EasyPact D3N – LC1N – 3 Poles (3NO) Contactor, 95A – Schneider Contactors & Reversing Contactors

USD $ 64.68

SKU: N/A

Specifications

Main
Part Number LC1N95B5N LC1N95CC5N LC1N95E5N LC1N95F5N
Product Series Compact Compact Compact Compact
product type Contactor Contactor Contactor Contactor
product short name LC1N LC1N LC1N LC1N
Application field of contactor Applied to non-inductive or micro-inductive loads, and
resistance furnaces to AC loads with a power factor greater than or equal to 0.95
Applied to non-inductive or micro-inductive loads, and
resistance furnaces to AC loads with a power factor greater than or equal to 0.95
Applied to AC loads with power factor greater than or equal to 0.95
Applied to non-inductive or slightly inductive loads, resistance furnaces
Applied to non-inductive or micro-inductive loads, and
resistance furnaces to AC loads with a power factor greater than or equal to 0.95
use category AC-3
AC-1
AC-4
AC-4
AC-1
AC-3
AC-3
AC-4
AC-1
AC-3
AC-4
AC-1
number of poles 3P 3P 3P 3P
Rated working voltage [Ue] Power circuit: <= 690 V AC 50/60 Hz Power circuit: <= 690 V AC 50/60 Hz Power circuit: <= 690 V AC 50/60 Hz Power circuit: <= 690 V AC 50/60 Hz
Rated operating current [Ie] 95 A 60 °C) at <= 440 V AC AC-3 for power circuit
110 A 60 °C) at <= 440 V AC AC-1 for power circuit
44 A 60 °C) at< = 440 V AC AC-4 for power circuits
95 A 60 °C) at <= 440 V AC AC-3 for power circuit
110 A 60 °C) at <= 440 V AC AC-1 for power circuit
44 A 60 °C) at< = 440 V AC AC-4 for power circuits
95 A 60 °C) at <= 440 V AC AC-3 for power circuit
110 A 60 °C) at <= 440 V AC AC-1 for power circuit
44 A 60 °C) at< = 440 V AC AC-4 for power circuits
95 A 60 °C) at <= 440 V AC AC-3 for power circuit
110 A 60 °C) at <= 440 V AC AC-1 for power circuit
44 A 60 °C) at< = 440 V AC AC-4 for power circuits
[Uc] control circuit voltage 24 V AC 50 Hz 36V AC 50Hz 48V AC 50Hz 110V AC 50Hz
Additional information
Motor power (kW) 45 kW at 660/690 V AC 50/60 Hz
55 kW at 500 V AC 50/60 Hz
25 kW at 220/230 V AC 50/60 Hz
45 kW at 380/400 V AC 50/60 Hz
45 kW at 415/440 V AC 50/60 Hz
45 kW at 660/690 V AC 50/60 Hz
55 kW at 500 V AC 50/60 Hz
25 kW at 220/230 V AC 50/60 Hz
45 kW at 380/400 V AC 50/60 Hz
45 kW at 415/440 V AC 50/60 Hz
45 kW at 660/690 V AC 50/60 Hz
55 kW at 500 V AC 50/60 Hz
25 kW at 220/230 V AC 50/60 Hz
45 kW at 380/400 V AC 50/60 Hz
45 kW at 415/440 V AC 50/60 Hz
45 kW at 660/690 V AC 50/60 Hz
55 kW at 500 V AC 50/60 Hz
25 kW at 220/230 V AC 50/60 Hz
45 kW at 380/400 V AC 50/60 Hz
45 kW at 415/440 V AC 50/60 Hz
Loop contact type 3 NO 3 NO 3 NO 3 NO
Conventional thermal current [Ith] 110 A at <60 °C for power circuits 110 A at <60 °C for power circuits 110 A at <60 °C for power circuits 110 A at <60 °C for power circuits
Rated making capacity [Irms] 950 A at 440 V AC for power circuits according to IEC 60947-4-1
140 A AC for auxiliary contacts according to IEC 60947-5-1
950 A at 440 V AC for power circuits according to IEC 60947-4-1
140 A AC for auxiliary contacts according to IEC 60947-5-1
950 A at 440 V AC for power circuits according to IEC 60947-4-1
