QUINT4-PS/1AC/48DC/5 – 2904610 – Phoenix Contact Power Supply

$ 367.54

SKU: Phoenix Contact 2904610

Inosaki is one of the largest Phoenix Contact Distributors to provide terminal block, interface module, power supply and relay. And our best offer for terminal block types are Feed-through, Fuse Modular, Spring Cage, Double Level, and Multi-level, hence the series model references to  PT Series, ST Series, TB Series, UT Series, UK Series. In additional for power supply are QUINT Power, STEP Power, Trio Power, and UNO Power. Please email us for catalog: sales@inosaki.my

Product Description

The fourth generation of the high-performance QUINT POWER power supplies ensures superior system availability by means of new functions. Signaling thresholds and characteristic curves can be individually adjusted via the NFC interface.
The unique SFB technology and preventive function monitoring of the QUINT POWER power supply increase the availability of your application.

Dimensions

Article Number 2904610
Width 50 mm
Height 130 mm
Depth 125 mm
Width with alternative assembly 122 mm
Height with alternative assembly 130 mm
Depth with alternative assembly 53 mm
Installation distance right/left 5 mm / 5 mm
Installation distance top/bottom 50 mm / 50 mm

Ambient conditions

Degree of protection IP20
Inflammability class in acc. with UL 94 (housing / terminal blocks) V0
Ambient temperature (operation) -25 °C … 70 °C (> 60 °C Derating: 2,5 %/K)
Ambient temperature (start-up type tested) -40 °C
Ambient temperature (storage/transport) -40 °C … 85 °C
Max. permissible relative humidity (operation) ≤ 95 % (at 25 °C, non-condensing)
Climatic class 3K3 (in acc. with EN 60721)
Degree of pollution 2
Installation height ≤ 5000 m (> 2000 m, observe derating)

Input data

Nominal input voltage range 100 V AC … 240 V AC
110 V DC … 250 V DC
Input voltage range 100 V AC … 240 V AC -15 % … +10 %
110 V DC … 250 V DC -18 % … +40 %
Dielectric strength maximum 300 V AC 60 s
AC frequency range 50 Hz … 60 Hz -10 % … +10 %
Frequency range (fN) 50 Hz … 60 Hz -10 % … +10 %
16.7 Hz (acc. to EN 50163)
Discharge current to PE < 3.5 mA
Current consumption 3.4 A (100 V AC)
2.8 A (120 V AC)
1.5 A (230 V AC)
1.5 A (240 V AC)
Nominal power consumption 271 VA
Inrush current typ. 16 A (at 25 °C)
Mains buffering time typ. 43 ms (120 V AC)
typ. 43 ms (230 V AC)
Input fuse 8 A (slow-blow, internal)
Recommended breaker for input protection 10 A … 16 A (Characteristic B, C, D, K or comparable)
Type of protection Transient surge protection
Protective circuit/component Varistor, gas-filled surge arrester

Output data

Nominal output voltage 48 V DC
Setting range of the output voltage (USet) 48 V DC … 56 V DC (constant capacity)
Nominal output current (IN) 5 A
Static Boost (IStat.Boost) 6.25 A
Dynamic Boost (IDyn.Boost) 10 A (5 s)
Selective Fuse Breaking (ISFB) 30 A (15 ms)
Derating > 60 °C … 70 °C (2.5%/K)
Connection in parallel yes, for redundancy and increased capacity
Connection in series yes
Feedback voltage resistance ≤ 60 V DC
Protection against overvoltage at the output (OVP) ≤ 60 V DC
Control deviation < 0.5 % (Static load change 10 % … 90 %)
< 4 % (Dynamic load change 10 % … 90 %, (10 Hz))
< 0.25 % (change in input voltage ±10 %)
Residual ripple < 70 mVPP (with nominal values)
Output power 240 W
Typical response time 300 ms (from SLEEP MODE)
Maximum power dissipation in no-load condition < 3 W (120 V AC)
< 3 W (230 V AC)
Power loss nominal load max. < 19 W (120 V AC)
< 16 W (230 V AC)

