RIF-0-RPT-24DC/ 1 – 2903361 – Relay Module – Phoenix Contact Solid-state Relays And Electromechanical Relays
USD 14.82
Phoenix Contact develops terminal blocks, power supplies, relays, connectors, signal conditioners, controllers & PLCs, I/O systems, Industrial Ethernet, controller system cabling, PCB terminal blocks & connectors, and surge suppression.
Commercial Data
| Item number |
2903361 |
| Packing unit |
10 pc |
| Minimum order quantity |
10 pc |
| Product key |
DK6528 |
| Catalog page |
Page 319 (C-5-2019) |
| GTIN |
4046356731997 |
| Weight per piece (including packing) |
24.7 g |
| Weight per piece (excluding packing) |
21.805 g |
| Customs tariff number |
85364110 |
| Country of origin |
CN |
Product Properties
| Product type |
Relay Module |
| Product family |
RIFLINE complete |
| Application |
Universal |
| Operating mode |
100% operating factor |
| Mechanical service life |
approx. 2x 107 cycles |
| Insulation characteristics |
| Insulation |
safe isolation |
| Overvoltage category |
III |
| Pollution degree |
2 |
| Data management status |
| Date of last data management |
21.01.2025 |
Electrical Properties
| Service life electrical |
see diagram |
| Maximum power dissipation for nominal condition |
0.22 W |
| Test voltage (Winding/contact) |
4 kVrms (50 Hz, 1 min., winding/contact) |
| Rated insulation voltage |
250 V AC |
| Rated surge voltage |
6 kV |
Input Data
| Coil side |
| Nominal input voltage UN |
24 V DC |
| Input voltage range |
19.2 V DC … 36 V DC (20 °C) |
| Input voltage range in reference to UN |
see diagram |
| Drive and function |
monostable |
| Drive (polarity) |
polarized |
| Typical input current at UN |
9 mA |
| Typical response time |
5 ms |
| Typical release time |
8 ms |
| Coil voltage |
24 V DC |
| Protective circuit |
Freewheeling diode |
| Operating voltage display |
Yellow LED |
Output Data
| Switching |
| Contact switching type |
1 N/O contact |
| Type of switch contact |
Single contact |
| Contact material |
AgSnO |
| Maximum switching voltage |
250 V AC/DC |
| Minimum switching voltage |
5 V (100 mA) |
| Limiting continuous current |
6 A |
| Maximum inrush current |
10 A (4 s) |
| Min. switching current |
10 mA (12 V) |
| Interrupting rating (ohmic load) max. |
140 W (24 V DC) |
| 20 W (48 V DC) |
| 18 W (60 V DC) |
| 23 W (110 V DC) |
| 40 W (220 V DC) |
| 1500 VA (250 V AC) |
| Utilization category CB Scheme (IEC 60947-5-1) |
AC15, 3 A/250 V (N/O contact) |
| AC15, 1 A/250 V (N/C contact) |
| DC13, 1.5 A/24 V (N/O contact) |
| DC13, 0.2 A/110 V (N/O contact) |
| DC13, 0.1 A/220 V (N/O contact) |
Connection Data
| Connection method |
Push-in connection |
| Stripping length |
8 mm |
| Conductor cross section rigid |
0.14 mm² … 1.5 mm² |
| Conductor cross section flexible |
0.14 mm² … 1.5 mm² |
| 0.14 mm² … 1.5 mm² (Ferrule with plastic sleeve) |
| Conductor cross section AWG |
24 … 16 |
Dimension
| Item dimensions |
| Width |
6.2 mm |
| Height |
93 mm |
| Depth |
66 mm |
Material Specifications
| Color |
gray (RAL 7042) |
| Flammability rating according to UL 94 |
V2 (Housing) |
Environmental and real-life conditions
| Ambient conditions |
| Degree of protection (Relay base) |
IP20 (Relay base) |
| Degree of protection (Relay) |
RT III (Relay) |
| Ambient temperature (operation) |
-40 °C … 60 °C |
| Ambient temperature (storage/transport) |
-40 °C … 85 °C |
Standards And Regulations
| Standards/regulations |
IEC 60947-5-1 |
Approvals
| Corrosive gas test |
| Identification |
ISA-S71.04. G3 Harsh Group |
| EN 60068-2-60 |
Mounting
| Mounting type |
DIN rail mounting |
| Assembly note |
in rows with zero spacing |
| Mounting position |
any |