140 A AC for auxiliary contacts according to IEC 60947-5-1
950 A at 440 V AC for power circuits according to IEC 60947-4-1
140 A AC for auxiliary contacts according to IEC 60947-5-1
Rated breaking capacity 760 A at 440 V for power circuits conforming to IEC 60947 760 A at 440 V for power circuits conforming to IEC 60947 760 A at 440 V for power circuits conforming to IEC 60947 760 A at 440 V for power circuits conforming to IEC 60947
Rated short-time withstand current [Icw] 135 A for power circuits at <40 °C – 600 s
800 A for power circuits at <40 °C – 10 s
400 A for power circuits at <40 °C – 60 s
135 A for power circuits at <40 °C – 600 s
800 A for power circuits at <40 °C – 10 s
400 A for power circuits at <40 °C – 60 s
135 A for power circuits at <40 °C – 600 s
800 A for power circuits at <40 °C – 10 s
400 A for power circuits at <40 °C – 60 s
135 A for power circuits at <40 °C – 600 s
800 A for power circuits at <40 °C – 10 s
400 A for power circuits at <40 °C – 60 s
Fuses for use with relays 10 A gG at <= 690 V for type 1 suitable control circuits conforming to IEC 60947-5-1
160 A gG at <= 690 V for type 1 suitable power circuits
10 A gG at <= 690 V for type 1 suitable control circuits conforming to IEC 60947-5-1
160 A gG at <= 690 V for type 1 suitable power circuits
10 A gG at <= 690 V for type 1 suitable control circuits conforming to IEC 60947-5-1
160 A gG at <= 690 V for type 1 suitable power circuits
10 A gG at <= 690 V for type 1 suitable control circuits conforming to IEC 60947-5-1
160 A gG at <= 690 V for type 1 suitable power circuits
average impedance 0.8 mΩ – Ith 120 A 50 Hz for power circuits 0.8 mΩ – Ith 120 A 50 Hz for power circuits 0.8 mΩ – Ith 120 A 50 Hz for power circuits 0.8 mΩ – Ith 120 A 50 Hz for power circuits
power consumption per pole 7.2W AC-3
12W AC-1
7.2W AC-3
12W AC-1
7.2W AC-3
12W AC-1
7.2W AC-3
12W AC-1
Rated insulation voltage [Ui] 690 V conforming to IEC 60947-4-1 690 V conforming to IEC 60947-4-1 690 V conforming to IEC 60947-4-1 690 V conforming to IEC 60947-4-1
Overvoltage category III III III III
pollution level 3 3 3 3
Rated impulse withstand voltage [Uimp] 6 kV coil not connected to power circuit conforming to IEC 60947 6 kV coil not connected to power circuit conforming to IEC 60947 6 kV coil not connected to power circuit conforming to IEC 60947 6 kV coil not connected to power circuit conforming to IEC 60947
Mechanical life 300000 times 300000 times 300000 times 300000 times
Electrical life 350,000 AC-1
900,000 AC-3
150,000 AC-4
350,000 AC-1
900,000 AC-3
150,000 AC-4
350,000 AC-1
900,000 AC-3
150,000 AC-4
350,000 AC-1
900,000 AC-3
150,000 AC-4
Control loop characteristics AC at 50 Hz AC at 50 Hz AC at 50 Hz AC at 50 Hz
Control voltage limit 0.85…1.1 Uc 55 °C run 50 Hz
0.3…0.6 Uc 55 °C release 50 Hz
0.85…1.1 Uc 55 °C run 50 Hz
0.3…0.6 Uc 55 °C release 50 Hz
0.85…1.1 Uc 55 °C run 50 Hz
0.3…0.6 Uc 55 °C release 50 Hz
0.85…1.1 Uc 55 °C run 50 Hz
0.3…0.6 Uc 55 °C release 50 Hz
(~50Hz pickup) power consumption (VA) 200VA 50Hz (0.75 20°C) 200VA 50Hz (0.75 20°C) 200VA 50Hz (0.75 20°C) 200VA 50Hz (0.75 20°C)
