EasyPact D3N – LC1N – 3 Poles (3NO) Contactor, 25A – Schneider Contactors & Reversing Contactors

USD $ 13.86USD $ 14.49

SKU: N/A

Specifications

Main
Part Number LC1N2501B5N LC1N2501CC5N LC1N2501E5N LC1N2501F5N
Product Series Compact Compact Compact Compact
product type Contactor Contactor Contactor Contactor
product short name LC1N LC1N LC1N LC1N
Application field of contactor Applied to AC loads with power factor greater than or equal to 0.95
Applied to non-inductive or slightly inductive loads, resistance furnaces
Applied to non-inductive or micro-inductive loads, and
resistance furnaces to AC loads with a power factor greater than or equal to 0.95
Applied to non-inductive or micro-inductive loads, and
resistance furnaces to AC loads with a power factor greater than or equal to 0.95
Applied to non-inductive or micro-inductive loads, and
resistance furnaces to AC loads with a power factor greater than or equal to 0.95
use category AC-3
AC-1
AC-4
AC-4
AC-1
AC-3
AC-3
AC-4
AC-1
AC-3
AC-1
AC-4
number of poles 3P 3P 3P 3P
Rated working voltage [Ue] Power circuit: <= 690 V AC 50/60 Hz Power circuit: <= 690 V AC 50/60 Hz Power circuit: <= 690 V AC 50/60 Hz Power circuit: <= 690 V AC 50/60 Hz
Rated operating current [Ie] 25 A 60 °C) at <= 440 V AC AC-3 for power circuit
32 A 60 °C) at <= 440 V AC AC-1 for power circuit
8.5 A 60 °C) at < = 440 V AC AC-4 for power circuits
25 A 60 °C) at <= 440 V AC AC-3 for power circuit
32 A 60 °C) at <= 440 V AC AC-1 for power circuit
8.5 A 60 °C) at < = 440 V AC AC-4 for power circuits
25 A 60 °C) at <= 440 V AC AC-3 for power circuit
32 A 60 °C) at <= 440 V AC AC-1 for power circuit
8.5 A 60 °C) at < = 440 V AC AC-4 for power circuits
25 A 60 °C) at <= 440 V AC AC-3 for power circuit
32 A 60 °C) at <= 440 V AC AC-1 for power circuit
8.5 A 60 °C) at < = 440 V AC AC-4 for power circuits
[Uc] control circuit voltage 24 V AC 50 Hz 36V AC 50Hz 48V AC 50Hz 110V AC 50Hz
Additional information
Motor power (kW) 5.5 kW at 220/230 V AC 50/60 Hz
11 kW at 380/400 V AC 50/60 Hz
11 kW at 415/440 V AC 50/60 Hz
15 kW at 500 V AC 50/60 Hz
15 kW at 660/690 V AC 50/60 Hz
5.5 kW at 220/230 V AC 50/60 Hz
11 kW at 380/400 V AC 50/60 Hz
11 kW at 415/440 V AC 50/60 Hz
15 kW at 500 V AC 50/60 Hz
15 kW at 660/690 V AC 50/60 Hz
5.5 kW at 220/230 V AC 50/60 Hz
11 kW at 380/400 V AC 50/60 Hz
11 kW at 415/440 V AC 50/60 Hz
15 kW at 500 V AC 50/60 Hz
15 kW at 660/690 V AC 50/60 Hz
5.5 kW at 220/230 V AC 50/60 Hz
11 kW at 380/400 V AC 50/60 Hz
11 kW at 415/440 V AC 50/60 Hz
15 kW at 500 V AC 50/60 Hz
15 kW at 660/690 V AC 50/60 Hz
Loop contact type 3 NO 3 NO 3 NO 3 NO
Conventional thermal current [Ith] 32 A at <60 °C for power circuits 32 A at <60 °C for power circuits 32 A at <60 °C for power circuits 32 A at <60 °C for power circuits
Rated making capacity [Irms] 250 A at 440 V AC for power circuits according to IEC 60947-4-1
140 A AC for auxiliary contacts according to IEC 60947-5-1
250 A at 440 V AC for power circuits according to IEC 60947-4-1
140 A AC for auxiliary contacts according to IEC 60947-5-1
250 A at 440 V AC for power circuits according to IEC 60947-4-1
140 A AC for auxiliary contacts according to IEC 60947-5-1
250 A at 440 V AC for power circuits according to IEC 60947-4-1
140 A AC for auxiliary contacts according to IEC 60947-5-1
Rated breaking capacity 200 A at 440 V for power circuits conforming to IEC 60947 200 A at 440 V for power circuits conforming to IEC 60947 200 A at 440 V for power circuits conforming to IEC 60947 200 A at 440 V for power circuits conforming to IEC 60947
Rated short-time withstand current [Icw] 240 A at <40 °C – 10 s for power circuits
120 A at <40 °C – 60 s for power circuits
50 A at <40 °C – 600 s for power circuits
240 A at <40 °C – 10 s for power circuits
120 A at <40 °C – 60 s for power circuits
50 A at <40 °C – 600 s for power circuits
240 A at <40 °C – 10 s for power circuits
120 A at <40 °C – 60 s for power circuits
50 A at <40 °C – 600 s for power circuits
240 A at <40 °C – 10 s for power circuits
120 A at <40 °C – 60 s for power circuits
50 A at <40 °C – 600 s for power circuits
Fuses for use with relays 10 A gG at <= 690 V for type 1 suitable control circuits conforming to IEC 60947-5-1
40 A gG at <= 690 V for type 1 suitable power circuits
10 A gG at <= 690 V for type 1 suitable control circuits conforming to IEC 60947-5-1
40 A gG at <= 690 V for type 1 suitable power circuits
10 A gG at <= 690 V for type 1 suitable control circuits conforming to IEC 60947-5-1
40 A gG at <= 690 V for type 1 suitable power circuits
10 A gG at <= 690 V for type 1 suitable control circuits conforming to IEC 60947-5-1
40 A gG at <= 690 V for type 1 suitable power circuits
average impedance 2.5 mΩ – Ith 36 A 50 Hz for power loop 2.5 mΩ – Ith 36 A 50 Hz for power loop 2.5 mΩ – Ith 36 A 50 Hz for power loop 2.5 mΩ – Ith 36 A 50 Hz for power loop
power consumption per pole 1.6W AC-3
3.2W AC-1
1.6W AC-3
3.2W AC-1
1.6W AC-3
3.2W AC-1
1.6W AC-3
3.2W AC-1
Rated insulation voltage [Ui] 690 V conforming to IEC 60947-4-1 690 V conforming to IEC 60947-4-1 690 V conforming to IEC 60947-4-1 690 V conforming to IEC 60947-4-1
Overvoltage category III III III III
pollution level 3 3 3 3
