SIMATIC S7-300 – CPU319F-3 PN/DP – Siemens PLC

USD $ 4,153.75

SKU: 6ES7318-3FL01-0AB0

The CPU 319F-3 PN/DP is the fastest S7-300 CPU with a large program memory. It is ideally suited to plants with extensive automation tasks and stringent safety requirements.It can be implemented as a PROFINET IO controller and as a standard PROFIBUS DP master in SIMATIC S7-300. The CPU 319F-3 PN/DP can also be used as distributed intelligence (DP slave).Distributed I/O devices with fail-safe I/O modules can be connected over the three integrated interfaces. The fail-safe ET 200M I/O modules can also be installed in central and safety-related configurations.The integrated communication options of the CPU support networked automation solutions (also fail-safe) without the need for additional components.

Siemens PLC S7-300 Product Specifications:

Article number 6ES7318-3FL01-0AB0
CPU319F-3 PN/DP, 2.5 MB
General information
HW functional status 1
Firmware version V3.2
Product function
● Isochronous mode Yes; Via 2nd PROFIBUS DP or PROFINET interface
Engineering with
● Programming package STEP 7 V5.5 or higher, Distributed Safety V5.4 SP4
Supply voltage
Rated value (DC) 24 V
permissible range, lower limit (DC) 19.2 V
permissible range, upper limit (DC) 28.8 V
external protection for power supply lines (recommendation) 2 A min.
Mains buffering
● Mains/voltage failure stored energy time 5 ms
● Repeat rate, min. 1 s
Input current
Current consumption (rated value) 1 250 mA
Current consumption (in no-load operation), typ. 500 mA
Inrush current, typ. 4 A
I²t 1.2 A²·s
Power loss
Power loss, typ. 14 W
Memory
Work memory
● integrated 2 560 kbyte
● expandable No
Load memory
● Plug-in (MMC) Yes
● Plug-in (MMC), max. 8 Mbyte
● Data management on MMC (after last programming), min. 10 y
Backup
● present Yes
● without battery Yes
CPU processing times
for bit operations, typ. 0.004 µs
for word operations, typ. 0.01 µs
for fixed point arithmetic, typ. 0.01 µs
for floating point arithmetic, typ. 0.04 µs
CPU-blocks
Number of blocks (total) 4 096; (DBs, FCs, FBs); the maximum number of loadable blocks can be reduced by the MMC used.
DB
● Number, max. 4 096; Number range: 1 to 16000
● Size, max. 64 kbyte
FB
● Number, max. 4 096; Number range: 0 to 7999
● Size, max. 64 kbyte
FC
● Number, max. 4 096; Number range: 0 to 7999
● Size, max. 64 kbyte
OB
● Size, max. 64 kbyte
● Number of free cycle OBs 1; OB 1
● Number of time alarm OBs 1; OB 10
● Number of delay alarm OBs 2; OB 20, 21
● Number of cyclic interrupt OBs 4; OB 32, 33, 34, 35 (OB 35: smallest settable clock pulse = 500 µs)
● Number of process alarm OBs 1; OB 40
● Number of DPV1 alarm OBs 3; OB 55, 56, 57
● Number of isochronous mode OBs 1; OB 61
● Number of startup OBs 1; OB 100
● Number of asynchronous error OBs 6; OB 80, 82, 83, 85, 86, 87 (OB83 only for PROFINET IO)
● Number of synchronous error OBs 2; OB 121, 122
Nesting depth
● per priority class 16
● additional within an error OB 4
Counters, timers and their retentivity
S7 counter
● Number 2 048
Retentivity
— adjustable Yes
— lower limit 0
— upper limit 2 047
— preset Z 0 to Z 7
Counting range
— adjustable Yes
— lower limit 0
— upper limit 999
IEC counter
● present Yes
● Type SFB
● Number Unlimited (limited only by RAM capacity)
S7 times
● Number 2 048
Retentivity
— adjustable Yes
— lower limit 0
— upper limit 2 047
— preset No retentivity
Time range
— lower limit 10 ms
— upper limit 9 990 s
IEC timer
● present Yes
● Type SFB
● Number Unlimited (limited only by RAM capacity)
Data areas and their retentivity
Retentive data area (incl. timers, counters, flags), max. 700 kbyte
Flag
● Size, max. 8 192 byte
● Retentivity available Yes; From MB 0 to MB 8 191
● Retentivity preset MB 0 to MB 15
● Number of clock memories 8; 1 memory byte
Data blocks
● Retentivity adjustable Yes; via non-retain property on DB
● Retentivity preset Yes
Local data
● per priority class, max. 32 768 byte; Max. 2048 bytes per block
Address area
I/O address area
● Inputs 8 192 byte