(~50Hz hold) power consumption (VA) 20VA 50Hz 0.3 20°C) 20VA 50Hz 0.3 20°C) 20VA 50Hz 0.3 20°C) 20VA 50Hz 0.3 20°C)
heat dissipation 6…10 W for control circuits 6…10 W for control circuits 6…10 W for control circuits 6…10 W for control circuits
action time 20…35 ms off
6…30 ms on opening
20…35 ms off
6…30 ms on opening
20…35 ms off
6…30 ms on opening
20…35 ms off
6…30 ms on opening
operating frequency 1200 cycles/h at <60 °C 1200 cycles/h at <60 °C 1200 cycles/h at <60 °C 1200 cycles/h at <60 °C
Wiring capacity Control circuit: Bolt fastening1 1…4 mm² Cable selection: Flexible cord without wire terminals
Control circuit: Bolt fastening2 1…4 mm² Cable selection: Flexible cord without wire terminal
Control circuit: Bolt fastening 2 1…2.5 mm² cable option: flexible cable with wire terminals
control circuit: screw-on1 1…4 mm² cable option: rigid without cable terminal
control circuit: screw-on2 1…4 mm² cable option Type: Solid without wire terminals
Control circuit: Bolt tight1 1…2.5 mm² Cable selection: Flexible wire with wire terminals
Power circuit: Bolt fastened1 4…50 mm² Cable selection: Flexible wire with wire Terminals
Power circuit: screw-on2 4…16 mm² Cable option: flexible with wire terminal
Power circuit: screw-on1 4…50 mm² Cable option: solid without cable terminal
Power circuit: screw-on 2 4…25 mm² Cable option: solid without cable terminals
Control circuit: Bolt fastening1 1…4 mm² Cable selection: Flexible cord without wire terminals
Control circuit: Bolt fastening2 1…4 mm² Cable selection: Flexible cord without wire terminal
Control circuit: Bolt fastening 2 1…2.5 mm² cable option: flexible cable with wire terminals
control circuit: screw-on1 1…4 mm² cable option: rigid without cable terminal
control circuit: screw-on2 1…4 mm² cable option Type: Solid without wire terminals
Control circuit: Bolt tight1 1…2.5 mm² Cable selection: Flexible wire with wire terminals
Power circuit: Bolt fastened1 4…50 mm² Cable selection: Flexible wire with wire Terminals
Power circuit: screw-on2 4…16 mm² Cable option: flexible with wire terminal
Power circuit: screw-on1 4…50 mm² Cable option: solid without cable terminal
Power circuit: screw-on 2 4…25 mm² Cable option: solid without cable terminals
Control circuit: Bolt fastening1 1…4 mm² Cable selection: Flexible cord without wire terminals
Control circuit: Bolt fastening2 1…4 mm² Cable selection: Flexible cord without wire terminal
Control circuit: Bolt fastening 2 1…2.5 mm² cable option: flexible cable with wire terminals
control circuit: screw-on1 1…4 mm² cable option: rigid without cable terminal
control circuit: screw-on2 1…4 mm² cable option Type: Solid without wire terminals
Control circuit: Bolt tight1 1…2.5 mm² Cable selection: Flexible wire with wire terminals
Power circuit: Bolt fastened1 4…50 mm² Cable selection: Flexible wire with wire Terminals
Power circuit: screw-on2 4…16 mm² Cable option: flexible with wire terminal
Power circuit: screw-on1 4…50 mm² Cable option: solid without cable terminal
Power circuit: screw-on 2 4…25 mm² Cable option: solid without cable terminals