Rated impulse withstand voltage [Uimp] 6 kV coil not connected to power circuit conforming to IEC 60947 6 kV coil not connected to power circuit conforming to IEC 60947 6 kV coil not connected to power circuit conforming to IEC 60947 6 kV coil not connected to power circuit conforming to IEC 60947
Mechanical life 10000000 times 10000000 times 10000000 times 10000000 times
Electrical life 1,200,000 AC-3
350,000 AC-1
200,000 AC-4
1,200,000 AC-3
350,000 AC-1
200,000 AC-4
1,200,000 AC-3
350,000 AC-1
200,000 AC-4
1,200,000 AC-3
350,000 AC-1
200,000 AC-4
Control loop characteristics AC at 50 Hz AC at 50 Hz AC at 50 Hz AC at 50 Hz
Control voltage limit 0.85…1.1 Uc 55 °C run 50 Hz
0.3…0.6 Uc 55 °C release 50 Hz
0.85…1.1 Uc 55 °C run 50 Hz
0.3…0.6 Uc 55 °C release 50 Hz
0.85…1.1 Uc 55 °C run 50 Hz
0.3…0.6 Uc 55 °C release 50 Hz
0.85…1.1 Uc 55 °C run 50 Hz
0.3…0.6 Uc 55 °C release 50 Hz
(~50Hz pickup) power consumption (VA) 95 VA 50 Hz (0.75 20 °C) 95 VA 50 Hz (0.75 20 °C) 95 VA 50 Hz (0.75 20 °C) 95 VA 50 Hz (0.75 20 °C)
(~50Hz hold) power consumption (VA) 8.3 VA 50 Hz (0.3 20 °C) 8.3 VA 50 Hz (0.3 20 °C) 8.3 VA 50 Hz (0.3 20 °C) 8.3 VA 50 Hz (0.3 20 °C)
heat dissipation 2…3 W for control circuits 2…3 W for control circuits 2…3 W for control circuits 2…3 W for control circuits
action time 12…22 ms off
4…19 ms on opening
12…22 ms off
4…19 ms on opening
12…22 ms off
4…19 ms on opening
12…22 ms off
4…19 ms on opening
operating frequency 1800 cycles/h at <60 °C 1800 cycles/h at <60 °C 1800 cycles/h at <60 °C 1800 cycles/h at <60 °C
Wiring capacity Control circuit: Bolt fastening1 1…4 mm² Cable selection: Flexible cord without wire terminals
Control circuit: Bolt fastening2 1…4 mm² Cable selection: Flexible cord without wire terminal
Control circuit: Bolt fastening 1 1…4 mm² cable option: flexible cable with wire terminals
control circuit: screw-on1 1…4 mm² cable option: rigid without cable terminal
control circuit: screw-on2 cable option 1…4 mm² Type: Solid without wire terminals
Power circuit: Bolt-on1 1.5…6 mm² Cable option: Solid without wire terminals
Power circuit: Bolt-on2 1.5…6 mm² Cable option: Hard without Cable terminal
Power circuit: screw-on1 1…6 mm² Cable option: flexible cable with cable terminal Power
circuit: screw-on2 1…4 mm² Cable option: flexible cable with cable terminal
Control circuit: screw-on Solid 2 1…4 mm² Cable selection: Flexible with cable terminals
Control circuit: Bolt fastening1 1…4 mm² Cable selection: Flexible cord without wire terminals
Control circuit: Bolt fastening2 1…4 mm² Cable selection: Flexible cord without wire terminal
Control circuit: Bolt fastening 1 1…4 mm² cable option: flexible cable with wire terminals
control circuit: screw-on1 1…4 mm² cable option: rigid without cable terminal
control circuit: screw-on2 cable option 1…4 mm² Type: Solid without wire terminals
Power circuit: Bolt-on1 1.5…6 mm² Cable option: Solid without wire terminals
Power circuit: Bolt-on2 1.5…6 mm² Cable option: Hard without Cable terminal
Power circuit: screw-on1 1…6 mm² Cable option: flexible cable with cable terminal Power
circuit: screw-on2 1…4 mm² Cable option: flexible cable with cable terminal
Control circuit: screw-on Solid 2 1…4 mm² Cable selection: Flexible with cable terminals
Control circuit: Bolt fastening1 1…4 mm² Cable selection: Flexible cord without wire terminals
Control circuit: Bolt fastening2 1…4 mm² Cable selection: Flexible cord without wire terminal
Control circuit: Bolt fastening 1 1…4 mm² cable option: flexible cable with wire terminals
control circuit: screw-on1 1…4 mm² cable option: rigid without cable terminal
control circuit: screw-on2 cable option 1…4 mm² Type: Solid without wire terminals
Power circuit: Bolt-on1 1.5…6 mm² Cable option: Solid without wire terminals
Power circuit: Bolt-on2 1.5…6 mm² Cable option: Hard without Cable terminal
Power circuit: screw-on1 1…6 mm² Cable option: flexible cable with cable terminal Power
circuit: screw-on2 1…4 mm² Cable option: flexible cable with cable terminal
Control circuit: screw-on Solid 2 1…4 mm² Cable selection: Flexible with cable terminals
Control circuit: Bolt fastening1 1…4 mm² Cable selection: Flexible cord without wire terminals
Control circuit: Bolt fastening2 1…4 mm² Cable selection: Flexible cord without wire terminal
Control circuit: Bolt fastening 1 1…4 mm² cable option: flexible cable with wire terminals
control circuit: screw-on1 1…4 mm² cable option: rigid without cable terminal
control circuit: screw-on2 cable option 1…4 mm² Type: Solid without wire terminals
Power circuit: Bolt-on1 1.5…6 mm² Cable option: Solid without wire terminals
Power circuit: Bolt-on2 1.5…6 mm² Cable option: Hard without Cable terminal
Power circuit: screw-on1 1…6 mm² Cable option: flexible cable with cable terminal Power
circuit: screw-on2 1…4 mm² Cable option: flexible cable with cable terminal
Control circuit: screw-on Solid 2 1…4 mm² Cable selection: Flexible with cable terminals
Tightening torque Control circuit: 1.2 Nm
Power circuit: 1.7 Nm
Control circuit: 1.2 Nm
Power circuit: 1.7 Nm
Control circuit: 1.2 Nm
Power circuit: 1.7 Nm
Control circuit: 1.2 Nm
Power circuit: 1.7 Nm
Auxiliary contact type 1 NC 1 NC 1 NC 1 NC
