MINI MCR-BL-PT100-I-NC – 2810489 – Temperature Measuring Transducer – Phoenix Contact Signal Conditioners And Measuring Transducers
USD 133.90
Phoenix Contact develops terminal blocks, power supplies, relays, connectors, signal conditioners, controllers & PLCs, I/O systems, Industrial Ethernet, controller system cabling, PCB terminal blocks & connectors, and surge suppression.
Commercial Data
| Item number |
2810489 |
| Packing unit |
1 pc |
| Minimum order quantity |
1 pc |
| Note |
Made to order (non-returnable) |
| Sales key |
***** |
| Product key |
DKA135 |
| GTIN |
4046356166706 |
| Weight per piece (including packing) |
67.9 g |
| Weight per piece (excluding packing) |
60.5 g |
| Customs tariff number |
85437090 |
| Country of origin |
DE |
Notes
| Utilization restriction |
| EMC note |
EMC: class A product, see manufacturer’s declaration in the download area |
Product Properties
| Product type |
Temperature transmitter |
| Product family |
MINI Analog |
| No. of channels |
1 |
| Type |
Temperature signal conditioner |
| Insulation characteristics |
| Overvoltage category |
II |
| Pollution degree |
2 |
Electrical Properties
| Step response (0–99%) |
< 500 ms |
| Maximum temperature coefficient |
< 0.02 %/K |
| Transmission error in the set measuring range |
((50 K / Δ Temp)+ 0.05)% |
| Transmission error in the full measuring range |
≤ 0.25 % |
| Electrical isolation Input/output/power supply |
| Rated insulation voltage |
50 V AC/DC |
| Test voltage |
1.5 kV AC (50 Hz, 60 s) |
| Insulation |
Basic insulation in accordance with IEC/EN 61010 |
| Supply |
| Nominal supply voltage |
24 V DC ±10 % |
| Supply voltage range |
19.2 V DC … 30 V DC |
| Max. current consumption |
< 25 mA |
| Power consumption |
< 500 mW |
Input Data
| Signal |
| Number of inputs |
1 |
| Measurement |
| Sensor types (RTD) that can be used |
Pt 100 (IEC 60751/EN 60751) |
| Temperature measuring range |
-50 °C … 200 °C |
| Temperature measuring range |
min. 50 K |
| Sensor type: |
-50 °C … 200 °C (configurable) |
| Sensor input current |
1 mA (constant) |
| Max. permissible overall conductor resistance |
10 Ω (Per cable) |
| Connection technology |
3-conductor |
Output Data
| Signal: Current |
| Configurable/programmable |
no |
| Non-load voltage |
approx. 12.5 V |
| Current output signal |
0 mA … 20 mA |
| 4 mA … 20 mA |
| Max. current output signal |
23 mA |
| Load/output load current output |
< 500 Ω (at 20 mA) |
| Ripple |
< 20 mVPP (at 500 Ω) |
Connection Data
| Connection method |
Screw connection |
| Stripping length |
12 mm |
| Screw thread |
M3 |
| Conductor cross section rigid |
0.2 mm² … 2.5 mm² |
| Conductor cross section flexible |
0.2 mm² … 2.5 mm² |
| Conductor cross section AWG |
26 … 12 |
Dimension
| Width |
6.2 mm |
| Height |
93.1 mm |
| Depth |
102.5 mm |
Material Specifications
| Color |
green (RAL 6021) |
| Housing material |
PBT |
| Fire protection for rail vehicles (DIN EN 45545-2) R22 |
HL 1 – HL 2 |
| Fire protection for rail vehicles (DIN EN 45545-2) R23 |
HL 1 – HL 2 |
| Fire protection for rail vehicles (DIN EN 45545-2) R24 |
HL 1 – HL 2 |
Environmental and real-life conditions
| Ambient conditions |
| Degree of protection |
IP20 |
| Ambient temperature (operation) |
-10 °C … 60 °C |
| Ambient temperature (storage/transport) |
-20 °C … 65 °C |
Approvals
| CE |
| Certificate |
CE-compliant |
| UKCA |
| Certificate |
UKCA-compliant |
EMC Data
| Electromagnetic compatibility |
Conformance with EMC directive |
| Noise immunity |
EN 61000-6-2:2005 |
| Noise emission |
| Standards/regulations |
EN 61000-6-4 |
| Electrostatic discharge |
| Comments |
Safety measures must be taken to prevent electrostatic discharge. |
Mounting
| Mounting type |
DIN rail mounting |
| Mounting position |
any |