● Outputs 8 192 byte
of which distributed
— Inputs 8 192 byte
— Outputs 8 192 byte
Process image
● Inputs 8 192 byte
● Outputs 8 192 byte
● Inputs, adjustable 8 192 byte
● Outputs, adjustable 8 192 byte
● Inputs, default 1 024 byte
● Outputs, default 1 024 byte
Subprocess images
● Number of subprocess images, max. 1; With PROFINET IO, the length of the user data is limited to 1600 bytes
Digital channels
● Inputs 65 536
— of which central 1 024
● Outputs 65 536
— of which central 1 024
Analog channels
● Inputs 4 096
— of which central 256
● Outputs 4 096
— of which central 256
Hardware configuration
Number of DP masters
● integrated 2
● via CP 4
Number of operable FMs and CPs (recommended)
● FM 8
● CP, PtP 8
● CP, LAN 10
Rack
● Racks, max. 4
● Modules per rack, max. 8
Time of day
Clock
● Hardware clock (real-time) Yes
● retentive and synchronizable Yes
● Backup time 6 wk; At 40 °C ambient temperature
● Deviation per day, max. 10 s; Typ.: 2 s
● Behavior of the clock following POWER-ON Clock continues running after POWER OFF
● Behavior of the clock following expiry of backup period the clock continues at the time of day it had when power was switched off
Operating hours counter
● Number 4
● Number/Number range 0 to 3
● Range of values 0 to 2^31 hours (when using SFC 101)
● Granularity 1 h
● retentive Yes; Must be restarted at each restart
Clock synchronization
● supported Yes
● to MPI, master Yes
● to MPI, slave Yes
● to DP, master Yes; With DP slave only slave clock
● to DP, slave Yes
● in AS, master Yes
● in AS, slave Yes
● on Ethernet via NTP Yes; As client
Digital inputs
Number of digital inputs 0
Digital outputs
Number of digital outputs 0
Analog inputs
Number of analog inputs 0
Analog outputs
Number of analog outputs 0
Interfaces
Number of industrial Ethernet interfaces 1
Number of PROFINET interfaces 1
Number of RS 485 interfaces 2
Number of RS 422 interfaces 0
1. Interface
Interface type Integrated RS 485 interface
Isolated Yes
Interface types
● RS 485 Yes
● Output current of the interface, max. 150 mA
Protocols
● MPI Yes
● PROFIBUS DP master Yes
● PROFIBUS DP slave Yes; A DP slave at both interfaces simultaneously is not possible
● Point-to-point connection No
MPI
● Transmission rate, max. 12 Mbit/s
Services
— PG/OP communication Yes
— Routing Yes
— Global data communication Yes
— S7 basic communication Yes
— S7 communication Yes
— S7 communication, as client No; but via CP and loadable FB
— S7 communication, as server Yes
PROFIBUS DP master
● Transmission rate, max. 12 Mbit/s
● Number of DP slaves, max. 124
Services
— PG/OP communication Yes
— Routing Yes
— Global data communication No
— S7 basic communication Yes; I blocks only
— S7 communication Yes
— S7 communication, as client No
— S7 communication, as server Yes
— Equidistance Yes
— Isochronous mode No
— SYNC/FREEZE Yes
— Activation/deactivation of DP slaves Yes
— Number of DP slaves that can be simultaneously activated/deactivated, max. 8
— Direct data exchange (slave-to-slave communication) Yes; as subscriber
— DPV1 Yes
Address area
— Inputs, max. 8 kbyte
— Outputs, max. 8 kbyte
User data per DP slave
— Inputs, max. 244 byte
— Outputs, max. 244 byte
PROFIBUS DP slave
● Transmission rate, max. 12 Mbit/s
● automatic baud rate search Yes; only with passive interface
● Address area, max. 32
● User data per address area, max. 32 byte
Services
— PG/OP communication Yes
— Routing Yes; with interface active
— Global data communication No
— S7 basic communication No
— S7 communication Yes
— S7 communication, as client No
— S7 communication, as server Yes; Connection configured on one side only
— Direct data exchange (slave-to-slave communication) Yes
— DPV1 No
Transfer memory
— Inputs 244 byte
— Outputs 244 byte
2. Interface
Interface type Integrated RS 485 interface
Isolated Yes
Interface types
● RS 485 Yes
● Output current of the interface, max. 200 mA
Protocols
● MPI No
● PROFINET IO Controller No
● PROFINET IO Device No
● PROFINET CBA No
● PROFIBUS DP master Yes