Minimum switching voltage 17 V for control circuits 17 V for control circuits 17 V for control circuits 17 V for control circuits
Minimum switching current [Imin] 5 mA for control loop 5 mA for control loop 5 mA for control loop 5 mA for control loop
Insulation resistance > 10 MΩ for control loops > 10 MΩ for control loops > 10 MΩ for control loops > 10 MΩ for control loops
non-overlapping time 1.5 ms power-on to ensure NC and NO contact
1.5 ms power-off to ensure NC and NO contact
1.5 ms power-on to ensure NC and NO contact
1.5 ms power-off to ensure NC and NO contact
1.5 ms power-on to ensure NC and NO contact
1.5 ms power-off to ensure NC and NO contact
1.5 ms power-on to ensure NC and NO contact
1.5 ms power-off to ensure NC and NO contact
installation method Chassis mounting
DIN rail mounting
DIN rail mount
chassis mount
Chassis mounting
DIN rail mounting
Chassis mounting
DIN rail mounting
environment
standard EN 60947-4-1
EN 60947-1
IEC 60947-1
IEC 60947-4-1
GB 14048.4
IEC 60947-4-1
IEC 60947-1
EN 60947-1
EN 60947-4-1
GB 14048.4
EN 60947-4-1
IEC 60947-4-1
EN 60947-1
IEC 60947-1
GB 14048.4
IEC 60947-1
GB 14048.4
EN 60947-1
EN 60947-4-1
IEC 60947-4-1
certified product CCC CCC CCC CCC
IP protection class IP20 conforming to IEC 60529 IP20 conforming to IEC 60529 IP20 conforming to IEC 60529 IP20 conforming to IEC 60529
Protective measures TH (pollution degree 3) conforming to IEC 60068 TH (pollution degree 3) conforming to IEC 60068 TH (pollution degree 3) conforming to IEC 60068 TH (pollution degree 3) conforming to IEC 60068
ambient air temperature -20…70 °C (allowed at Uc)
-60…80 °C storage
-5…55 °C operation
-20…70 °C (allowed at Uc)
-60…80 °C storage
-5…55 °C operation
-20…70 °C (allowed at Uc)
-60…80 °C storage
-5…55 °C operation
-20…70 °C (allowed at Uc)
-60…80 °C storage
-5…55 °C operation
working altitude 3000 m None 3000 m None 3000 m None 3000 m None
Fire resistance and abnormal high temperature resistance 850 °C conforming to IEC 60695-2-1 850 °C conforming to IEC 60695-2-1 850 °C conforming to IEC 60695-2-1 850 °C conforming to IEC 60695-2-1
Shock and vibration resistance Shock resistance with contacts open (1.5 gn (5 … 300 Hz))
shock resistance with contacts closed (3 gn (5…300 Hz))
shock resistance with contacts closed (10 gn (11ms))
Shock performance Contact opening (6 gn (11ms))
Shock resistance with contacts open (1.5 gn (5 … 300 Hz))
shock resistance with contacts closed (3 gn (5…300 Hz))
shock resistance with contacts closed (10 gn (11ms))
Shock performance Contact opening (6 gn (11ms))
Shock resistance with contacts open (1.5 gn (5 … 300 Hz))
shock resistance with contacts closed (3 gn (5…300 Hz))
shock resistance with contacts closed (10 gn (11ms))
Shock performance Contact opening (6 gn (11ms))
Shock resistance with contacts open (1.5 gn (5 … 300 Hz))
shock resistance with contacts closed (3 gn (5…300 Hz))
shock resistance with contacts closed (10 gn (11ms))
Shock performance Contact opening (6 gn (11ms))
high 74 mm 74 mm 74 mm 74 mm
width 45 mm 45 mm 45 mm 45 mm
depth 85 mm 85 mm 85 mm 85 mm
Product Weight 0.36kg 0.36kg 0.36kg 0.36kg
packaging unit
Unit Type of Package 1 PCE PCE PCE PCE
Number of Units in Package 1 1 1 1 1
Package 1 Height 4.5cm 5.104 cm 4.5cm 5.11cm
Package 1 Width 7.4cm 7.5cm 7.4cm 7.578 cm
Package 1 Length 8.5cm 8.611 cm 8.5cm 8.688 cm
Package 1 Weight 360g 361.0g 360g 350.0g
contract warranty
Warranty 18 months 18 months 18 months 18 months

 

Main
Part Number LC1N2501M5N LC1N2501Q5N LC1N2510B5N LC1N2510CC5N
Product Series Compact Compact Compact Compact
product type Contactor Contactor Contactor Contactor
product short name LC1N LC1N LC1N LC1N
Application field of contactor Applied to AC loads with power factor greater than or equal to 0.95
Applied to non-inductive or slightly inductive loads, resistance furnaces
Applied to non-inductive or micro-inductive loads, and
resistance furnaces to AC loads with a power factor greater than or equal to 0.95
Applied to AC loads with power factor greater than or equal to 0.95
Applied to non-inductive or slightly inductive loads, resistance furnaces
Applied to AC loads with power factor greater than or equal to 0.95
Applied to non-inductive or slightly inductive loads, resistance furnaces
use category AC-4
AC-1
AC-3
AC-4
AC-1
AC-3
AC-3
AC-1
AC-4
AC-1
AC-4
AC-3
number of poles 3P 3P 3P 3P
Rated working voltage [Ue] Power circuit: <= 690 V AC 50/60 Hz Power circuit: <= 690 V AC 50/60 Hz Power circuit: <= 690 V AC 50/60 Hz Power circuit: <= 690 V AC 50/60 Hz
Rated operating current [Ie] 25 A 60 °C) at <= 440 V AC AC-3 for power circuit
32 A 60 °C) at <= 440 V AC AC-1 for power circuit
8.5 A 60 °C) at < = 440 V AC AC-4 for power circuits
25 A 60 °C) at <= 440 V AC AC-3 for power circuit
32 A 60 °C) at <= 440 V AC AC-1 for power circuit
8.5 A 60 °C) at < = 440 V AC AC-4 for power circuits
25 A 60 °C) at <= 440 V AC AC-3 for power circuit
32 A 60 °C) at <= 440 V AC AC-1 for power circuit
8.5 A 60 °C) at < = 440 V AC AC-4 for power circuits
25 A 60 °C) at <= 440 V AC AC-3 for power circuit
32 A 60 °C) at <= 440 V AC AC-1 for power circuit
8.5 A 60 °C) at < = 440 V AC AC-4 for power circuits
[Uc] control circuit voltage 230V AC 50Hz 380V AC 50Hz 24 V AC 50 Hz 36V AC 50Hz