Control circuit: Bolt fastening1 1…4 mm² Cable selection: Flexible cord without wire terminals
Control circuit: Bolt fastening2 1…4 mm² Cable selection: Flexible cord without wire terminal
Control circuit: Bolt fastening 2 1…2.5 mm² cable option: flexible cable with wire terminals
control circuit: screw-on1 1…4 mm² cable option: rigid without cable terminal
control circuit: screw-on2 1…4 mm² cable option Type: Solid without wire terminals
Control circuit: Bolt tight1 1…2.5 mm² Cable selection: Flexible wire with wire terminals
Power circuit: Bolt fastened1 4…50 mm² Cable selection: Flexible wire with wire Terminals
Power circuit: screw-on2 4…16 mm² Cable option: flexible with wire terminal
Power circuit: screw-on1 4…50 mm² Cable option: solid without cable terminal
Power circuit: screw-on 2 4…25 mm² Cable option: solid without cable terminals
Tightening torque Control circuit: 1.2 Nm
Power circuit: 12 Nm
Control circuit: 1.2 Nm
Power circuit: 12 Nm
Control circuit: 1.2 Nm
Power circuit: 12 Nm
Control circuit: 1.2 Nm
Power circuit: 12 Nm
Auxiliary contact type 1 NO + 1 NC 1 NO + 1 NC 1 NO + 1 NC 1 NO + 1 NC
Minimum switching voltage 17 V for control circuits 17 V for control circuits 17 V for control circuits 17 V for control circuits
Minimum switching current [Imin] 5 mA for control loop 5 mA for control loop 5 mA for control loop 5 mA for control loop
Insulation resistance > 10 MΩ for control loops > 10 MΩ for control loops > 10 MΩ for control loops > 10 MΩ for control loops
non-overlapping time 1.5 ms power-on to ensure NC and NO contact
1.5 ms power-off to ensure NC and NO contact
1.5 ms power-on to ensure NC and NO contact
1.5 ms power-off to ensure NC and NO contact
1.5 ms power-on to ensure NC and NO contact
1.5 ms power-off to ensure NC and NO contact
1.5 ms power-on to ensure NC and NO contact
1.5 ms power-off to ensure NC and NO contact
installation method Chassis mounting
DIN rail mounting
DIN rail mount
chassis mount
Chassis mounting
DIN rail mounting
DIN rail mount
chassis mount
environment
standard GB 14048.4
EN 60947-4-1
IEC 60947-4-1
IEC 60947-1
EN 60947-1
IEC 60947-4-1
EN 60947-4-1
IEC 60947-1
GB 14048.4
EN 60947-1
IEC 60947-1
IEC 60947-4-1
EN 60947-1
GB 14048.4
EN 60947-4-1
EN 60947-4-1
EN 60947-1
IEC 60947-1
GB 14048.4
IEC 60947-4-1
certified product CCC CCC CCC CCC
IP protection class IP20 conforming to IEC 60529 IP20 conforming to IEC 60529 IP20 conforming to IEC 60529 IP20 conforming to IEC 60529
Protective measures TH (pollution degree 3) conforming to IEC 60068 TH (pollution degree 3) conforming to IEC 60068 TH (pollution degree 3) conforming to IEC 60068 TH (pollution degree 3) conforming to IEC 60068
ambient air temperature -20…70 °C (allowed at Uc)
-60…80 °C storage
-5…55 °C operation
-20…70 °C (allowed at Uc)
-60…80 °C storage
-5…55 °C operation
-20…70 °C (allowed at Uc)
-60…80 °C storage
-5…55 °C operation
-20…70 °C (allowed at Uc)
-60…80 °C storage
-5…55 °C operation
working altitude 3000 m None 3000 m None 3000 m None 3000 m None
Fire resistance and abnormal high temperature resistance 850 °C conforming to IEC 60695-2-1 850 °C conforming to IEC 60695-2-1 850 °C conforming to IEC 60695-2-1 850 °C conforming to IEC 60695-2-1
