Scalable and cost-optimized configuration of a ET 200SP station is achieved by a comprehensive portfolio of digital and analog IO modules.
SIMATIC ET 200SP is about 50% narrower than other distributed peripheries. With its height of 115 millimeters, the system can accommodate 16 channels with single-wire connection (without AUX-plugs). For a 3-wire connection with AUX-plugs the height for 8 channels is 140 millimeters. The depth is 75 millimeters. In order to keep its small size, the power module for load group formation is integrated into the system of SIMATIC ET 200SP.
The peripheral modules are labelled with different colored squares to identify easily the type of module.
Article number | 6ES7132-6BF61-0AA0 | 6ES7132-6BH00-0AA0 | 6ES7132-6BF01-0AA0 | 6ES7132-6BH01-0BA0 | 6ES7132-6BF01-0BA0 |
ET 200SP, DQ 8x 24VDC/0,5A SINK BA, PU 1 | ET 200SP, DQ 16X24VDC/0,5A BA, PU 1 | ET 200SP, DQ 8x 24V DC/0,5A Basic, PU 1 | ET 200SP, DQ 16x 24V DC/0,5A ST, PU 1 | ET 200SP, DQ 8x 24V DC/0,5A ST, PU 1 | |
General information | |||||
Product type designation | DQ 8x24VDC/0,5A SNK BA | DQ 16x24VDC/0.5A BA | DQ 8x24VDC/0.5A BA | DQ 16x24VDC/0.5A ST | DQ 8x24VDC/0.5A ST |
HW functional status | From FS02 | From FS03 | From FS02 | From FS03 | From FS02 |
Firmware version | V0.0 | V0.0 | V0.0 | V0.0 | V0.0 |
● FW update possible | No | No | No | No | No |
usable BaseUnits | BU type A0 | BU type A0 | BU type A0 | BU type A0 | BU type A0 |
Color code for module-specific color identification plate | CC01 | CC00 | CC02 | CC00 | CC02 |
Product function | |||||
● I&M data | Yes; I&M0 to I&M3 | Yes; I&M0 to I&M3 | Yes; I&M0 to I&M3 | Yes; I&M0 to I&M3 | Yes; I&M0 to I&M3 |
● Isochronous mode | No | No | No | No | No |
Engineering with | |||||
● STEP 7 TIA Portal configurable/integrated from version | V14 | V14 | V14 | V14 | V14 |
● STEP 7 configurable/integrated from version | V5.5 SP3 | STEP 7 V5.5 or higher | V5.5 SP3 | V5.5 SP3 | V5.5 SP3 or higher |
● PCS 7 configurable/integrated from version | V8.1 SP1 | V8.1 SP1 | |||
● PROFIBUS from GSD version/GSD revision | One GSD file each, Revision 3 and 5 and higher | One GSD file each, Revision 3 and 5 and higher | One GSD file each, Revision 3 and 5 and higher | One GSD file each, Revision 3 and 5 and higher | One GSD file each, Revision 3 and 5 and higher |
● PROFINET from GSD version/GSD revision | GSDML V2.3 | GSDML V2.3 | GSDML V2.3 | GSDML V2.3 | GSDML V2.3 |
Operating mode | |||||
● DQ | Yes | Yes | Yes | Yes | Yes |
● DQ with energy-saving function | No | No | No | No | No |
● PWM | No | No | No | No | No |
● Oversampling | No | No | No | No | No |
● MSO | No | No | No | No | No |
Redundancy | |||||
● Redundancy capability | Yes | ||||
Supply voltage | |||||
Rated value (DC) | 24 V | 24 V | 24 V | 24 V | 24 V |
permissible range, lower limit (DC) | 19.2 V | 19.2 V | 19.2 V | 19.2 V | 19.2 V |
permissible range, upper limit (DC) | 28.8 V | 28.8 V | 28.8 V | 28.8 V | 28.8 V |
Reverse polarity protection | Yes | Yes | Yes | Yes | |
Input current | |||||
Current consumption, max. | 55 mA; without load | 45 mA; without load | 60 mA; without load | 35 mA; without load | |
output voltage / header | |||||
Rated value (DC) | 24 V | 24 V | 24 V | 24 V | 24 V |
Power loss | |||||
Power loss, typ. | 1.5 W | 1 W | 1 W | 1 W | 1 W |
Address area | |||||
Address space per module | |||||
● Address space per module, max. | 1 byte | 2 byte; + 2 bytes for QI information | 1 byte; + 1 byte for QI information | ||