Additional information
Motor power (kW) 5.5 kW at 220/230 V AC 50/60 Hz
11 kW at 380/400 V AC 50/60 Hz
11 kW at 415/440 V AC 50/60 Hz
15 kW at 500 V AC 50/60 Hz
15 kW at 660/690 V AC 50/60 Hz
5.5 kW at 220/230 V AC 50/60 Hz
11 kW at 380/400 V AC 50/60 Hz
11 kW at 415/440 V AC 50/60 Hz
15 kW at 500 V AC 50/60 Hz
15 kW at 660/690 V AC 50/60 Hz
5.5 kW at 220/230 V AC 50/60 Hz
11 kW at 380/400 V AC 50/60 Hz
11 kW at 415/440 V AC 50/60 Hz
15 kW at 500 V AC 50/60 Hz
15 kW at 660/690 V AC 50/60 Hz
5.5 kW at 220/230 V AC 50/60 Hz
11 kW at 380/400 V AC 50/60 Hz
11 kW at 415/440 V AC 50/60 Hz
15 kW at 500 V AC 50/60 Hz
15 kW at 660/690 V AC 50/60 Hz
Loop contact type 3 NO 3 NO 3 NO 3 NO
Conventional thermal current [Ith] 32 A at <60 °C for power circuits 32 A at <60 °C for power circuits 32 A at <60 °C for power circuits 32 A at <60 °C for power circuits
Rated making capacity [Irms] 250 A at 440 V AC for power circuits according to IEC 60947-4-1
140 A AC for auxiliary contacts according to IEC 60947-5-1
250 A at 440 V AC for power circuits according to IEC 60947-4-1
140 A AC for auxiliary contacts according to IEC 60947-5-1
250 A at 440 V AC for power circuits according to IEC 60947-4-1
140 A AC for auxiliary contacts according to IEC 60947-5-1
250 A at 440 V AC for power circuits according to IEC 60947-4-1
140 A AC for auxiliary contacts according to IEC 60947-5-1
Rated breaking capacity 200 A at 440 V for power circuits conforming to IEC 60947 200 A at 440 V for power circuits conforming to IEC 60947 200 A at 440 V for power circuits conforming to IEC 60947 200 A at 440 V for power circuits conforming to IEC 60947
Rated short-time withstand current [Icw] 240 A at <40 °C – 10 s for power circuits
120 A at <40 °C – 60 s for power circuits
50 A at <40 °C – 600 s for power circuits
240 A at <40 °C – 10 s for power circuits
120 A at <40 °C – 60 s for power circuits
50 A at <40 °C – 600 s for power circuits
240 A at <40 °C – 10 s for power circuits
120 A at <40 °C – 60 s for power circuits
50 A at <40 °C – 600 s for power circuits
240 A at <40 °C – 10 s for power circuits
120 A at <40 °C – 60 s for power circuits
50 A at <40 °C – 600 s for power circuits
Fuses for use with relays 10 A gG at <= 690 V for type 1 suitable control circuits conforming to IEC 60947-5-1
40 A gG at <= 690 V for type 1 suitable power circuits
10 A gG at <= 690 V for type 1 suitable control circuits conforming to IEC 60947-5-1
40 A gG at <= 690 V for type 1 suitable power circuits
10 A gG at <= 690 V for type 1 suitable control circuits conforming to IEC 60947-5-1
40 A gG at <= 690 V for type 1 suitable power circuits
10 A gG at <= 690 V for type 1 suitable control circuits conforming to IEC 60947-5-1
40 A gG at <= 690 V for type 1 suitable power circuits
average impedance 2.5 mΩ – Ith 36 A 50 Hz for power loop 2.5 mΩ – Ith 36 A 50 Hz for power loop 2.5 mΩ – Ith 36 A 50 Hz for power loop 2.5 mΩ – Ith 36 A 50 Hz for power loop
power consumption per pole 1.6W AC-3
3.2W AC-1
1.6W AC-1
2.5W AC-3
1.6W AC-1
2.5W AC-3
1.6W AC-1
2.5W AC-3
Rated insulation voltage [Ui] 690 V conforming to IEC 60947-4-1 690 V conforming to IEC 60947-4-1 690 V conforming to IEC 60947-4-1 690 V conforming to IEC 60947-4-1
Overvoltage category III III III III
pollution level 3 3 3 3
Rated impulse withstand voltage [Uimp] 6 kV coil not connected to power circuit conforming to IEC 60947 6 kV coil not connected to power circuit conforming to IEC 60947 6 kV coil not connected to power circuit conforming to IEC 60947 6 kV coil not connected to power circuit conforming to IEC 60947
Mechanical life 10000000 times 10000000 times 10000000 times 10000000 times
Electrical life 1,200,000 AC-3
350,000 AC-1
200,000 AC-4
1,200,000 AC-3
350,000 AC-1
200,000 AC-4
1,200,000 AC-3
350,000 AC-1
200,000 AC-4
1,200,000 AC-3
350,000 AC-1
200,000 AC-4
Control loop characteristics AC at 50 Hz AC at 50 Hz AC at 50 Hz AC at 50 Hz
Control voltage limit 0.85…1.1 Uc 55 °C run 50 Hz
0.3…0.6 Uc 55 °C release 50 Hz
0.85…1.1 Uc 55 °C run 50 Hz
0.3…0.6 Uc 55 °C release 50 Hz
0.85…1.1 Uc 55 °C run 50 Hz
0.3…0.6 Uc 55 °C release 50 Hz
0.85…1.1 Uc 55 °C run 50 Hz
0.3…0.6 Uc 55 °C release 50 Hz
(~50Hz pickup) power consumption (VA) 95 VA 50 Hz (0.75 20 °C) 95 VA 50 Hz (0.75 20 °C) 95 VA 50 Hz (0.75 20 °C) 95 VA 50 Hz (0.75 20 °C)
(~50Hz hold) power consumption (VA) 8.3 VA 50 Hz (0.3 20 °C) 8.3 VA 50 Hz (0.3 20 °C) 8.3 VA 50 Hz (0.3 20 °C) 8.3 VA 50 Hz (0.3 20 °C)
heat dissipation 2…3 W for control circuits 2…3 W for control circuits 2…3 W for control circuits 2…3 W for control circuits
action time 12…22 ms off
4…19 ms on opening
12…22 ms off
4…19 ms on opening
12…22 ms off
4…19 ms on opening
12…22 ms off
4…19 ms on opening
operating frequency 1800 cycles/h at <60 °C 1800 cycles/h at <60 °C 1800 cycles/h at <60 °C 1800 cycles/h at <60 °C
Wiring capacity Control circuit: Bolt fastening1 1…4 mm² Cable selection: Flexible cord without wire terminals
Control circuit: Bolt fastening2 1…4 mm² Cable selection: Flexible cord without wire terminal
Control circuit: Bolt fastening 1 1…4 mm² cable option: flexible cable with wire terminals
control circuit: screw-on1 1…4 mm² cable option: rigid without cable terminal