Shock and vibration resistance Shock resistance with contacts open (1.5 gn (5…300 Hz))
shock resistance with contacts closed (3 gn (5…300 Hz))
shock resistance with contacts open (6 gn (11ms))
shock resistance Performance Contact closed state (7 gn (11ms))
Shock resistance with contacts open (1.5 gn (5…300 Hz))
shock resistance with contacts closed (3 gn (5…300 Hz))
shock resistance with contacts open (6 gn (11ms))
shock resistance Performance Contact closed state (7 gn (11ms))
Shock resistance with contacts open (1.5 gn (5…300 Hz))
shock resistance with contacts closed (3 gn (5…300 Hz))
shock resistance with contacts open (6 gn (11ms))
shock resistance Performance Contact closed state (7 gn (11ms))
Shock resistance with contacts open (1.5 gn (5…300 Hz))
shock resistance with contacts closed (3 gn (5…300 Hz))
shock resistance with contacts open (6 gn (11ms))
shock resistance Performance Contact closed state (7 gn (11ms))
high 127 mm 127mm 127mm 127 mm
width 85 mm 85 mm 85 mm 85 mm
depth 121mm 121 mm 121 mm 121mm
Product Weight 1.52kg 1.52kg 1.52kg 1.52kg
packaging unit
Unit Type of Package 1 PCE PCE PCE PCE
Number of Units in Package 1 1 1 1 1
Package 1 Height 15cm 15cm 15cm 15cm
Package 1 Width 11.1 cm 11.1 cm 11.1 cm 11.1 cm
Package 1 Length 16cm 16cm 16cm 16cm
Package 1 Weight 1554.7g 1556.7g 1557g 1552.7g
contract warranty
Warranty 18 months 18 months 18 months 18 months

 

Main
Part Number LC1N95M5N LC1N95Q5N
Product Series Compact Compact
product type Contactor Contactor
product short name LC1N LC1N
Application field of contactor Applied to non-inductive or micro-inductive loads, and
resistance furnaces to AC loads with a power factor greater than or equal to 0.95
Applied to AC loads with power factor greater than or equal to 0.95
Applied to non-inductive or slightly inductive loads, resistance furnaces
use category AC-4
AC-1
AC-3
AC-3
AC-1
AC-4
number of poles 3P 3P
Rated working voltage [Ue] Power circuit: <= 690 V AC 50/60 Hz Power circuit: <= 690 V AC 50/60 Hz
Rated operating current [Ie] 95 A 60 °C) at <= 440 V AC AC-3 for power circuit
110 A 60 °C) at <= 440 V AC AC-1 for power circuit
44 A 60 °C) at< = 440 V AC AC-4 for power circuits
95 A 60 °C) at <= 440 V AC AC-3 for power circuit
110 A 60 °C) at <= 440 V AC AC-1 for power circuit
44 A 60 °C) at< = 440 V AC AC-4 for power circuits
[Uc] control circuit voltage 230V AC 50Hz 380V AC 50Hz
Additional information
Motor power (kW) 45 kW at 660/690 V AC 50/60 Hz
55 kW at 500 V AC 50/60 Hz
25 kW at 220/230 V AC 50/60 Hz
45 kW at 380/400 V AC 50/60 Hz
45 kW at 415/440 V AC 50/60 Hz
45 kW at 660/690 V AC 50/60 Hz
55 kW at 500 V AC 50/60 Hz
25 kW at 220/230 V AC 50/60 Hz
45 kW at 380/400 V AC 50/60 Hz
45 kW at 415/440 V AC 50/60 Hz
Loop contact type 3 NO 3 NO
Conventional thermal current [Ith] 110 A at <60 °C for power circuits 110 A at <60 °C for power circuits
Rated making capacity [Irms] 950 A at 440 V AC for power circuits according to IEC 60947-4-1
140 A AC for auxiliary contacts according to IEC 60947-5-1
