Schneider Electric Acti9 C60H-DC MCB

USD 135.07

2-pole, 20A C-curve thermal-magnetic DC miniature circuit breaker rated for 500V DC. Provides 6kA breaking capacity and reliable industrial circuit protection.

SKU Schneider-A9N61532 Category
Top Brands > Schneider Electric > Schneider Circuit Breakers

Schneider Electric Acti9 C60H-DC MCB

Model Identifier Acti9 C60H-DC
Official Part Number A9N61532
GTIN Standard 3606480424311

Technical Overview

2-pole, 20A C-curve thermal-magnetic DC miniature circuit breaker rated for 500V DC. Provides 6kA breaking capacity and reliable industrial circuit protection.

Key Features

  • Designed specifically for DC distribution networks with a rated operational voltage of 500 V DC [1.1.3]
  • Tripping characteristic C curve optimized for general-purpose and inductive loads (7 to 10 times In)
  • Two-pole (2P) configuration with two protected poles for comprehensive circuit isolation
  • High short-circuit breaking capacity of up to 20 kA at 220 V and 250 V DC (Icu conforming to IEC 60947-2)
  • IP20 degree of protection, rising to IP40 when installed inside a modular enclosure
  • Fast-closing mechanism independent of manual toggle speed to minimize contact wear and extend lifespan
  • Fully compatible with standard 35 mm DIN rail installations and Acti9 auxiliaries
  • Suitability for industrial isolation according to the stringent IEC/EN 60947-2 standard

Rated current of 20 A at 25 °C and operating voltage of 500 V DC, featuring a 6 kA breaking capacity at 500 V DC and up to 20 kA at 220/250 V DC.

Technical Specification Matrix

ParameterValue
Poles Description2P [1.1.3]
Number of Protected Poles2
Rated Current (In)20 A at 25 °C
Network TypeDC
Tripping Curve CodeC
Rated Operational Voltage (Ue)500 V DC
Rated Insulation Voltage (Ui)500 V DC conforming to IEC 60947-2
Rated Impulse Withstand Voltage (Uimp)6 kV conforming to IEC 60947-2
Breaking Capacity (Icu)6 kA at 500 V DC, 10 kA at 440 V DC, 20 kA at 220 V DC, 20 kA at 250 V DC
Rated Service Breaking Capacity (Ics)7.5 kA 75% of Icu at 440 V DC, 4.5 kA 75% of Icu at 500 V DC
Magnetic Tripping Limit7...10 x In
IP RatingIP20
Mechanical Durability20,000 cycles
Electrical Durability3,000 cycles L/R = 2 ms, 6,000 cycles at 500 V DC
Tightening Torque2.5 N.m top or bottom
Mounting Support35 mm symmetrical DIN rail
Physical Weight (kg)0.26
Dimensions L x W x H (cm)8.1 x 3.6 x 8.5

Industrial Applications

1. Photovoltaic String Overcurrent Protection

Used in solar energy generation installations to protect DC cabling between photovoltaic strings and inverters or combiner boxes. Operating in solar installations requires handling high open-circuit DC voltages (up to 500V DC) and protecting against reverse currents [2.3.8].

Problem Solved

Mitigates the risk of cable damage and fire caused by reverse current flow in multi-string PV arrays by providing thermal-magnetic overcurrent and short-circuit protection at voltages up to 500 V DC with a 6 kA breaking capacity.

Photovoltaic ProtectionSolar Combiner BoxDC String Protection500V DC Circuit BreakerOvercurrent Protection

2. Industrial DC Control Loop Protection

Protects 220V DC and 440V DC auxiliary control power supplies, battery charger systems, and emergency backup battery banks utilized in power substations and critical industrial plants.

Problem Solved

Ensures reliable isolation and prevents short-circuit faults from causing cascading system failures in critical DC control loops. Leverages its 20 kA breaking capacity at 220V DC / 250V DC and C-curve tripping characteristic to handle inrush currents from inductive relay coils without nuisance tripping.

DC Control CircuitBattery Charger ProtectionSubstation Auxiliary PowerThermal-Magnetic MCB220V DC Control Loop

3. DC Motor and Actuator Branch Circuit Protection

Provides overcurrent and short-circuit protection for DC motors, pumps, and actuators in material handling systems, industrial automation lines, and crane systems operating on DC distribution buses.

Problem Solved

Solves the issue of nuisance tripping during DC motor startup. The C tripping curve (7...10 times In) accommodates the high initial inductive inrush currents of DC motors rated up to 20 A while maintaining robust short-circuit defense at up to 500V DC.

DC Motor ProtectionActuator Branch CircuitC-Curve TrippingIndustrial AutomationDIN Rail DC MCB
Select your currency