Skip to content

Contact Us:
sales@inosaki.com

SICK 1047399 DT50 Class 1 PNP 4–20 mA Laser Distance Sensor

SICK 1047399 DT50 Class 1 PNP 4–20 mA Laser Distance Sensor

USD 1,667.90

DT50-P2123 measures 200–13,000 mm at 90% remission with a class 1 red laser, one PNP output, one 4–20 mA signal, averaging settings and M12 connection.

SKU: SICK-1047399 Category:
Laser Distance Sensors - SICK Dx50

SICK DT50-P2123 PNP Analog Laser Distance Sensor

BrandSICK
Model IdentifierDT50-P2123
Official Part Number1047399

Technical Overview

The SICK DT50-P2123 measures distance to natural objects using a class 1 visible-red time-of-flight laser. Its range is 200–13,000 mm at 90% remission, 200–5,800 mm at 18% and 200–3,400 mm at 6%. One PNP output provides a switching condition and one 4–20 mA output provides a distance-related signal with 16-bit output resolution. Teaching, scaling and inversion apply to both outputs. Fast, medium and slow averaging give 15, 30 or 80 ms lateral-entry response, while continuous distance change has output time ≥2 ms. The IP65 zinc die-cast sensor has an LC display, two LEDs, a five-pin M12 connector and warm-up time up to 15 minutes.

Class 1 red laser distance sensor with target-dependent 200–13,000 mm range, one PNP output, one 4–20 mA output and fast/medium/slow averaging.

Key Features

  • 200–13,000 mm at 90% remission; 200–5,800 mm at 18%; 200–3,400 mm at 6%
  • 658 nm class 1 visible red laser; typical 15 × 15 mm spot at 10 m
  • One PNP switching output, ≤100 mA, short-circuit protected
  • One 4–20 mA analog output; load ≤300 Ω; 16-bit output resolution
  • Teach-in, scaling and inversion of digital and analog outputs
  • Fast / medium / slow averaging; 15 / 30 / 80 ms lateral-entry response
  • Output time ≥2 ms for continuous distance change
  • Distance-to-object switching; 10–1,000 mm hysteresis; multifunction laser-off/external-teach input
  • 10–30 V DC; ≤2.1 W without load; M12 five-pin connection
  • IP65 zinc die-cast housing; PMMA window; LC display and two LEDs

Transmit a distance-related current signal and a taught switching condition to external control, checking target remission, timing and analog load.

Technical Specification Matrix

ParameterValue
Functional principleTime-of-flight laser distance measurement to natural objects
Measuring range200–13,000 mm at 90% remission; 200–5,800 mm at 18%; 200–3,400 mm at 6%
Resolution1,000 µm
Repeatability≥1 mm, equivalent to 1σ; 6–90% remission; depends on averaging setting
Measurement accuracy±7 mm at 90% remission
AveragingFast / medium / slow
Response time15 / 30 / 80 ms according to averaging; lateral object entry
Output time≥2 ms for continuous distance change within measuring range
Light sourceVisible red laser; 658 nm
Laser class1; IEC 60825-1:2014 and EN 60825-1:2014
Laser pulse figuresMaximum output 120 mW; pulse duration 2.5 ns; duty cycle 1/400
Typical light spot15 × 15 mm at 10 m
Average laser service life100,000 h at +25 °C
Digital outputOne PNP output; ≤100 mA; Q short-circuit protected
Signal voltage HIGH/LOWPNP: Vs−(<2.5 V) / 0 V
Analog outputOne 4–20 mA current output; load ≤300 Ω; 16-bit output resolution
Output adjustmentTeach-in, scaling and inversion of digital and analog outputs
Switching modeDistance to object, DtO
Hysteresis10–1,000 mm
Multifunction inputLaser off / external teach / deactivated; input response ≤15 ms; HIGH=Vs, LOW≤2.5 V
Other functionsSwitch off display; reset to factory default; lock user interface
Power supply10–30 V DC, limit values; reverse-polarity protected; short-circuit-protected network maximum 8 A
Power consumption≤2.1 W without load
Ripple≤5 Vpp; remain within supply tolerances
Initialization time≤250 ms
Warm-up time≤15 min
Display and indicatorsLC display; two LEDs; orange Q1 indicator and green supply-active indicator
ConnectionM12 five-pin male connector
Pin assignment1 BN=L+; 2 WH=QA analog; 3 BU=M; 4 BK=Q digital; 5 GY=MF
Housing materialZinc die-cast metal
Window materialPMMA plastic
Mounting holesØ4.5 mm
IP ratingIP65
Protection classIII
Operating temperature−30 to +65 °C normally; −30 to +80 °C with two cooling plates; −30 to +140 °C with two cooling plates and protection filter
Storage temperature−40 to +75 °C
Relative humidity≤95%, noncondensing
Typical ambient-light immunity40,000 lx
Vibration resistanceEN 60068-2-6 and EN 60068-2-64
Shock resistanceEN 60068-2-27
MTTFD101 years
DCavg0%
Physical Weight (kg)0.2
Dimensions L x W x H (cm)5.77 × 3.61 × 7.27

Industrial Applications

1. Following a material-loop distance

A material loop can present a suitable surface within the laser’s target-dependent measuring range. The 4–20 mA output supplies a distance-related signal to an external controller, which determines how the measured position affects feed motion. Setup establishes output scale, verifies target remission and spot placement, and selects averaging to match the required response and acceptable reading variation.

Problem Solved

A continuous distance reference helps external feed-control logic monitor a material loop, with scaling and averaging chosen for the actual target and process dynamics.

Material loop Analog distance External feed control

2. Checking a presented load against a distance threshold

An inspection station can present a load surface within the verified measuring range and teach a PNP switching threshold for the expected position. External logic samples the output during the presentation window. Commissioning checks actual surface remission, distance accuracy, hysteresis and selected averaging so variations in the load and its presentation remain compatible with the required decision margin.

Problem Solved

A taught distance condition helps external inspection logic check a load position, supporting an ordinary process decision after target variation and measurement uncertainty are assessed.

Load position PNP threshold Distance inspection

3. Teaching a distance signal after a format change

A machine can present reference positions for a changed format and use the available teach-in, scaling and inversion functions to configure its analog and digital distance signals. External setup logic may use the multifunction input for teaching or laser-off behavior. Commissioning verifies the resulting output scale, switching condition and selected response mode before returning to ordinary production.

Problem Solved

Teach-in and output adjustment help commissioning staff establish distance signals for a changed format, reducing dependence on settings that were chosen for a different target position.

Format setup Output teaching Multifunction input
Select your currency