1. Motor Starter Circuit Overcurrent Protection
This 2-pole C-curve miniature circuit breaker protects control circuits and small single-phase motor starters from thermal overloads and high-current short circuits in industrial switchboards.
Problem SolvedAvoids nuisance tripping during motor startup due to the C-curve magnetic tripping profile (8x In ±20%), while ensuring rapid isolation in the event of a genuine short circuit.
C-curve trippingOvercurrent protectionMotor startersInductive loads
2. HVAC Fan and Pump Protection
Used in sub-distribution boards to isolate and protect 25A single-phase HVAC compressors, fans, and pump motors.
Problem SolvedProvides visual diagnostics via VisiTrip to quickly locate failed components, minimizing HVAC downtime, while VisiSafe ensures maintenance personnel can work downstream with absolute confidence of isolated contacts.
VisiTrip diagnosticVisiSafe isolationHVAC controlSub-distribution
3. DC Control Loop Isolation
Leverages the multi-standard rating of the iC60N to secure 24V to 125V DC control loops, protecting auxiliary power supplies and PLCs from downstream field faults.
Problem SolvedSafeguards sensitive DC power supplies with a rated DC breaking capacity of up to 10 kA at 72-125 V DC, ensuring that localized field device failures do not cascade into complete system blackouts.
DC breaking capacityControl loopsAuxiliary power supplyPLC protection