● Outputs | 1 byte | 2 byte | |||
Hardware configuration | |||||
Automatic encoding | Yes | Yes | Yes | Yes | Yes |
● Mechanical coding element | Yes | Yes | Yes | Yes | Yes |
● Type of mechanical coding element | type B | Type A | Type A | Type A | Type A |
Selection of BaseUnit for connection variants | |||||
● 1-wire connection | BU type A0 | BU type A0 | BU type A0 | BU type A0 | |
● 2-wire connection | BU type A0 + Potential distributor module | BU type A0 | BU type A0 + Potential distributor module | BU type A0 | |
● 3-wire connection | BU type A0 + Potential distributor module | BU type A0 with AUX terminals or potential distributor module | BU type A0 + Potential distributor module | BU type A0 with AUX terminals or potential distributor module | |
● 4-wire connection | BU type A0 + Potential distributor module | BU type A0 + Potential distributor module | BU type A0 + Potential distributor module | BU type A0 + Potential distributor module | |
Digital outputs | |||||
Type of digital output | Source output (PNP, current-sourcing) | Source output (PNP, current-sourcing) | Source output (PNP, current-sourcing) | Source output (PNP, current-sourcing) | Source output (PNP, current-sourcing) |
Number of digital outputs | 8 | 16 | 8 | 16 | 8 |
Current-sinking | Yes | No | No | ||
Current-sourcing | Yes | Yes | Yes | Yes | |
Digital outputs, parameterizable | Yes | Yes | Yes | Yes | Yes |
Short-circuit protection | Yes | Yes | Yes; per channel, electronic | Yes | Yes |
● Response threshold, typ. | 1.5 A | 1.4 A; 0.7 to 1.9 A | 1 A | 1 A; 0.7 to 1.3 A | 1 A |
Open-circuit detection | No | Yes | |||
Limitation of inductive shutdown voltage to | Typ. 47 V | Typ. L+ (-53 V) | Typ. L+ (-50 V) | Typ. L+ (-50 V) | Typ. L+ (-50 V) |
Controlling a digital input | Yes | Yes | Yes | Yes | Yes |
Switching capacity of the outputs | |||||
● with resistive load, max. | 0.5 A | 0.5 A | 0.5 A | 0.5 A | 0.5 A |
● on lamp load, max. | 5 W | 5 W | 5 W | 5 W | 5 W |
Load resistance range | |||||
● lower limit | 48 Ω | 48 Ω | 48 Ω | 48 Ω | 48 Ω |
● upper limit | 3 400 Ω | 100 kΩ | 100 kΩ | 12 kΩ | 12 kΩ |
Output voltage | |||||
● for signal “1”, min. | L+ (-0.8 V) | ||||
Output current | |||||
● for signal “1” rated value | 0.5 A | 0.5 A | 0.5 A | 0.5 A | 0.5 A |
● for signal “1” permissible range, max. | 0.5 A | 0.5 A | 0.5 A | ||
● for signal “0” residual current, max. | 5 µA | 30 µA | 10 µA | 0.1 mA | 0.1 mA |
Output delay with resistive load | |||||
● “0” to “1”, typ. | 80 µs; at rated load | 50 µs | |||
● “0” to “1”, max. | 300 µs | 150 µs; at rated load | 100 µs; at rated load | 50 µs; at rated load | |
● “1” to “0”, typ. | 100 µs; at rated load | 100 µs | |||
● “1” to “0”, max. | 600 µs | 200 µs; at rated load | 150 µs; at rated load | 100 µs; at rated load | |
Parallel switching of two outputs | |||||
● for uprating | No | No | No | No | No |
● for redundant control of a load | Yes | Yes | Yes | Yes | Yes |
Switching frequency | |||||
● with resistive load, max. | 100 Hz | 100 Hz | 100 Hz | 100 Hz | 100 Hz |
● with inductive load, max. | 0.5 Hz | 2 Hz | 2 Hz | 2 Hz | 2 Hz |
● on lamp load, max. | 10 Hz | 10 Hz | 10 Hz | 10 Hz | 10 Hz |
Total current of the outputs | |||||
● Current per channel, max. | 0.5 A | 0.5 A | 0.5 A | 0.5 A | 0.5 A |
● Current per module, max. | 4 A | 8 A | 4 A | 8 A | 4 A |
Total current of the outputs (per module) | |||||
horizontal installation | |||||
— up to 40 °C, max. | 8 A | ||||
— up to 50 °C, max. | 6 A | ||||
