TRIO-PS/1AC/24DC/ 5 – 2866310 – Phoenix Contact Power Supply

USD $ 138.60

SKU: 2866310

Inosaki is one of the largest Phoenix Contact Distributors to provide terminal block, interface module, power supply and relay. And our best offer for terminal block types are Feed-through, Fuse Modular, Spring Cage, Double Level, and Multi-level, hence the series model references to  PT Series, ST Series, TB Series, UT Series, UK Series. In additional for power supply are QUINT Power, STEP Power, Trio Power, and UNO Power. Please email us for catalog: sales@inosaki.com

Product Description

TRIO POWER power supplies with standard functionality
TRIO POWER is particularly suited to standard machine production, thanks to 1- and 3-phase versions up to 960 W. The wide-range input and the international approval package enable worldwide use.
The robust metal housing, the high electric strength, and the wide temperature range ensure a high level of power supply reliability.

 

Dimensions

Dimensional drawing
Width 40 mm
Height 130 mm
Depth 115 mm

 

Ambient Conditions

Degree of protection IP20
Ambient temperature (operation) -25 °C … 70 °C (> 55° C derating : 2.5%/K)
Ambient temperature (storage/transport) -40 °C … 85 °C
Climatic class 3K3 (in acc. with EN 60721)
Max. permissible relative humidity (operation) ≤ 95 % (at 25 °C, non-condensing)
Shock 15g in all directions in acc. with IEC 60068-2-27
Vibration (operation) < 15 Hz, amplitude ±2.5 mm (according to IEC 60068-2-6)
15 Hz … 150 Hz, 2.3g, 90 min.

Input Data

AC operation
Nominal input voltage range 100 V AC … 240 V AC
Input voltage range 85 V AC … 264 V AC (Derating < 90 V AC: 2,5 %/V)
Derating < 90 V AC (2.5 %/V)
Input voltage range AC 85 V AC … 264 V AC (Derating < 90 V AC: 2,5 %/V)
Electric strength, max. 300 V AC
Voltage type of supply voltage AC
Inrush current < 15 A
Inrush current integral (I2t) 1.1 A2s
AC frequency range 45 Hz … 65 Hz
Mains buffering time > 20 ms (120 V AC)
> 110 ms (230 V AC)
Current consumption 1.65 A (120 V AC)
0.9 A (230 V AC)
Nominal power consumption 189 VA
Protective circuit Transient surge protection; Varistor
Power factor (cos phi) 0.72
Typical response time < 1 s
Input fuse 3.15 A (slow-blow, internal)
Permissible backup fuse B6 B10 B16
Recommended breaker for input protection 6 A … 16 A (Characteristics B, C, D, K)
Discharge current to PE < 3.5 mA

Output Data

Efficiency 89 % (for 230 V AC and nominal values)
Output characteristic U/I
Nominal output voltage 24 V DC ±1 %
Setting range of the output voltage (USet) 22.5 V DC … 29.5 V DC (> 24 V DC, constant capacity restricted)
Nominal output current (IN) 5 A (UOUT = 24 V DC)
Derating 55 °C … 70 °C (2.5%/K)
Feedback voltage resistance 35 V DC
Protection against overvoltage at the output (OVP) < 35 V DC
Max. capacitive load unlimited
Active current limitation approx. 10 A (for short-circuit)
Control deviation < 1 % (change in load, static 10 % … 90 %)
< 2 % (change in load, dynamic 10 % … 90 %)
< 0.1 % (change in input voltage ±10 %)
Residual ripple < 20 mVPP
Output power 120 W
Peak switching voltages nominal load < 30 mVPP
Maximum no-load power dissipation 1.1 W
Power loss nominal load max. 18 W
Rise time < 2 ms (UOUT (10 % … 90 %))
Connection in parallel yes, for redundancy and increased capacity
Connection in series yes

Commercial Data

Item number 2866310
Packing unit 1 pc
Minimum order quantity 1 pc
Sales Key CM11
Product Key CMPT13
Catalog Page Page 175 (C-6-2013)
GTIN 4046356046640
Weight per Piece (including packing) 749 g
Weight per Piece (excluding packing) 618 g
Customs tariff number 85044083
Country of origin CN