950 A at 440 V AC for power circuits according to IEC 60947-4-1
140 A AC for auxiliary contacts according to IEC 60947-5-1
Rated breaking capacity 760 A at 440 V for power circuits conforming to IEC 60947 760 A at 440 V for power circuits conforming to IEC 60947
Rated short-time withstand current [Icw] 135 A for power circuits at <40 °C – 600 s
800 A for power circuits at <40 °C – 10 s
400 A for power circuits at <40 °C – 60 s
135 A for power circuits at <40 °C – 600 s
800 A for power circuits at <40 °C – 10 s
400 A for power circuits at <40 °C – 60 s
Fuses for use with relays 10 A gG at <= 690 V for type 1 suitable control circuits conforming to IEC 60947-5-1
160 A gG at <= 690 V for type 1 suitable power circuits
10 A gG at <= 690 V for type 1 suitable control circuits conforming to IEC 60947-5-1
160 A gG at <= 690 V for type 1 suitable power circuits
average impedance 0.8 mΩ – Ith 120 A 50 Hz for power circuits 0.8 mΩ – Ith 120 A 50 Hz for power circuits
power consumption per pole 7.2W AC-3
12W AC-1
7.2W AC-3
12W AC-1
Rated insulation voltage [Ui] 690 V conforming to IEC 60947-4-1 690 V conforming to IEC 60947-4-1
Overvoltage category III III
pollution level 3 3
Rated impulse withstand voltage [Uimp] 6 kV coil not connected to power circuit conforming to IEC 60947 6 kV coil not connected to power circuit conforming to IEC 60947
Mechanical life 300000 times 300000 times
Electrical life 350,000 AC-1
900,000 AC-3
150,000 AC-4
350,000 AC-1
900,000 AC-3
150,000 AC-4
Control loop characteristics AC at 50 Hz AC at 50 Hz
Control voltage limit 0.85…1.1 Uc 55 °C run 50 Hz
0.3…0.6 Uc 55 °C release 50 Hz
0.85…1.1 Uc 55 °C run 50 Hz
0.3…0.6 Uc 55 °C release 50 Hz
(~50Hz pickup) power consumption (VA) 200VA 50Hz (0.75 20°C) 200VA 50Hz (0.75 20°C)
(~50Hz hold) power consumption (VA) 20VA 50Hz 0.3 20°C) 20VA 50Hz 0.3 20°C)
heat dissipation 6…10 W for control circuits 6…10 W for control circuits
action time 20…35 ms off
6…30 ms on opening
20…35 ms off
6…30 ms on opening
operating frequency 1200 cycles/h at <60 °C 1200 cycles/h at <60 °C
Wiring capacity Control circuit: Bolt fastening1 1…4 mm² Cable selection: Flexible cord without wire terminals
Control circuit: Bolt fastening2 1…4 mm² Cable selection: Flexible cord without wire terminal
Control circuit: Bolt fastening 2 1…2.5 mm² cable option: flexible cable with wire terminals
control circuit: screw-on1 1…4 mm² cable option: rigid without cable terminal
control circuit: screw-on2 1…4 mm² cable option Type: Solid without wire terminals
Control circuit: Bolt tight1 1…2.5 mm² Cable selection: Flexible wire with wire terminals
Power circuit: Bolt fastened1 4…50 mm² Cable selection: Flexible wire with wire Terminals
Power circuit: screw-on2 4…16 mm² Cable option: flexible with wire terminal
Power circuit: screw-on1 4…50 mm² Cable option: solid without cable terminal
Power circuit: screw-on 2 4…25 mm² Cable option: solid without cable terminals
Control circuit: Bolt fastening1 1…4 mm² Cable selection: Flexible cord without wire terminals
Control circuit: Bolt fastening2 1…4 mm² Cable selection: Flexible cord without wire terminal