control circuit: screw-on2 cable option 1…4 mm² Type: Solid without wire terminals
Power circuit: Bolt-on1 1.5…6 mm² Cable option: Solid without wire terminals
Power circuit: Bolt-on2 1.5…6 mm² Cable option: Hard without Cable terminal
Power circuit: screw-on1 1…6 mm² Cable option: flexible cable with cable terminal Power
circuit: screw-on2 1…4 mm² Cable option: flexible cable with cable terminal
Control circuit: screw-on Solid 2 1…4 mm² Cable selection: Flexible with cable terminals
Control circuit: Bolt fastening1 1…4 mm² Cable selection: Flexible cord without wire terminals
Control circuit: Bolt fastening2 1…4 mm² Cable selection: Flexible cord without wire terminal
Control circuit: Bolt fastening 1 1…4 mm² cable option: flexible cable with wire terminals
control circuit: screw-on1 1…4 mm² cable option: rigid without cable terminal
control circuit: screw-on2 cable option 1…4 mm² Type: Solid without wire terminals
Power circuit: Bolt-on1 1.5…6 mm² Cable option: Solid without wire terminals
Power circuit: Bolt-on2 1.5…6 mm² Cable option: Hard without Cable terminal
Power circuit: screw-on1 1…6 mm² Cable option: flexible cable with cable terminal Power
circuit: screw-on2 1…4 mm² Cable option: flexible cable with cable terminal
Control circuit: screw-on Solid 2 1…4 mm² Cable selection: Flexible with cable terminals
Control circuit: Bolt fastening1 1…4 mm² Cable selection: Flexible cord without wire terminals
Control circuit: Bolt fastening2 1…4 mm² Cable selection: Flexible cord without wire terminal
Control circuit: Bolt fastening 1 1…4 mm² cable option: flexible cable with wire terminals
control circuit: screw-on1 1…4 mm² cable option: rigid without cable terminal
control circuit: screw-on2 cable option 1…4 mm² Type: Solid without wire terminals
Power circuit: Bolt-on1 1.5…6 mm² Cable option: Solid without wire terminals
Power circuit: Bolt-on2 1.5…6 mm² Cable option: Hard without Cable terminal
Power circuit: screw-on1 1…6 mm² Cable option: flexible cable with cable terminal Power
circuit: screw-on2 1…4 mm² Cable option: flexible cable with cable terminal
Control circuit: screw-on Solid 2 1…4 mm² Cable selection: Flexible with cable terminals
Control circuit: Bolt fastening1 1…4 mm² Cable selection: Flexible cord without wire terminals
Control circuit: Bolt fastening2 1…4 mm² Cable selection: Flexible cord without wire terminal
Control circuit: Bolt fastening 1 1…4 mm² cable option: flexible cable with wire terminals
control circuit: screw-on1 1…4 mm² cable option: rigid without cable terminal
control circuit: screw-on2 cable option 1…4 mm² Type: Solid without wire terminals
Power circuit: Bolt-on1 1.5…6 mm² Cable option: Solid without wire terminals
Power circuit: Bolt-on2 1.5…6 mm² Cable option: Hard without Cable terminal
Power circuit: screw-on1 1…6 mm² Cable option: flexible cable with cable terminal Power
circuit: screw-on2 1…4 mm² Cable option: flexible cable with cable terminal
Control circuit: screw-on Solid 2 1…4 mm² Cable selection: Flexible with cable terminals
Tightening torque Control circuit: 1.2 Nm
Power circuit: 1.7 Nm
Control circuit: 1.2 Nm
Power circuit: 1.7 Nm
Control circuit: 1.2 Nm
Power circuit: 1.7 Nm
Control circuit: 1.2 Nm
Power circuit: 1.7 Nm
Auxiliary contact type 1 NC 1 NC 1 NO 1 NO
Minimum switching voltage 17 V for control circuits 17 V for control circuits 17 V for control circuits 17 V for control circuits
Minimum switching current [Imin] 5 mA for control loop 5 mA for control loop 5 mA for control loop 5 mA for control loop
Insulation resistance > 10 MΩ for control loops > 10 MΩ for control loops > 10 MΩ for control loops > 10 MΩ for control loops
non-overlapping time 1.5 ms power-on to ensure NC and NO contact
1.5 ms power-off to ensure NC and NO contact
1.5 ms power-on to ensure NC and NO contact
1.5 ms power-off to ensure NC and NO contact
1.5 ms power-on to ensure NC and NO contact
1.5 ms power-off to ensure NC and NO contact
1.5 ms power-on to ensure NC and NO contact
1.5 ms power-off to ensure NC and NO contact
installation method Chassis mounting
DIN rail mounting
Chassis mounting
DIN rail mounting
DIN rail mount
chassis mount
Chassis mounting
DIN rail mounting
environment
standard IEC 60947-4-1
EN 60947-4-1
IEC 60947-1
EN 60947-1
GB 14048.4
IEC 60947-1
EN 60947-1
IEC 60947-4-1
EN 60947-4-1
GB 14048.4
GB 14048.4
EN 60947-4-1
IEC 60947-4-1
EN 60947-1
IEC 60947-1
IEC 60947-4-1
EN 60947-1
GB 14048.4
IEC 60947-1
EN 60947-4-1
certified product CCC CCC CCC CCC
IP protection class IP20 conforming to IEC 60529 IP20 conforming to IEC 60529 IP20 conforming to IEC 60529 IP20 conforming to IEC 60529
Protective measures TH (pollution degree 3) conforming to IEC 60068 TH (pollution degree 3) conforming to IEC 60068 TH (pollution degree 3) conforming to IEC 60068 TH (pollution degree 3) conforming to IEC 60068
ambient air temperature -20…70 °C (allowed at Uc)
-60…80 °C storage
-5…55 °C operation
-20…70 °C (allowed at Uc)
-60…80 °C storage
-5…55 °C operation
-20…70 °C (allowed at Uc)
-60…80 °C storage
-5…55 °C operation
-20…70 °C (allowed at Uc)
-60…80 °C storage
-5…55 °C operation
working altitude 3000 m None 3000 m None 3000 m None 3000 m None