Connection Data, Input

Connection method Screw connection
Conductor cross section, rigid min. 0.2 mm²
Conductor cross section, rigid max. 2.5 mm²
Conductor cross section flexible min. 0.2 mm²
Conductor cross section flexible max. 2.5 mm²
Conductor cross section AWG min. 24
Conductor cross section AWG max. 14
Stripping length 9 mm
Screw thread M2,5
Tightening torque, min 0.4 Nm
Tightening torque max 0.5 Nm

Connection Data, Output

Connection method Screw connection
Conductor cross section, rigid min. 0.2 mm²
Conductor cross section, rigid max. 2.5 mm²
Conductor cross section flexible min. 0.2 mm²
Conductor cross section flexible max. 2.5 mm²
Conductor cross section AWG min. 24
Conductor cross section AWG max. 14
Stripping length 9 mm
Screw thread M2,5
Tightening torque, min 0.4 Nm
Tightening torque max 0.5 Nm

Standards and Regulations

Standard – Electronic equipment for use in electrical power installations and their assembly into electrical power installations EN 50178/VDE 0160 (PELV)
Standard – Limitation of mains harmonic currents EN 61000-3-2
Standard – Electrical safety EN 60950-1/VDE 0805 (SELV)
Standard – Protection against shock currents, basic requirements for protective separation in electrical equipment EN 50178
Standard – Safety extra-low voltage EN 60950-1 (SELV)
EN 60204 (PELV)
Standard – Safe isolation DIN VDE 0100-410

EMC Data

Low Voltage Directive Conformance with Low Voltage Directive 2014/35/EC
EMC requirements for noise emission EN 61000-6-3
EN 61000-6-4
EMC requirements for noise immunity EN 61000-6-1
EN 61000-6-2
Electromagnetic compatibility Conformance with EMC Directive 2014/30/EU
Electrostatic discharge
Standards/regulations EN 61000-4-2
Electrostatic discharge
Contact discharge 8 kV (Test Level 4)
Discharge in air 8 kV (Test Level 3)
Comments Criterion A
Electromagnetic HF field
Standards/regulations EN 61000-4-3
Electromagnetic HF field
Frequency range 80 MHz … 1 GHz
Test field strength 10 V/m
Frequency range 1 GHz … 2 GHz
Test field strength 10 V/m
Frequency range 2 GHz … 3 GHz
Test field strength 10 V/m
Comments Criterion A
Fast transients (burst)
Standards/regulations EN 61000-4-4
Fast transients (burst)
Input 4 kV (Test Level 4 – asymmetrical)
Output 4 kV (Test Level 4 – asymmetrical)
Signal 2 kV (Test Level 3 – asymmetrical)
Comments Criterion A
Surge voltage load (surge)
Standards/regulations EN 61000-4-5
Input 2 kV (Test Level 3 – symmetrical)
4 kV (Test Level 4 – asymmetrical)
Output 1 kV (Test Level 2 – symmetrical)
2 kV (Test Level 3 – asymmetrical)
Comments Criterion A
Conducted interference
Standards/regulations EN 61000-4-6
Conducted interference
Frequency range 10 kHz … 15 kHz
10 kHz … 15 kHz
Comments Criterion A
Criterion A
Voltage 3 V (Test Level 2)
3 V (Test Level 2)
Conducted interference
Frequency range 10 kHz … 15 kHz
10 kHz … 15 kHz
Comments Criterion A
Criterion A
Voltage 3 V (Test Level 2)
3 V (Test Level 2)
Voltage dips
Standards/regulations EN 61000-4-11
Emitted interference
Standards/regulations EN 61000-6-3
Radio interference voltage in acc. with EN 55011 EN 55011 (EN 55022) Class B, area of application: Industry and residential
Emitted radio interference in acc. with EN 55011 EN 55011 (EN 55022) Class B, area of application: Industry and residential
Weight 0.618 kg
Dimensions 11.50 × 4.00 × 13.00 cm