General

Net weight 1 kg
Environmental protection directive RoHS Directive 2011/65/EU
WEEE
Reach
Efficiency typ. 92.3 % (120 V AC)
typ. 93.5 % (230 V AC)
MTBF (IEC 61709, SN 29500) > 1242000 h (25 °C)
> 784000 h (40 °C)
> 374000 h (60 °C)
Insulation voltage input/output 4 kV AC (type test)
2 kV AC (routine test)
Insulation voltage input / PE 3.5 kV AC (type test)
2.4 kV AC (routine test)
Insulation voltage output / PE 0.5 kV DC (type test)
0.5 kV DC (routine test)
Degree of protection IP20
Protection class I
Inflammability class in acc. with UL 94 (housing / terminal blocks) V0
Mounting position horizontal DIN rail NS 35, EN 60715
Assembly instructions alignable: PN ≥50%, 5 mm horizontally, 15 mm next to active components, 50 mm vertically
alignable: PN <50%, 0 mm horizontally, 40 mm vertically top, 20 mm vertically bottom

Connection data, input

Connection method Screw connection
Conductor cross section solid min. 0.2 mm²
Conductor cross section solid max. 2.5 mm²
Conductor cross section flexible min. 0.2 mm²
Conductor cross section flexible max. 2.5 mm²
Conductor cross section AWG min. 24
Conductor cross section AWG max. 14
Stripping length 6.5 mm

Connection data, output

Connection method Screw connection
Conductor cross section solid min. 0.2 mm²
Conductor cross section solid max. 2.5 mm²
Conductor cross section flexible min. 0.2 mm²
Conductor cross section flexible max. 2.5 mm²
Conductor cross section AWG min. 24
Conductor cross section AWG max. 14
Stripping length 6.5 mm

Connection data for signaling

Connection method Push-in connection
Conductor cross section solid min. 0.2 mm²
Conductor cross section solid max. 1 mm²
Conductor cross section flexible min. 0.2 mm²
Conductor cross section flexible max. 1.5 mm²
Conductor cross section AWG min. 24
Conductor cross section AWG max. 16
Stripping length 8 mm

Standards

EMC requirements for noise immunity EN 61000-6-1
EN 61000-6-2
EMC requirements for noise emission EN 61000-6-3
EN 61000-6-4
EMC requirements, power plant IEC 61850-3
EN 61000-6-5
HART FSK Physical Layer Test Specification Compliance Output voltage UOut compliant
Standard – Safety of transformers EN 61558-2-16
Standard – Electrical safety IEC 61010-2-201 (SELV)
Standard – safety for equipment for measurement, control, and laboratory use IEC 61010-1
Standard – Safety extra-low voltage IEC 61010-1 (SELV)
IEC 61010-2-201 (PELV)
Standard – Safe isolation IEC 61558-2-16
Standard – Limitation of mains harmonic currents EN 61000-3-2
Mains variation/undervoltage SEMI F47-0706, EN 61000-4-11
Rail applications EN 50121-3-2
EN 50121-4
EN 50121-5
IEC 62236-3-2
IEC 62236-4
IEC 62236-5
Overvoltage category EN 61010-1 II (≤ 5000 m)
Overvoltage category EN 62477-1 III (≤ 2000 m)

Conformance/approvals

UL approvals UL Listed UL 508
UL/C-UL Recognized UL 60950-1
UL ANSI/ISA-12.12.01 Class I, Division 2, Groups A, B, C, D (Hazardous Location)
CSA CAN/CSA-C22.2 No. 60950-1-07
CSA-C22.2 No. 107.1-01