● PROFIBUS DP slave Yes; A DP slave at both interfaces simultaneously is not possible
● Open IE communication No
● Web server No
PROFIBUS DP master
● Transmission rate, max. 12 Mbit/s
● Number of DP slaves, max. 124
Services
— PG/OP communication Yes
— Routing Yes
— Global data communication No
— S7 basic communication Yes; I blocks only
— S7 communication Yes
— S7 communication, as client No
— S7 communication, as server Yes; Connection configured on one side only
— Equidistance Yes
— Isochronous mode Yes; OB 61 – isochronous mode is possible either on DP or PROFINET IO (not simultaneously)
— SYNC/FREEZE Yes
— Activation/deactivation of DP slaves Yes
— Number of DP slaves that can be simultaneously activated/deactivated, max. 8
— Direct data exchange (slave-to-slave communication) Yes; as subscriber
— DPV1 Yes
Address area
— Inputs, max. 8 kbyte
— Outputs, max. 8 kbyte
User data per DP slave
— Inputs, max. 244 byte
— Outputs, max. 244 byte
PROFIBUS DP slave
● GSD file The latest GSD file is available at: http://www.siemens.com/profibus-gsd
● Transmission rate, max. 12 Mbit/s
● automatic baud rate search Yes; only with passive interface
● Address area, max. 32
● User data per address area, max. 32 byte
Services
— PG/OP communication Yes
— Routing Yes; with interface active
— Global data communication No
— S7 basic communication No
— S7 communication Yes
— S7 communication, as client No
— S7 communication, as server Yes; Connection configured on one side only
— Direct data exchange (slave-to-slave communication) Yes
— DPV1 No
Transfer memory
— Inputs 244 byte
— Outputs 244 byte
3. Interface
Interface type PROFINET
Isolated Yes
automatic detection of transmission rate Yes; 10/100 Mbit/s
Autonegotiation Yes
Autocrossing Yes
Change of IP address at runtime, supported Yes
Interface types
● RJ 45 (Ethernet) Yes
● Number of ports 2
● integrated switch Yes
Protocols
● MPI No
● PROFINET IO Controller Yes; Also simultaneously with I-Device functionality
● PROFINET IO Device Yes; Also simultaneously with IO Controller functionality
● PROFINET CBA Yes
● PROFIBUS DP master No
● PROFIBUS DP slave No
● Open IE communication Yes; Via TCP/IP, ISO on TCP, and UDP
● Web server Yes
● Media redundancy Yes
PROFINET IO Controller
● Transmission rate, max. 100 Mbit/s
Services
— PG/OP communication Yes
— Routing Yes
— S7 communication Yes; with loadable FBs, max. configurable connections: 16, max. number of instances: 32
— Isochronous mode Yes; OB 61 – isochronous mode is possible either on DP or PROFINET IO (not simultaneously)
— Shared device Yes
— Prioritized startup Yes
— Number of IO devices with prioritized startup, max. 32
— Number of connectable IO Devices, max. 256
— Of which IO devices with IRT, max. 64
— of which in line, max. 64
— Number of IO Devices with IRT and the option “high flexibility” 256
— of which in line, max. 61
— Number of connectable IO Devices for RT, max. 256
— of which in line, max. 256
— Activation/deactivation of IO Devices Yes
— Number of IO Devices that can be simultaneously activated/deactivated, max. 8
— IO Devices changing during operation (partner ports), supported Yes
— Number of IO Devices per tool, max. 8
— Device replacement without swap medium Yes
— Send cycles 250 μs, 500 μs,1 ms; 2 ms, 4 ms (not in the case of IRT with “high flexibility” option)
— Updating time 250 µs to 512 ms (depending on the operating mode, see Manual “S7-300 CPU 31xC and CPU 31x, technical Data” for more details)
Address area
— Inputs, max. 8 kbyte
— Outputs, max. 8 kbyte
— User data consistency, max. 1 024 byte
PROFINET IO Device
Services
— PG/OP communication Yes
— Routing Yes
— S7 communication Yes; with loadable FBs, max. configurable connections: 16, max. number of instances: 32
— Isochronous mode No
— IRT Yes
— PROFIenergy Yes; With SFB 73 / 74 prepared for loadable PROFIenergy standard FB for I-Device
— Shared device Yes
— Number of IO Controllers with shared device, max. 2
Transfer memory