Control circuit: Bolt fastening 2 1…2.5 mm² cable option: flexible cable with wire terminals
control circuit: screw-on1 1…4 mm² cable option: rigid without cable terminal
control circuit: screw-on2 1…4 mm² cable option Type: Solid without wire terminals
Control circuit: Bolt tight1 1…2.5 mm² Cable selection: Flexible wire with wire terminals
Power circuit: Bolt fastened1 4…50 mm² Cable selection: Flexible wire with wire Terminals
Power circuit: screw-on2 4…16 mm² Cable option: flexible with wire terminal
Power circuit: screw-on1 4…50 mm² Cable option: solid without cable terminal
Power circuit: screw-on 2 4…25 mm² Cable option: solid without cable terminals
Tightening torque Control circuit: 1.2 Nm
Power circuit: 12 Nm
Control circuit: 1.2 Nm
Power circuit: 12 Nm
Auxiliary contact type 1 NO + 1 NC 1 NO + 1 NC
Minimum switching voltage 17 V for control circuits 17 V for control circuits
Minimum switching current [Imin] 5 mA for control loop 5 mA for control loop
Insulation resistance > 10 MΩ for control loops > 10 MΩ for control loops
non-overlapping time 1.5 ms power-on to ensure NC and NO contact
1.5 ms power-off to ensure NC and NO contact
1.5 ms power-on to ensure NC and NO contact
1.5 ms power-off to ensure NC and NO contact
installation method Chassis mounting
DIN rail mounting
DIN rail mount
chassis mount
environment
standard IEC 60947-4-1
IEC 60947-1
EN 60947-4-1
GB 14048.4
EN 60947-1
EN 60947-4-1
IEC 60947-1
GB 14048.4
IEC 60947-4-1
EN 60947-1
certified product CCC CCC
IP protection class IP20 conforming to IEC 60529 IP20 conforming to IEC 60529
Protective measures TH (pollution degree 3) conforming to IEC 60068 TH (pollution degree 3) conforming to IEC 60068
ambient air temperature -20…70 °C (allowed at Uc)
-60…80 °C storage
-5…55 °C operation
-20…70 °C (allowed at Uc)
-60…80 °C storage
-5…55 °C operation
working altitude 3000 m None 3000 m None
Fire resistance and abnormal high temperature resistance 850 °C conforming to IEC 60695-2-1 850 °C conforming to IEC 60695-2-1
Shock and vibration resistance Shock resistance with contacts open (1.5 gn (5…300 Hz))
shock resistance with contacts closed (3 gn (5…300 Hz))
shock resistance with contacts open (6 gn (11ms))
shock resistance Performance Contact closed state (7 gn (11ms))
Shock resistance with contacts open (1.5 gn (5…300 Hz))
shock resistance with contacts closed (3 gn (5…300 Hz))
shock resistance with contacts open (6 gn (11ms))
shock resistance Performance Contact closed state (7 gn (11ms))
high 127 mm 127 mm
width 85 mm 85 mm
depth 121mm 121 mm
Product Weight 1.52kg 1.52kg
packaging unit
Unit Type of Package 1 PCE PCE
Number of Units in Package 1 1 1
Package 1 Height 11.25cm 11.296 cm
Package 1 Width 15.35cm 15.276 cm
Package 1 Length 15.8 cm 15.657 cm
Package 1 Weight 1.571kg 1.55kg
Unit Type of Package 2 CAR CAR
Number of Units in Package 2 5 5
Package 2 Height 19.3 cm 19.0cm
Package 2 Width 29.4 cm 29.6 cm
Package 2 Length 41.0 cm 40.5cm
Package 2 Weight 8.261kg 8.221 kg
contract warranty
Warranty 18 months 18 months

 

Weight N/A
Dimensions N/A