EMC data

Electromagnetic compatibility Conformance with EMC Directive 2014/30/EU
Low Voltage Directive Conformance with Low Voltage Directive 2014/35/EC
Conducted noise emission EN 55016
EN 61000-6-3 (Class B)
Noise emission EN 55016
EN 61000-6-3 (Class B)
Harmonic currents EN 61000-3-2
EN 61000-3-2 (Class A)
Flicker EN 61000-3-3
EN 61000-3-3
Electrostatic discharge EN 61000-4-2
Contact discharge 8 kV (Test Level 4)
Discharge in air 15 kV (Test Level 4)
Electromagnetic HF field EN 61000-4-3
Frequency range 80 MHz … 1 GHz
Test field strength 20 V/m (Test Level 3)
Frequency range 1 GHz … 6 GHz
Test field strength 10 V/m (Test Level 3)
Frequency range 1 GHz … 6 GHz
Test field strength 10 V/m (Test Level 3)
Comments Criterion A
Fast transients (burst) EN 61000-4-4
Input 4 kV (Test Level 4 – asymmetrical)
Output 4 kV (Test Level 4 – asymmetrical)
Signal 4 kV (Test Level 4 – asymmetrical)
Comments Criterion A
Input 3 kV (Test Level 4 – symmetrical)
6 kV (Test Level 4 – asymmetrical)
Output 1 kV (Test Level 3 – symmetrical)
2 kV (Test Level 3 – asymmetrical)
Signal 4 kV (Test Level 4 – asymmetrical)
Comments Criterion A
Conducted interference EN 61000-4-6
I/O/S asymmetrical
Frequency range 0.15 MHz … 80 MHz
Voltage 10 V (Test Level 3)
Comments Criterion A
Power frequency magnetic field EN 61000-4-8
Frequency 16.7 Hz
50 Hz
60 Hz
Test field strength 100 A/m
Additional text 60 s
Comments Criterion A
Frequency 50 Hz
60 Hz
Frequency range 50 Hz … 60 Hz
Test field strength 1 kA/m
Additional text 3 s
Frequency 0 Hz
Test field strength 300 A/m
Additional text DC, 60 s
Voltage dips EN 61000-4-11
Voltage 230 V AC
Frequency 50 Hz
Voltage dip 70 %
Number of periods 0.5 / 1 / 25 periods
Additional text Test Level 2
Comments Criterion A: 0.5 / 1 / 25 periods
Voltage dip 40 %
Number of periods 5 / 10 / 50 periods
Additional text Test Level 2
Comments Criterion A
Voltage dip 0 %
Number of periods 0,5 / 1 / 5 / 50 / 250 periods
Additional text Test Level 2
Comments Criterion A: 0.5 / 1 period
Criterion B: 5 / 50 / 250 periods
Pulse-shape magnetic field EN 61000-4-9
Test field strength 1000 A/m
Comments Criterion A
Damped oscillating magnetic field EN 61000-4-10
Test field strength 110 A/m
Test level 1 100 kHz
Test field strength 110 A/m
Test level 2 1 MHz
Comments Criterion A
Attenuated sinusoidal oscillations (ring wave) EN 61000-4-12
Input 2 kV (Test Level 4 – symmetrical)
4 kV (Test Level 4 – asymmetrical)
Comments Criterion A
Asymmetrical conducted disturbance variables EN 61000-4-16
Test level 1 15 Hz 150 Hz (Test Level 4)
Voltage 30 V 3 V
Test level 2 150 Hz 1.5 kHz (Test Level 4)
Voltage 3 V
Test level 3 1.5 kHz 15 kHz (Test Level 4)
Voltage 3 V 30 V
Test level 4 15 kHz 150 kHz (Test Level 4)
Voltage 30 V
Test level 5 16.7 Hz 50 Hz 60 Hz (Test Level 4)
Voltage 30 V (Permanent)
Test level 6 16.7 Hz 50 Hz 60 Hz (Test Level 4)
Voltage 300 V (1 s)
Comments Criterion A
Attenuated oscillating wave EN 61000-4-18
Input, output (test level 1) 100 kHz 1 MHz (Test Level 3 – symmetrical)
Voltage 1 kV
Input, output (test level 2) 10 MHz
Voltage 1 kV
Input, output (test level 3) 100 kHz 1 MHz (Test Level 3 – asymmetrical)
Voltage 2.5 kV
Signals (test level 1) 100 kHz 1 MHz (Test Level 3 – symmetrical)
Voltage 1 kV
Signals (test level 2) 100 kHz 1 MHz (Test Level 3 – asymmetrical)
Voltage 2.5 kV
Comments Criterion A
Criterion A Normal operating behavior within the specified limits.
Criterion B Temporary impairment to operational behavior that is corrected by the device itself.
Criterion C Temporary adverse effects on the operating behavior, which the device corrects automatically or which can be restored by actuating the operating elements.

 

Environmental Product Compliance

REACh SVHC Lead 7439-92-1
China RoHS Environmentally Friendly Use Period = 25;