: 16, NPN output: 16) 32 points (DC input: 16, NPN output: 16) 24 points (DC input: 16, relay output: 8) 28 points (DC input: 16, PNP output: 12)
With FP0R expansion units Max. 128 points (up to 3 units) * When
using transistor output type expansion units
Max. 128 points (up to 3 units) * When
using transistor output type expansion units
Max. 120 points (up to 3 units) * When
using transistor output type expansion units
Max. 124 points (up to 3 units) * When
using transistor output type expansion units
With FPΣ expansion units Not possible Max. 288 points (up to 4 units) * When
using transistor output type expansion units
Max. 280 points (up to 4 units) * When
using transistor output type expansion units
Max. 284 points (up to 4 units) * When
using NPN output type expansion units
With FP0R and FPΣ
expansion units
Max. 128 points * When using transistor
output type expansion units
Max. 384 points * When using transistor
output type expansion units
Max. 376 points * When using transistor
output type expansion units
Max. 380 points * When using NPN output
type expansion units
Programming method / Control method Relay symbol / Cyclic operation
Program memory / Program capacity Built-in flash ROM (no backup battery required) / 32 k steps
Number of
instructions
Basic instructions 93
High-level instructions 216 218 216 218
Operation speed Basic instruction: 0.32 μs~/step
Operation memory Relay Internal relay (R) 4,096 points: R0 to R255F (Note 1)
Timer / Counter (T/C) 1,024 points (Note 1, 2) [for initial setting, timer: 1,008 points (T0 to T1007), counter: 16 points (C1008 to C1023)]
Timer: Counts each unit up to 32,767 times (units: 1 ms, 10 ms, 100 ms, or 1 sec.). Counter: Counts 1 to 32,767.
Link relays (L) 2,048 points
32,765 words (DT0 to DT32764) (Note 1)
Memory area Data register (DT) 32,765 words (DT0 to DT32764) (Note 1)
Link data register (LD) 256 words
Index register (I) 14 words (I0 to ID)
Differential points Unlimited
Master control relay points (MCR) 256
Number of labels (JP and LOOP) 256
Number of step ladders 1,000 stages
Number of subroutines 100 subroutines
Pulse catch input 8 points (X0 to X7)
Number of interrupt programs 9 programs (8 external input points (X0 to X7), 1 periodical interrupt point 0.5 ms to 30 sec.)
Self-diagnosis function E. g. watchdog timer, program syntax check
Clock / calendar function Available year (last two digits), month, day, hour (24-hour display), minute, second and day of week;
however, this function can only be used when a battery is installed. (Note 3)
Potentiometer (Volume) input 2 points, resolution: 10 bits (K0 to K1000)
Battery life 220 days or more (actual usage value: approx. 840 days (+25 ℃ +77 ℉).
Suggested replacement interval: 1 year. (Value applies when no power is supplied at all.)
Comment storage All kinds of comments, including I/O comments, remarks, and block comments, can be stored (without backup battery).
Link function Computer link (1 : 1, 1 : N) (Note 4), General-purpose communication (1 : 1, 1 : N) (Note 4, 5), PLC link (Note 6)
Other functions Program edition during RUN, constant scan, forced on/off, password, floating-point operation, and PID processing
Differential points Linear/Circular interpolation for positioning

 

Notes: 1) If no battery is used, only the fixed area is backed up (counters 16 points: C1008 to C1023, internal relays 128 points: R2480 to R255F, data registers 55 words: DT32710 to DT32764).
When the optional battery is used, data can be backed up. Areas to be held and not held can be specified using the system registers. (Exclusive instructions allow writing and reading data in flash ROM.)
2) The number of points can be increased by using an auxiliary timer.
3) Precision of calendar timer: – At 0 ℃ +32 ℉, less than 119 seconds error per month.
– At +25 ℃ +77 ℉, less than 51 seconds error per month.
– At +55 ℃ +131 ℉, less than 148 seconds error per month.
4) An optional communication cassette (RS-232C type) is required in order to use 1 : 1 communication.
5) An optional communication cassette (RS-485 type) is required in order to use 1 : N communication.
6) An optional communication cassette (RS-485 type) is required.
When the communication cassette is attached and it communicates, re-send processing is recommended.

 

Product Number FPG-C24R2H
Part Number AFPG2423H
Product FPΣ Control Units
Details FPΣ C24 Left-side expansion type Control unit

 

Product Number FPG-C24R2HTM
Part Number AFPG2423HTM
Product FPΣ Control Units
Details FPΣ C24 Left-side expansion type Control unit with thermistor input

 

Product Number FPG-C32TH
Part Number AFPG2543H
Product FPΣ Control Units
Details FPΣ C32 Control unit

 

Product Number FPG-C32THTM
Part Number AFPG2543HTM
Product FPΣ Control Units
Details FPΣ C32 Control unit with thermistor input

 

Product Number FPG-C32T2HTM
Part Number AFPG2643HTM
Product FPΣ Control Units
Details FPΣ C32 Left-side expansion type Control unit with thermistor input

 

Product Number FPG-C28P2H
Part Number AFPG2653H
Product FPΣ Control Units
Details FPΣ C28 Left-side expansion type Control unit (PNP)

 

Product Number FPG-C28P2HTM
Part Number AFPG2653HTM
Product FPΣ Control Units
Details FPΣ C28 Left-side expansion type Control unit (PNP) with thermistor input

Additional information

Related Products

SCHNEIDER_Safety Relays
PHOENIX CONTACT_POWER SUPPLY-QUINTPOWER__2904598
c-mount_lens_12mm_tamron_5megapixel_ids_ueye-3
Festo_Vacuum generators_VN-07-L-T3-PQ2-VQ2-RO1_193572
SCHNEIDER_LXM52 Single Drive 24A-72A
Festo Type Air Source Processor LF-D-MINI-MIDI Oil-Water Separator Air Filter Pneumatic Component
Select your currency