— up to 60 °C, max. | 4 A | 8 A | 4 A | 4 A | 4 A |
vertical installation | |||||
— up to 30 °C, max. | 8 A | ||||
— up to 40 °C, max. | 6 A | ||||
— up to 50 °C, max. | 4 A | 8 A | 4 A | 4 A | 4 A |
Cable length | |||||
● shielded, max. | 1 000 m | 1 000 m | 1 000 m | 1 000 m | 1 000 m |
● unshielded, max. | 600 m | 600 m | 600 m | 600 m | 600 m |
Interrupts/diagnostics/status information | |||||
Diagnostics function | Yes | Yes | Yes | Yes | Yes |
Substitute values connectable | Yes | Yes | Yes | Yes | Yes |
Alarms | |||||
● Diagnostic alarm | Yes | Yes | Yes | Yes | Yes |
Diagnoses | |||||
● Monitoring the supply voltage | Yes | Yes | Yes | Yes | Yes |
● Wire-break | No | No | No | Yes; Module-wise | Yes; Module-wise |
● Short-circuit | No | No | No | ||
● Short-circuit to M | Yes; Module-wise | Yes; Module-wise | |||
● Short-circuit to L+ | Yes; Module-wise | Yes; Module-wise | |||
● Group error | Yes | Yes | Yes | Yes | Yes |
Diagnostics indication LED | |||||
● Monitoring of the supply voltage (PWR-LED) | Yes; green PWR LED | Yes; green PWR LED | Yes; green PWR LED | Yes; green PWR LED | Yes; green PWR LED |
● Channel status display | Yes; green LED | Yes; green LED | Yes; green LED | Yes; green LED | Yes; green LED |
● for channel diagnostics | No | No | No | No | No |
● for module diagnostics | Yes; green/red DIAG LED | Yes; green/red DIAG LED | Yes; green/red DIAG LED | Yes; green/red DIAG LED | Yes; green/red DIAG LED |
Potential separation | |||||
Potential separation channels | |||||
● between the channels | No | No | No | No | No |
● between the channels and backplane bus | Yes | Yes | Yes | Yes | Yes |
● between the channels and the power supply of the electronics | No | No | |||
Isolation | |||||
Isolation tested with | 707 V DC (type test) | 707 V DC (type test) | 707 V DC (type test) | 707 V DC (type test) | 707 V DC (type test) |
Standards, approvals, certificates | |||||
Suitable for safety functions | No | No | No | No | No |
Suitable for safety-related tripping of standard modules | No | Yes; see FAQ Entry ID: 39198632 | Yes; see FAQ Entry ID: 39198632 | Yes; see FAQ Entry ID: 39198632 | |
Highest safety class achievable in safety mode | |||||
● Performance level according to ISO 13849-1 | PL d | PL d | PL d | ||
● SIL acc. to IEC 61508 | SIL 2 | SIL 2 | SIL 2 | ||
Ambient conditions | |||||
Ambient temperature during operation | |||||
● horizontal installation, min. | -25 °C | -30 °C | -30 °C; < 0 °C as of FS02 | -30 °C; < 0 °C as of FS03 | -30 °C; < 0 °C as of FS02 |
● horizontal installation, max. | 60 °C | 60 °C | 60 °C | 60 °C | 60 °C |
● vertical installation, min. | -25 °C | -30 °C | -30 °C; < 0 °C as of FS02 | -30 °C; < 0 °C as of FS03 | -30 °C; < 0 °C as of FS02 |
● vertical installation, max. | 50 °C | 50 °C | 50 °C | 50 °C | 50 °C |
Altitude during operation relating to sea level | |||||
● Installation altitude above sea level, max. | 5 000 m; Restrictions for installation altitudes > 2 000 m, see manual | 5 000 m; Restrictions for installation altitudes > 2 000 m, see manual | 5 000 m; Restrictions for installation altitudes > 2 000 m, see manual | 5 000 m; Restrictions for installation altitudes > 2 000 m, see manual | 5 000 m; Restrictions for installation altitudes > 2 000 m, see manual |
Dimensions | |||||
Width | 15 mm | 15 mm | 15 mm | 15 mm | 15 mm |
Height | 73 mm | 73 mm | 73 mm | 73 mm | 73 mm |
Depth | 58 mm | 58 mm | 58 mm | 58 mm | 58 mm |
Weights | |||||
Weight, approx. | 30 g | 30 g | 30 g | 30 g | 30 g |