Fire resistance and abnormal high temperature resistance 850 °C conforming to IEC 60695-2-1 850 °C conforming to IEC 60695-2-1 850 °C conforming to IEC 60695-2-1 850 °C conforming to IEC 60695-2-1
Shock and vibration resistance Shock resistance with contacts open (1.5 gn (5 … 300 Hz))
shock resistance with contacts closed (3 gn (5…300 Hz))
shock resistance with contacts closed (10 gn (11ms))
Shock performance Contact opening (6 gn (11ms))
Shock resistance with contacts open (1.5 gn (5…300 Hz))
shock resistance with contacts closed (3 gn (5…300 Hz)) shock
resistance with contacts closed (10 gn (11ms))
Shock performance Contact opening (6 gn (11ms))
Shock resistance with contacts open (1.5 gn (5…300 Hz))
shock resistance with contacts closed (3 gn (5…300 Hz)) shock
resistance with contacts closed (10 gn (11ms))
Shock performance Contact opening (6 gn (11ms))
Shock resistance with contacts open (1.5 gn (5 … 300 Hz))
shock resistance with contacts closed (3 gn (5…300 Hz))
shock resistance with contacts closed (10 gn (11ms))
Shock performance Contact opening (6 gn (11ms))
high 74 mm 74 mm 74 mm 74 mm
width 45 mm 45 mm 45 mm 45 mm
depth 85 mm 85 mm 85 mm 85 mm
Product Weight 0.36kg 0.36kg 0.36kg 0.36kg
packaging unit
Unit Type of Package 1 PCE PCE PCE PCE
Number of Units in Package 1 1 1 1 1
Package 1 Height 4.983 cm 4.5cm 4.922 cm 4.5cm
Package 1 Width 7.605 cm 7.4cm 7.472 cm 7.4cm
Package 1 Length 8.719 cm 8.5cm 8.71cm 8.5cm
Package 1 Weight 350.0g 360g 367.0g 360g
Unit Type of Package 2 S02 CAR
Number of Units in Package 2 36 36
Package 2 Height 15.0cm 15.0cm
Package 2 Width 30.0cm 29.5cm
Package 2 Length 40.0cm 39.5 cm
Package 2 Weight 13.221kg 13.5 kg
Unit Type of Package 3 PAL PAL
Number of Units in Package 3 576 576
Package 3 Height 60.0cm 60.0cm
Package 3 Width 80.0cm 80.0cm
Package 3 Length 60.0cm 60.0cm
Package 3 Weight 214.144 kg 214.144 kg
contract warranty
Warranty 18 months 18 months 18 months 18 months

 

Main
Part Number LC1N2510E5N LC1N2510F5N LC1N2510M5N LC1N2510Q5N
Product Series Compact Compact Compact Compact
product type Contactor Contactor Contactor Contactor
product short name LC1N LC1N LC1N LC1N
Application field of contactor Applied to non-inductive or micro-inductive loads, and
resistance furnaces to AC loads with a power factor greater than or equal to 0.95
Applied to non-inductive or micro-inductive loads, and
resistance furnaces to AC loads with a power factor greater than or equal to 0.95
Applied to non-inductive or micro-inductive loads, and
resistance furnaces to AC loads with a power factor greater than or equal to 0.95
Applied to AC loads with power factor greater than or equal to 0.95
Applied to non-inductive or slightly inductive loads, resistance furnaces
use category AC-3
AC-4
AC-1
AC-3
AC-4
AC-1
AC-4
AC-1
AC-3
AC-3
AC-4
AC-1
number of poles 3P 3P 3P 3P
Rated working voltage [Ue] Power circuit: <= 690 V AC 50/60 Hz Power circuit: <= 690 V AC 50/60 Hz Power circuit: <= 690 V AC 50/60 Hz Power circuit: <= 690 V AC 50/60 Hz
Rated operating current [Ie] 25 A 60 °C) at <= 440 V AC AC-3 for power circuit
32 A 60 °C) at <= 440 V AC AC-1 for power circuit
8.5 A 60 °C) at < = 440 V AC AC-4 for power circuits
25 A 60 °C) at <= 440 V AC AC-3 for power circuit
32 A 60 °C) at <= 440 V AC AC-1 for power circuit
8.5 A 60 °C) at < = 440 V AC AC-4 for power circuits
25 A 60 °C) at <= 440 V AC AC-3 for power circuit
32 A 60 °C) at <= 440 V AC AC-1 for power circuit
8.5 A 60 °C) at < = 440 V AC AC-4 for power circuits
25 A 60 °C) at <= 440 V AC AC-3 for power circuit
32 A 60 °C) at <= 440 V AC AC-1 for power circuit
8.5 A 60 °C) at < = 440 V AC AC-4 for power circuits
[Uc] control circuit voltage 48V AC 50Hz 110V AC 50Hz 230V AC 50Hz 380V AC 50Hz
Additional information
Motor power (kW) 5.5 kW at 220/230 V AC 50/60 Hz
11 kW at 380/400 V AC 50/60 Hz
11 kW at 415/440 V AC 50/60 Hz
15 kW at 500 V AC 50/60 Hz
15 kW at 660/690 V AC 50/60 Hz
5.5 kW at 220/230 V AC 50/60 Hz
11 kW at 380/400 V AC 50/60 Hz
11 kW at 415/440 V AC 50/60 Hz
15 kW at 500 V AC 50/60 Hz
15 kW at 660/690 V AC 50/60 Hz
5.5 kW at 220/230 V AC 50/60 Hz
11 kW at 380/400 V AC 50/60 Hz
11 kW at 415/440 V AC 50/60 Hz
15 kW at 500 V AC 50/60 Hz
15 kW at 660/690 V AC 50/60 Hz
5.5 kW at 220/230 V AC 50/60 Hz
11 kW at 380/400 V AC 50/60 Hz
11 kW at 415/440 V AC 50/60 Hz
15 kW at 500 V AC 50/60 Hz
15 kW at 660/690 V AC 50/60 Hz
Loop contact type 3 NO 3 NO 3 NO 3 NO
Conventional thermal current [Ith] 32 A at <60 °C for power circuits 32 A at <60 °C for power circuits 32 A at <60 °C for power circuits 32 A at <60 °C for power circuits
Rated making capacity [Irms] 250 A at 440 V AC for power circuits according to IEC 60947-4-1
140 A AC for auxiliary contacts according to IEC 60947-5-1
250 A at 440 V AC for power circuits according to IEC 60947-4-1
140 A AC for auxiliary contacts according to IEC 60947-5-1
250 A at 440 V AC for power circuits according to IEC 60947-4-1
140 A AC for auxiliary contacts according to IEC 60947-5-1
250 A at 440 V AC for power circuits according to IEC 60947-4-1
140 A AC for auxiliary contacts according to IEC 60947-5-1
