Phoenix Contact develops terminal blocks, power supplies, relays, connectors, signal conditioners, controllers & PLCs, I/O systems, Industrial Ethernet, controller system cabling, PCB terminal blocks & connectors, and surge suppression.
Commercial Data
| Item number |
2900387 |
| Packing unit |
10 pc |
| Minimum order quantity |
1 pc |
| Product key |
DK62A3 |
| Catalog page |
Page 408 (C-5-2019) |
| GTIN |
4046356506908 |
| Weight per piece (including packing) |
31.59 g |
| Weight per piece (excluding packing) |
32.33 g |
| Customs tariff number |
85364900 |
| Country of origin |
DE |
Product Properties
| Product type |
Solid-state relay module |
| Product family |
PLC-INTERFACE |
| Application |
With integrated solid-state relay |
| Operating mode |
100% operating factor |
| Insulation characteristics: Standards/regulations |
| Insulation |
Basic insulation |
| Overvoltage category |
III |
| Pollution degree |
2 |
| Data management status |
| Date of last data management |
20.03.2025 |
Electrical Properties
| Maximum power dissipation for nominal condition |
1.23 W |
| Standards/regulations |
| Rated insulation voltage |
300 V |
| Rated surge voltage |
2.5 kV |
Input Data
| Nominal input voltage UN |
220 V DC |
| Input voltage range in reference to UN |
0.8 … 1.2 |
| Input voltage range |
176 V DC … 264 V DC |
| Switching threshold “0” signal in reference to UN |
≤ 0.4 |
| Switching threshold “1” signal in reference to UN |
≥ 0.8 |
| Typical input current at UN |
3 mA |
| Typical response time |
0.4 ms |
| Typical turn-off time |
1.4 ms |
| Operating voltage display |
Yellow LED |
| Protective circuit |
Reverse polarity protection; Polarity protection diode |
| Surge protection; Varistor |
| Transmission frequency |
50 Hz |
Output Data
| Designation |
Output data |
| Contact switching type |
1 N/O contact |
| Design of digital output |
electronic |
| Output voltage range |
12 V DC … 300 V DC (Partition plate PLC-ATP must be installed for voltages larger than 250 V (L1, L2, L3) between identical terminal points in adjacent modules. Potential bridging is then carried out with FBST 8-PLC… or …FBST 500…) |
| Limiting continuous current |
1 A (see derating curve) |
| Voltage drop at max. limiting continuous current |
< 500 mV |
| Protective circuit |
Reverse polarity protection; Polarity protection diode |
| Surge protection; Varistor |
Connection Data
| Connection method |
Push-in connection |
| Stripping length |
10 mm |
| Conductor cross section rigid |
0.14 mm² … 2.5 mm² |
| Conductor cross section flexible |
0.14 mm² … 2.5 mm² |
| 0.2 mm² … 2.5 mm² (Single ferrule) |
| 2x 0.5 mm² … 1 mm² (TWIN ferrule) |
| Conductor cross section AWG |
26 … 14 |
Dimensions
| Width |
6.2 mm |
| Height |
80 mm |
| Depth |
94 mm |
Material Specifications
| Color |
gray (RAL 7042) |
| Flammability rating according to UL 94 |
V0 (Housing) |
Environmental and real-life conditions
| Ambient conditions |
| Ambient temperature (operation) |
-25 °C … 60 °C |
| Ambient temperature (storage/transport) |
-40 °C … 85 °C |
Standards And Regulations
| Standards/regulations |
| Standards/regulations |
IEC 60947-5-1 |
Approvals
| CE |
| Certificate |
CE-compliant |
| UKCA |
| Certificate |
UKCA-compliant |
| Shipbuilding approval |
| Certificate |
TAE0000196 |
| Corrosive gas test |
| Identification |
ISA-S71.04. G3 Harsh Group |
| EN 60068-2-60 |
| Shipbuilding data |
| Temperature |
D |
| Humidity |
A |
| Vibration |
B/C |
| EMC |
B |
| Enclosure |
Required protection according to the Rules shall be provided upon installation on board |
EMC Data
| Electromagnetic compatibility |
Conformance with EMC directive |
| Low Voltage Directive |
Conformance with Low Voltage Directive |
Mounting
| Mounting type |
DIN rail mounting |
| Assembly note |
in rows with zero spacing |
| Mounting position |
any |