— Inputs, max. 1 440 byte; Per IO Controller with shared device
— Outputs, max. 1 440 byte; Per IO Controller with shared device
Submodules
— Number, max. 64
— User data per submodule, max. 1 024 byte
PROFINET CBA
● acyclic transmission Yes
● cyclic transmission Yes
Open IE communication
● Number of connections, max. 32
● Local port numbers used at the system end 0, 20, 21, 23, 25, 80, 102, 135, 161, 443, 8080, 34962, 34963, 34964, 65532, 65533, 65534, 65535
● Keep-alive function, supported Yes
Protocols
PROFIsafe Yes
Redundancy mode
Media redundancy
— Switchover time on line break, typ. 200 ms; PROFINET MRP
— Number of stations in the ring, max. 50
Open IE communication
● TCP/IP Yes; via integrated PROFINET interface and loadable FBs
— Number of connections, max. 32
— Data length for connection type 01H, max. 1 460 byte
— Data length for connection type 11H, max. 32 768 byte
● ISO-on-TCP (RFC1006) Yes; via integrated PROFINET interface and loadable FBs
— Number of connections, max. 32
— Data length, max. 32 768 byte
● UDP Yes; via integrated PROFINET interface and loadable FBs
— Number of connections, max. 32
— Data length, max. 1 472 byte
Web server
● supported Yes
● User-defined websites Yes
● Number of HTTP clients 5
communication functions / header
PG/OP communication Yes
Data record routing Yes
Global data communication
● supported Yes
● Number of GD loops, max. 8
● Number of GD packets, max. 8
● Number of GD packets, transmitter, max. 8
● Number of GD packets, receiver, max. 8
● Size of GD packets, max. 22 byte
● Size of GD packet (of which consistent), max. 22 byte
S7 basic communication
● supported Yes
● User data per job, max. 76 byte
● User data per job (of which consistent), max. 76 byte; 76 bytes (with X_SEND or X_RCV); 64 bytes (with X_PUT or X_GET as server)
S7 communication
● supported Yes
● as server Yes
● as client Yes; via integrated PROFINET interface and loadable FB or via CP and loadable FB
● User data per job, max. See online help of STEP 7 (shared parameters of the SFBs/FBs and of the SFCs/FCs of S7 Communication)
S5 compatible communication
● supported Yes; via CP and loadable FC
communication functions / PROFINET CBA (with set target communication load) / header
● Setpoint for the CPU communication load 20 %
● number of remote connection partners / with PROFINET CBA 32
● number of technological functions / with PROFINET CBA / for master or slave 50
● number of connections / with PROFINET CBA / for master or slave / total 3 000
● data volume / of the input variables / with PROFINET CBA / for master or slave 24 000 byte
● data volume / of the output variables / with PROFINET CBA / for master or slave 24 000 byte
● number of internal and PROFIBUS interconnections / with PROFINET CBA / maximum 1 000
● data volume / of internal and PROFIBUS interconnections / with PROFINET CBA / for master or slave 8 000 byte
● data volume / with PROFINET CBA / per connection / maximum 1 400 byte
performance data / PROFINET CBA / remote interconnection / with acyclic transfer / header
— update time / of the remote interconnections / in the case of acyclic transmission / with PROFINET CBA 200 ms
— number of remote connections to input variables / in the case of acyclic transmission / with PROFINET CBA / maximum 100
— number of remote connections to output variables / in the case of acyclic transmission / with PROFINET CBA / maximum 100
— data volume / as user data for remote interconnections with input variables / in the case of acyclic transmission / with PROFINET CBA 3 200 byte
— data volume / as user data for remote interconnections with output variables / in the case of acyclic transmission / with PROFINET CBA 3 200 byte
— data volume / as user data for remote interconnections / in the case of acyclic transmission / with PROFINET CBA / per connection / maximum 1 400 byte
performance data / PROFINET CBA / remote interconnection / with cyclic transfer / header
— update time / of the remote interconnections / with cyclical transfer / with PROFINET CBA 1 ms
