SIMATIC ET 200S – 1 COUNT 5 V/500 kHz Counter Module – Siemens Technology Modules

USD $ 317.60

SKU: 6ES7138-4DE02-0AB0

Siemens Technology Modules SIMATIC ET 200S Product Specifications:

Article number 6ES7138-4DE02-0AB0
ET200S, El-Mod., 1 Count 5V/500KHz
Supply voltage
Load voltage L+
● Rated value (DC) 24 V
● permissible range, lower limit (DC) 20.4 V
● permissible range, upper limit (DC) 28.8 V
● Reverse polarity protection Yes
Input current
from load voltage L+ (without load), max. 45 mA
from backplane bus 3.3 V DC, max. 10 mA
Encoder supply
24 V encoder supply
● 24 V Yes; L+ (-0.8 V)
● Short-circuit protection Yes
● Output current, max. 500 mA
Power loss
Power loss, typ. 2 W
Hardware configuration
Module exchange
● Module exchange during operation of the IM-DP Yes
● Module exchange under process voltage Yes
Digital inputs
Number of digital inputs 1
Functions Gate control, synchronization, latch function
Input characteristic curve in accordance with IEC 61131, type 2 Yes
Input voltage
● Rated value (DC) 24 V
● for signal “0” -30 to +5 V
● for signal “1” +11 to +30V
Input current
● for signal “0”, max. (permissible quiescent current) 2 mA
● for signal “1”, typ. 9 mA
Input delay (for rated value of input voltage)
for standard inputs
— at “0” to “1”, max. 2.5 µs
Cable length
● shielded, max. 50 m
Digital outputs
Number of digital outputs 2
Short-circuit protection Yes
● Response threshold, typ. 2.6 A to 4 A
Limitation of inductive shutdown voltage to L+ (-50 to -60 V)
Controlling a digital input Yes
Switching capacity of the outputs
● on lamp load, max. 10 W
Output voltage
● Rated value (DC) 24 V
● for signal “0”, max. 3 V
● for signal “1”, min. L+ (-1 V)
Output current
● for signal “1” rated value 2 A
● for signal “1” permissible range for 0 to 60 °C, min. 5 mA
● for signal “1” permissible range for 0 to 60 °C, max. 2.4 A
● for signal “0” residual current, max. 0.5 mA
Output delay with resistive load
● “0” to “1”, max. 100 µs
Switching frequency
● with resistive load, max. 100 Hz
● with inductive load, max. 2 Hz
● on lamp load, max. 10 Hz
Cable length
● shielded, max. 1 000 m
● unshielded, max. 600 m
Encoder
Number of connectable encoders, max. 1
Connectable encoders
● Incremental encoder (symmetrical) Yes
Encoder signals, incremental encoder (symmetrical)
● Trace mark signals A, notA, B, notB, A and B offset by 90°
● Zero mark signal N, notN
● Input voltage to RS-422
● Differential input voltage, min. 1 V
● Terminating resistor 330 Ω
● Input frequency, max. 650 kHz
● Cable length, shielded, max. 50 m; > 500 kHz: 30 m
Interrupts/diagnostics/status information
Diagnostics function Yes
Diagnostics indication LED
● Group error SF (red) Yes
● Status indicator digital input (green) Yes
● Status indicator digital output (green) Yes
● Status indicator forward counting (green) Yes
● Status indicator backward counting (green) Yes
● Synchronization SYN (green) Yes
Integrated Functions
Measuring functions
Measuring range
— Frequency measurement, min. 0.1 Hz
— Frequency measurement, max. 500 kHz
— Cycle duration measurement, min. 10 µs
— Cycle duration measurement, max. 120 s
— Speed measurement, min. 1 1/min
— Speed measurement, max. 25 000 1/min
Counter
Number of counter inputs 1; 32 bit
Parameter
Remark 16 byte
Potential separation
Potential separation digital inputs
● Potential separation digital inputs No; only opposite shielding
Potential separation counter
● between the channels and backplane bus Yes
● Between the channels and load voltage L+ No
Dimensions
Width 30 mm
Height 81 mm
Depth 52 mm
Weights
Weight, approx. 65 g
Weight 0.001 kg
Dimensions 6.5 × 9.3 × 3.8 cm