Rated breaking capacity 200 A at 440 V for power circuits conforming to IEC 60947 200 A at 440 V for power circuits conforming to IEC 60947 200 A at 440 V for power circuits conforming to IEC 60947 200 A at 440 V for power circuits conforming to IEC 60947
Rated short-time withstand current [Icw] 240 A at <40 °C – 10 s for power circuits
120 A at <40 °C – 60 s for power circuits
50 A at <40 °C – 600 s for power circuits
240 A at <40 °C – 10 s for power circuits
120 A at <40 °C – 60 s for power circuits
50 A at <40 °C – 600 s for power circuits
240 A at <40 °C – 10 s for power circuits
120 A at <40 °C – 60 s for power circuits
50 A at <40 °C – 600 s for power circuits
240 A at <40 °C – 10 s for power circuits
120 A at <40 °C – 60 s for power circuits
50 A at <40 °C – 600 s for power circuits
Fuses for use with relays 10 A gG at <= 690 V for type 1 suitable control circuits conforming to IEC 60947-5-1
40 A gG at <= 690 V for type 1 suitable power circuits
10 A gG at <= 690 V for type 1 suitable control circuits conforming to IEC 60947-5-1
40 A gG at <= 690 V for type 1 suitable power circuits
10 A gG at <= 690 V for type 1 suitable control circuits conforming to IEC 60947-5-1
40 A gG at <= 690 V for type 1 suitable power circuits
10 A gG at <= 690 V for type 1 suitable control circuits conforming to IEC 60947-5-1
40 A gG at <= 690 V for type 1 suitable power circuits
average impedance 2.5 mΩ – Ith 36 A 50 Hz for power loop 2.5 mΩ – Ith 36 A 50 Hz for power loop 2.5 mΩ – Ith 36 A 50 Hz for power loop 2.5 mΩ – Ith 36 A 50 Hz for power loop
power consumption per pole 1.6W AC-1
2.5W AC-3
1.6W AC-1
2.5W AC-3
1.6W AC-1
2.5W AC-3
1.6W AC-1
2.5W AC-3
Rated insulation voltage [Ui] 690 V conforming to IEC 60947-4-1 690 V conforming to IEC 60947-4-1 690 V conforming to IEC 60947-4-1 690 V conforming to IEC 60947-4-1
Overvoltage category III III III III
pollution level 3 3 3 3
Rated impulse withstand voltage [Uimp] 6 kV coil not connected to power circuit conforming to IEC 60947 6 kV coil not connected to power circuit conforming to IEC 60947 6 kV coil not connected to power circuit conforming to IEC 60947 6 kV coil not connected to power circuit conforming to IEC 60947
Mechanical life 10000000 times 10000000 times 10000000 times 10000000 times
Electrical life 1,200,000 AC-3
350,000 AC-1
200,000 AC-4
1,200,000 AC-3
350,000 AC-1
200,000 AC-4
1,200,000 AC-3
350,000 AC-1
200,000 AC-4
1,200,000 AC-3
350,000 AC-1
200,000 AC-4
Control loop characteristics AC at 50 Hz AC at 50 Hz AC at 50 Hz AC at 50 Hz
Control voltage limit 0.85…1.1 Uc 55 °C run 50 Hz
0.3…0.6 Uc 55 °C release 50 Hz
0.85…1.1 Uc 55 °C run 50 Hz
0.3…0.6 Uc 55 °C release 50 Hz
0.85…1.1 Uc 55 °C run 50 Hz
0.3…0.6 Uc 55 °C release 50 Hz
0.85…1.1 Uc 55 °C run 50 Hz
0.3…0.6 Uc 55 °C release 50 Hz
(~50Hz pickup) power consumption (VA) 95 VA 50 Hz (0.75 20 °C) 95 VA 50 Hz (0.75 20 °C) 95 VA 50 Hz (0.75 20 °C) 95 VA 50 Hz (0.75 20 °C)
(~50Hz hold) power consumption (VA) 8.3 VA 50 Hz (0.3 20 °C) 8.3 VA 50 Hz (0.3 20 °C) 8.3 VA 50 Hz (0.3 20 °C) 8.3 VA 50 Hz (0.3 20 °C)
heat dissipation 2…3 W for control circuits 2…3 W for control circuits 2…3 W for control circuits 2…3 W for control circuits
action time 12…22 ms off
4…19 ms on opening
12…22 ms off
4…19 ms on opening
12…22 ms off
4…19 ms on opening
12…22 ms off
4…19 ms on opening
operating frequency 1800 cycles/h at <60 °C 1800 cycles/h at <60 °C 1800 cycles/h at <60 °C 1800 cycles/h at <60 °C
Wiring capacity Control circuit: Bolt fastening1 1…4 mm² Cable selection: Flexible cord without wire terminals
Control circuit: Bolt fastening2 1…4 mm² Cable selection: Flexible cord without wire terminal
Control circuit: Bolt fastening 1 1…4 mm² cable option: flexible cable with wire terminals
control circuit: screw-on1 1…4 mm² cable option: rigid without cable terminal
control circuit: screw-on2 cable option 1…4 mm² Type: Solid without wire terminals
Power circuit: Bolt-on1 1.5…6 mm² Cable option: Solid without wire terminals
Power circuit: Bolt-on2 1.5…6 mm² Cable option: Hard without Cable terminal
Power circuit: screw-on1 1…6 mm² Cable option: flexible cable with cable terminal Power
circuit: screw-on2 1…4 mm² Cable option: flexible cable with cable terminal
Control circuit: screw-on Solid 2 1…4 mm² Cable selection: Flexible with cable terminals
Control circuit: Bolt fastening1 1…4 mm² Cable selection: Flexible cord without wire terminals
Control circuit: Bolt fastening2 1…4 mm² Cable selection: Flexible cord without wire terminal
Control circuit: Bolt fastening 1 1…4 mm² cable option: flexible cable with wire terminals
control circuit: screw-on1 1…4 mm² cable option: rigid without cable terminal
control circuit: screw-on2 cable option 1…4 mm² Type: Solid without wire terminals
Power circuit: Bolt-on1 1.5…6 mm² Cable option: Solid without wire terminals
Power circuit: Bolt-on2 1.5…6 mm² Cable option: Hard without Cable terminal
Power circuit: screw-on1 1…6 mm² Cable option: flexible cable with cable terminal Power
circuit: screw-on2 1…4 mm² Cable option: flexible cable with cable terminal
Control circuit: screw-on Solid 2 1…4 mm² Cable selection: Flexible with cable terminals
Control circuit: Bolt fastening1 1…4 mm² Cable selection: Flexible cord without wire terminals
Control circuit: Bolt fastening2 1…4 mm² Cable selection: Flexible cord without wire terminal