— number of remote connections to input variables / with PROFINET CBA / with cyclic transfer / maximum 300
— number of remote connections to output variables / with cyclical transfer / with PROFINET CBA / maximum 300
— data volume / as user data for remote interconnections with input variables / with cyclical transfer / with PROFINET CBA / maximum 4 800 byte
— data volume / as user data for remote interconnections with output variables / with cyclical transfer / with PROFINET CBA / maximum 4 800 byte
— data volume / as user data for remote interconnections / with cyclical transfer / with PROFINET CBA / per connection / maximum 450 byte
performance data / PROFINET CBA / HMI variables via PROFINET / acyclic / header
— number of connectable HMI stations / for HMI variables / in the case of acyclic transmission / with PROFINET CBA 3; 2x PN OPC/1x iMap
— update time / of the HMI variables / in the case of acyclic transmission / with PROFINET CBA 500 ms
— number of HMI variables / in the case of acyclic transmission / with PROFINET CBA / maximum 600
— data volume / as user data for HMI variables / in the case of acyclic transmission / with PROFINET CBA / maximum 9 600 byte
performance data / PROFINET CBA / PROFIBUS proxy functionality / header
— product function / with PROFINET CBA / PROFIBUS proxy functionality Yes
— number of coupled PROFIBUS devices / with PROFIBUS functionality 32
— data volume / with PROFIBUS proxy functionality / with PROFINET CBA / per connection / maximum 240 byte; Slave-dependent
Number of connections
● overall 32
● usable for PG communication 31
— reserved for PG communication 1
— adjustable for PG communication, min. 1
— adjustable for PG communication, max. 31
● usable for OP communication 31
— reserved for OP communication 1
— adjustable for OP communication, min. 1
— adjustable for OP communication, max. 31
● usable for S7 basic communication 30
— reserved for S7 basic communication 0
— adjustable for S7 basic communication, min. 0
— adjustable for S7 basic communication, max. 30
● usable for S7 communication 16
— reserved for S7 communication 0
— adjustable for S7 communication, min. 0
— adjustable for S7 communication, max. 16
● total number of instances, max. 32
● usable for routing X1 as MPI: max. 10; X1 as DP master: max. 24; X1 as DP slave (active): max. 14; X2 as DP master: max. 24; X2 as DP slave (active): max. 14; X3 as PROFINET: 48 max.
S7 message functions
Number of login stations for message functions, max. 32; Depending on the configured connections for PG/OP and S7 basic communication
Process diagnostic messages Yes
simultaneously active Alarm-S blocks, max. 300
Test commissioning functions
Status block Yes; Up to 2 simultaneously
Single step Yes
Number of breakpoints 4
Status/control
● Status/control variable Yes
● Variables Inputs, outputs, memory bits, DB, times, counters
● Number of variables, max. 30
— of which status variables, max. 30
— of which control variables, max. 14
Forcing
● Forcing Yes
● Forcing, variables Inputs, outputs
● Number of variables, max. 10
Diagnostic buffer
● present Yes
● Number of entries, max. 500
— adjustable No
— of which powerfail-proof 100
● Number of entries readable in RUN, max. 499
— adjustable Yes; From 10 to 499
— preset 10
Service data
● can be read out Yes
Ambient conditions
Ambient temperature during operation
● min. 0 °C
● max. 60 °C
configuration / header
Configuration software
● STEP 7 Yes; V5.5 or higher
configuration / programming / header
● Command set see instruction list
● Nesting levels 8
● System functions (SFC) see instruction list
● System function blocks (SFB) see instruction list
Programming language
— LAD Yes
— FBD Yes
— STL Yes
— SCL Yes
— CFC Yes
— GRAPH Yes
— HiGraph® Yes
Know-how protection
● User program protection/password protection Yes
● Block encryption Yes; With S7 block Privacy
Dimensions
Width 120 mm
Height 125 mm
Depth 130 mm
Weights
Weight, approx. 1 250 g
Weight 1.4 kg
Dimensions 16.7 × 18.1 × 15.5 cm