Control circuit: Bolt fastening 1 1…4 mm² cable option: flexible cable with wire terminals
control circuit: screw-on1 1…4 mm² cable option: rigid without cable terminal
control circuit: screw-on2 cable option 1…4 mm² Type: Solid without wire terminals
Power circuit: Bolt-on1 1.5…6 mm² Cable option: Solid without wire terminals
Power circuit: Bolt-on2 1.5…6 mm² Cable option: Hard without Cable terminal
Power circuit: screw-on1 1…6 mm² Cable option: flexible cable with cable terminal Power
circuit: screw-on2 1…4 mm² Cable option: flexible cable with cable terminal
Control circuit: screw-on Solid 2 1…4 mm² Cable selection: Flexible with cable terminals
Control circuit: Bolt fastening1 1…4 mm² Cable selection: Flexible cord without wire terminals
Control circuit: Bolt fastening2 1…4 mm² Cable selection: Flexible cord without wire terminal
Control circuit: Bolt fastening 1 1…4 mm² cable option: flexible cable with wire terminals
control circuit: screw-on1 1…4 mm² cable option: rigid without cable terminal
control circuit: screw-on2 cable option 1…4 mm² Type: Solid without wire terminals
Power circuit: Bolt-on1 1.5…6 mm² Cable option: Solid without wire terminals
Power circuit: Bolt-on2 1.5…6 mm² Cable option: Hard without Cable terminal
Power circuit: screw-on1 1…6 mm² Cable option: flexible cable with cable terminal Power
circuit: screw-on2 1…4 mm² Cable option: flexible cable with cable terminal
Control circuit: screw-on Solid 2 1…4 mm² Cable selection: Flexible with cable terminals
Tightening torque Control circuit: 1.2 Nm
Power circuit: 1.7 Nm
Control circuit: 1.2 Nm
Power circuit: 1.7 Nm
Control circuit: 1.2 Nm
Power circuit: 1.7 Nm
Control circuit: 1.2 Nm
Power circuit: 1.7 Nm
Auxiliary contact type 1 NO 1 NO 1 NO 1 NO
Minimum switching voltage 17 V for control circuits 17 V for control circuits 17 V for control circuits 17 V for control circuits
Minimum switching current [Imin] 5 mA for control loop 5 mA for control loop 5 mA for control loop 5 mA for control loop
Insulation resistance > 10 MΩ for control loops > 10 MΩ for control loops > 10 MΩ for control loops > 10 MΩ for control loops
non-overlapping time 1.5 ms power-on to ensure NC and NO contact
1.5 ms power-off to ensure NC and NO contact
1.5 ms power-on to ensure NC and NO contact
1.5 ms power-off to ensure NC and NO contact
1.5 ms power-on to ensure NC and NO contact
1.5 ms power-off to ensure NC and NO contact
1.5 ms power-on to ensure NC and NO contact
1.5 ms power-off to ensure NC and NO contact
installation method DIN rail mount
chassis mount
Chassis mounting
DIN rail mounting
DIN rail mount
chassis mount
Chassis mounting
DIN rail mounting
environment
standard IEC 60947-1
EN 60947-4-1
IEC 60947-4-1
GB 14048.4
EN 60947-1
EN 60947-1
IEC 60947-1
IEC 60947-4-1
GB 14048.4
EN 60947-4-1
IEC 60947-4-1
IEC 60947-1
EN 60947-4-1
EN 60947-1
GB 14048.4
EN 60947-1
IEC 60947-4-1
EN 60947-4-1
GB 14048.4
IEC 60947-1
IP protection class IP20 conforming to IEC 60529 IP20 conforming to IEC 60529 IP20 conforming to IEC 60529 IP20 conforming to IEC 60529
Protective measures TH (pollution degree 3) conforming to IEC 60068 TH (pollution degree 3) conforming to IEC 60068 TH (pollution degree 3) conforming to IEC 60068 TH (pollution degree 3) conforming to IEC 60068
ambient air temperature -20…70 °C (allowed at Uc)
-60…80 °C storage
-5…55 °C operation
-20…70 °C (allowed at Uc)
-60…80 °C storage
-5…55 °C operation
-20…70 °C (allowed at Uc)
-60…80 °C storage
-5…55 °C operation
-20…70 °C (allowed at Uc)
-60…80 °C storage
-5…55 °C operation
working altitude 3000 m None 3000 m None 3000 m None 3000 m None
Fire resistance and abnormal high temperature resistance 850 °C conforming to IEC 60695-2-1 850 °C conforming to IEC 60695-2-1 850 °C conforming to IEC 60695-2-1 850 °C conforming to IEC 60695-2-1
Shock and vibration resistance Shock resistance with contacts open (1.5 gn (5…300 Hz))
shock resistance with contacts closed (3 gn (5…300 Hz)) shock
resistance with contacts closed (10 gn (11ms))
Shock performance Contact opening (6 gn (11ms))
Shock resistance with contacts open (1.5 gn (5 … 300 Hz))
shock resistance with contacts closed (3 gn (5…300 Hz))
shock resistance with contacts closed (10 gn (11ms))
Shock performance Contact opening (6 gn (11ms))
Shock resistance with contacts open (1.5 gn (5 … 300 Hz))
shock resistance with contacts closed (3 gn (5…300 Hz))
shock resistance with contacts closed (10 gn (11ms))
Shock performance Contact opening (6 gn (11ms))
Shock resistance with contacts open (1.5 gn (5 … 300 Hz))
shock resistance with contacts closed (3 gn (5…300 Hz))
shock resistance with contacts closed (10 gn (11ms))
Shock performance Contact opening (6 gn (11ms))
high 74 mm 74 mm 74 mm 74 mm
width 45 mm 45 mm 45 mm 45 mm
depth 85 mm 85 mm 85 mm 85 mm
Product Weight 0.36kg 0.36kg 0.36kg 0.36kg
packaging unit
Unit Type of Package 1 PCE PCE PCE PCE
Number of Units in Package 1 1 1 1 1
Package 1 Height 4.5cm 4.5cm 4.81cm 4.5cm
Package 1 Width 7.4cm 7.4cm 7.434 cm 7.4cm
Package 1 Length 8.5cm 8.5cm 8.685 cm 8.5cm
Package 1 Weight 360g 360g 360.0g 360g
contract warranty
Warranty 18 months 18 months 18 months 18 months

 

Weight N/A
Dimensions N/A